2019-11-01 07:02:14 | 11/01/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| SEC. 107.3.5.3 (12) RESIDENTIAL GAS. SUBMIT AN |
| ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| CUT SECTIONS OF PIPE PER FBC RES. SECS. G2413.4.1, |
| G2413.4.2. |
| 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 7. PLEASE LABEL THE SHUTOFF VALVE, UNION AND DRIP LEG |
| ON GAS ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3. |
| 8. A SUB ELECTRICAL PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| 9. SIGNATURE OF PERSON THE DOING THE DRAWING IN |
| ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO |
| THE FBC SEC. 107.1 GENERAL. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |