2020-02-04 06:19:29 | 1) SHTS.A200.1 & A 500 SHOW THE DOOR IN FRONT OF THE |
| WATER CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN |
| THE WOMEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE |
| FRONT PARTITION OR IN THE SIDE WALL OR PARTITION |
| FARTHEST FROM THE WATER CLOSET PER FBC-ACCESS. |
| SEC.604.8.1.2. |
| 2) SHT. A200.1 SHOWS THE DOOR IN FRONT OF THE WATER |
| CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN THE |
| MEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE FRONT |
| PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST |
| FROM THE WATER CLOSET PER FBC-ACCESS. SEC.604.8.1.2. |
| 3) SHT. A500 - THE CLEAR FLOOR SPACE FOR THE WATER |
| CLOSET IN THE TOILET COMPARTMENTS IS SHOWN AS 48 X56 |
| INCHES. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL PER FBC-ACCESS. SEC. 604.3.1. 2ND |
| REQUEST. |
| 4) SHT. A500 - SHOW THE HEIGHT OF THE MIRROR FROM THE |
| FINISH FLOOR TO THE BOTTOM OF THE REFLECTIVE SERVICE OF |
| THE MIRROR. THE HEIGHT OF THE MIRROR SHALL COMPLY WITH |
| FBC-ACCESS. SEC.603.3. |
| 5) SHT. A500 - THE REAR WALL GRAB BAR SHALL BE 36 |
| INCHES LONG MINIMUM AND SHALL BE LOCATED IN ACCORDANCE |
| WITH FBC-ACCESS. SEC. 604.5.2. 2ND REQUEST. |
| 6) SHT. A500 - THE SEAT HEIGHT OF THE HANDICAP |
| ACCESSIBLE WATER CLOSETS SHALL COMPLY WITH FBC-ACCESS. |
| SEC. 604.4. SHOW COMPLIANCE ON THE PLANS. |
| 7) SHT. A500 - TOILET PAPER DISPENSERS IN THE |
| ACCESSIBLE TOILET COMPARTMENTS SHALL COMPY WITH |
| FBC-ACCESS. SEC.604.7. SHOW COMPLIANCE ON THE PLANS. |
| 2ND REQUEST. |
| 8) SHT. A500 - ONE OF THE URINALS IN THE MEN'S RESTROOM |
| SHALL COMPLY WITH FBC-ACCESS. SEC.605.2.SHOW COMPLIANCE |
| ON THE PLANS. 2ND REQUEST. |
| 9) SUBMIT ELEVATION DETAILS FOR ALLL HANDICAP |
| ACCESSIBLE PLUMBING FIXTURES AND COMPONENTS. WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| 10) THE LAYOUT OF THE PLUMBING FIXTURES IN THE MEN'S |
| ACCESSIBLE TOILET COMPARTMENT ON SHT. A200.1 DOES NOT |
| CORRELATE WITH THE LAYOUT ON SHT. A500. CLARIFY. |
| 11) SHT. A500 - THE STANDARD WATER CLOSET IN THE |
| WOMEN'S RESTROOM IS SHOWN AS 1' - 6" TO THE CENTERLINE |
| OF THE WATER CLOSET FROM THE SIDE PARTITION. THIS WOULD |
| LEAVE 1' - 1" FROM THE OTHER PARTITION TO THE |
| CENTERLINE. A MINIMUM OF 15 " IS REQUIRED PER |
| FBC-PLUMBING SEC.405.3.1. |
| 12) ONE OF THE STANDARD WATER CLOSET COMPARTMENTS IN |
| THE WOMEN'S RESTROOM IS SHOWN AS 4' - 5" IN DEPTH. THE |
| DEPTH OF THE STANDARD TOILET COMPARTMENTS SHALL COMPLY |
| WITH FBC-PLUMBING SEC.405.3.1. |
| 13) SHOW THE DEPTH OF ALL THE STANDARD TOILET |
| COMPARTMENTS ON THE PLANS. WPB AMEND. TO FBC SEC. |
| 107.2.1, FBC-PLUMBING SEC. 405.3.1. |
| 14) SHT. A200.1 SHOWS THE WIDTH OF ONE OF THE STANDARD |
| TOILET COMPARTMENTS AS 2' -11 1/2 INCHES WIDE AND SHT. |
| A500 SHOWS THE SAME COMPARTMENT WITH A WIDTH OF 2' - 7 |
| 1/2 INCHES WIDE. CLARIFY. |
| 15) SHT. P100 - GENERAL PLUMBING NOTE #10 B.2 - THE |
| WALL THICKNESS OF THE PIPE INSULATION FOR THE HOT WATER |
| SHALL COMPLY WITH TABLE C403.2.1 OF THE FBC- ENERGY. |
| REVISE THE NOTE. |
| 16) SHT.P.400 - A BACKFLOW PREVENTION DEVICE IS |
| REQUIRED ON THE DISHWASHERS PER FBC-PLUMBING SECS. |
| 608.2, 608.3. |
| 17) SHT.P400 SHOWS AN AIR ADMITTANCE VALVE ON THE |
| FUTURE SANITARY LINE .AIR ADMITTANCE VALVES SHALL VENT |
| ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND |
| CONNECT TO A HORIZONTAL BRANCH DRAIN. FBC-PLUMBING SEC. |
| 918.3.1. |
| 18) WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN |
| FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| PER FBC-PLUMBING SEC.918.3.1. HOW MANY FLOORS ARE IN |
| THIS BUILDING? |
| 19) THE FUTURE SANITARY LINE CANNOT BE DESIGNED AS A |
| WASTE STACK VENT PER FBC-PLUMBING SEC. 913. |
| 20) SHT. P400 - THE SANITARY RISER IS MISSING A WATER |
| CLOSET IN THE WOMEN'S RESTROOM. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 21) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE |
| RESTROOMS PER FBC- PLUMBING SEC.416.5. |
| 22) INDICATE ON THE PLANS IF THERE IS AN EXISTING |
| SERVICE SINK. IF NOT , ONE WILL BE REQUIRED. FBC_ |
| PLUMBING TABLE 403.1. |
| |