Notes
Date Text
2020-02-14 16:49:49BUILDING REVIEW APPROVED WITH PROVISO:
 SEE BUILDING PROVISO BY JIM WITMER ON SHEET A100 COVER
 SHEET. SEE COPY BELOW:
  
  
 ACTION: BUILDING PROVISO
  
 1) DEFERRED SUBMITTAL. SHEET M-210 INDICATES THE
 INSTALLATION OF A NEW MECHANICAL ROOF TOP EQUIPMENT
 STAND MIAMI-DADE NOA 17-1218/02. CONTRACTOR TO SUBMIT
 AT A LATER DATE, BEFORE SUBMITTING THE PRODUCT APPROVAL
 SHOW COMPLIANCE WITH:
 1A) THE ROOF TOP A/C STAND PRODUCT APPROVAL A
 MIAMI-DADE NOA 17-1218.02TO SHOW COMPLIANCE. PLEASE
 IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE
 AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 1B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  