2019-11-12 09:54:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101464
 11/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.1: THE O/A CALCULATIONS FOR THE AHU-2 RETAIL
 100 ARE INCORRECT. PLEASE SEE TABLE 403.3.1.1 FBC M:
 7.5 CFMS PER PERSON AND 0.12 CFMS PER SQ. FT. ARE
 REQUIRED.
  
 2) M.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY
 AIR SYSTEM OF EACH THE 5-TON AC SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S PERFORMANCE DATA INDICATES THE
 AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS
 OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  