Plan Review Notes For Permit 19101464 |
Permit Number |
19101464 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-11-12 09:54:07 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19101464 | | 11/12/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M.1: THE O/A CALCULATIONS FOR THE AHU-2 RETAIL | | 100 ARE INCORRECT. PLEASE SEE TABLE 403.3.1.1 FBC M: | | 7.5 CFMS PER PERSON AND 0.12 CFMS PER SQ. FT. ARE | | REQUIRED. | | | | 2) M.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY | | AIR SYSTEM OF EACH THE 5-TON AC SYSTEM PER SECTION | | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED | | IF THE MANUFACTURER'S PERFORMANCE DATA INDICATES THE | | AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS | | OF SUPPLY AIR. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|