2019-11-21 12:25:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGE E-101
  
 RISER SHOWS A TAP IN THE PANEL LOCATED IN THE KITCHEN
 WHICH STATES NO MAIN. TAP IS 10' OR LESS ACCORDING TO
 THE NOTE ON THE PAGE.
 WITH NO MAIN THESE CONDUCTORS WILL BE SERVICE
 CONDUCTORS AND CODE DOES NOT ALLOW SERVICE ENTRANCE
 CONDUCTORS TO BE RUN INSIDE OF THE BUILDING.
 PLEASE EXPLAIN HOW CONDUCTORS AR TO BE PROTECTED INSIDE
 BUILDING WITH OUT OCP PROTECTION.