Plan Review Notes For Permit 19101300
Permit Number 19101300
Review Stop P
Sequence Number 2
Notes
Date Text
2020-02-04 06:19:291) SHTS.A200.1 & A 500 SHOW THE DOOR IN FRONT OF THE
 WATER CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN
 THE WOMEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE
 FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET PER FBC-ACCESS.
 SEC.604.8.1.2.
 2) SHT. A200.1 SHOWS THE DOOR IN FRONT OF THE WATER
 CLOSET IN THE HANDICAP ACCESSIBLE TOILET STALL IN THE
 MEN'S RESTROOM.DOORS SHALL BE LOCATED IN THE FRONT
 PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET PER FBC-ACCESS. SEC.604.8.1.2.
 3) SHT. A500 - THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET IN THE TOILET COMPARTMENTS IS SHOWN AS 48 X56
 INCHES. CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL PER FBC-ACCESS. SEC. 604.3.1. 2ND
 REQUEST.
 4) SHT. A500 - SHOW THE HEIGHT OF THE MIRROR FROM THE
 FINISH FLOOR TO THE BOTTOM OF THE REFLECTIVE SERVICE OF
 THE MIRROR. THE HEIGHT OF THE MIRROR SHALL COMPLY WITH
 FBC-ACCESS. SEC.603.3.
 5) SHT. A500 - THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND SHALL BE LOCATED IN ACCORDANCE
 WITH FBC-ACCESS. SEC. 604.5.2. 2ND REQUEST.
 6) SHT. A500 - THE SEAT HEIGHT OF THE HANDICAP
 ACCESSIBLE WATER CLOSETS SHALL COMPLY WITH FBC-ACCESS.
 SEC. 604.4. SHOW COMPLIANCE ON THE PLANS.
 7) SHT. A500 - TOILET PAPER DISPENSERS IN THE
 ACCESSIBLE TOILET COMPARTMENTS SHALL COMPY WITH
 FBC-ACCESS. SEC.604.7. SHOW COMPLIANCE ON THE PLANS.
 2ND REQUEST.
 8) SHT. A500 - ONE OF THE URINALS IN THE MEN'S RESTROOM
 SHALL COMPLY WITH FBC-ACCESS. SEC.605.2.SHOW COMPLIANCE
 ON THE PLANS. 2ND REQUEST.
 9) SUBMIT ELEVATION DETAILS FOR ALLL HANDICAP
 ACCESSIBLE PLUMBING FIXTURES AND COMPONENTS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 10) THE LAYOUT OF THE PLUMBING FIXTURES IN THE MEN'S
 ACCESSIBLE TOILET COMPARTMENT ON SHT. A200.1 DOES NOT
 CORRELATE WITH THE LAYOUT ON SHT. A500. CLARIFY.
 11) SHT. A500 - THE STANDARD WATER CLOSET IN THE
 WOMEN'S RESTROOM IS SHOWN AS 1' - 6" TO THE CENTERLINE
 OF THE WATER CLOSET FROM THE SIDE PARTITION. THIS WOULD
 LEAVE 1' - 1" FROM THE OTHER PARTITION TO THE
 CENTERLINE. A MINIMUM OF 15 " IS REQUIRED PER
 FBC-PLUMBING SEC.405.3.1.
 12) ONE OF THE STANDARD WATER CLOSET COMPARTMENTS IN
 THE WOMEN'S RESTROOM IS SHOWN AS 4' - 5" IN DEPTH. THE
 DEPTH OF THE STANDARD TOILET COMPARTMENTS SHALL COMPLY
 WITH FBC-PLUMBING SEC.405.3.1.
 13) SHOW THE DEPTH OF ALL THE STANDARD TOILET
 COMPARTMENTS ON THE PLANS. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-PLUMBING SEC. 405.3.1.
 14) SHT. A200.1 SHOWS THE WIDTH OF ONE OF THE STANDARD
 TOILET COMPARTMENTS AS 2' -11 1/2 INCHES WIDE AND SHT.
 A500 SHOWS THE SAME COMPARTMENT WITH A WIDTH OF 2' - 7
 1/2 INCHES WIDE. CLARIFY.
 15) SHT. P100 - GENERAL PLUMBING NOTE #10 B.2 - THE
 WALL THICKNESS OF THE PIPE INSULATION FOR THE HOT WATER
 SHALL COMPLY WITH TABLE C403.2.1 OF THE FBC- ENERGY.
 REVISE THE NOTE.
 16) SHT.P.400 - A BACKFLOW PREVENTION DEVICE IS
 REQUIRED ON THE DISHWASHERS PER FBC-PLUMBING SECS.
 608.2, 608.3.
 17) SHT.P400 SHOWS AN AIR ADMITTANCE VALVE ON THE
 FUTURE SANITARY LINE .AIR ADMITTANCE VALVES SHALL VENT
 ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND
 CONNECT TO A HORIZONTAL BRANCH DRAIN. FBC-PLUMBING SEC.
 918.3.1.
 18) WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN
 FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 PER FBC-PLUMBING SEC.918.3.1. HOW MANY FLOORS ARE IN
 THIS BUILDING?
 19) THE FUTURE SANITARY LINE CANNOT BE DESIGNED AS A
 WASTE STACK VENT PER FBC-PLUMBING SEC. 913.
 20) SHT. P400 - THE SANITARY RISER IS MISSING A WATER
 CLOSET IN THE WOMEN'S RESTROOM. WPB AMEND. TO FBC SEC.
 107.2.1.
 21) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE
 RESTROOMS PER FBC- PLUMBING SEC.416.5.
 22) INDICATE ON THE PLANS IF THERE IS AN EXISTING
 SERVICE SINK. IF NOT , ONE WILL BE REQUIRED. FBC_
 PLUMBING TABLE 403.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  