2019-11-08 16:55:42 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101300
 11/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-200: FIRE DAMPERS MISSING AT CRAC-1 & 2
 RETURN DUCT PENETRATIONS AT THE FIRE-RATED IT ROOM
 WALLS- SECTION 607.5.3 FBC M.
  
 2) SHEET M210: REFERENCE IS MADE TO M-410 FOR ROOFTOP
 CONDENSER INSTALLATION DETAILS. PLEASE PROVIDE SHEET
 M-410.
  
 3) M-210: IT APPEARS THAT CU-2 WILL BE INSTALLED WITHIN
 10' OF THE ROOF EDGE. VERIFY THERE IS A 42" PARAPET AT
 THE ROOF EDGE OR PROVIDE A GUARD- SEE SECTION 304.11
 FBC M.
  
 4) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 5) SUBMIT AFL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR
 THE ROOF STAND- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  