2019-11-15 08:21:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 19101300
 W. P. B. PERMIT: 19011155
 ADD: 250 S. AUSTRALIAN AVE. SUITE: 18TH FLOOR.
 CONT: HEDRICK BROTHERS
 TEL/ CONTACT: DARA NUNEZ
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. / NOV. 15TH/ 2019
 ACTION: DENIED
  
 1) SHEET A.200 18TH FLOOR CONSTRUCTION PLAN NOW SHOWS
 WALL TYPE R A 1 HOUR FIRE RATED WALL SURROUNDING THE
 SERVER ROOM. SHEET A102 PARTITION TYPE SHOWS THIS WALL
 TYPE R AS THE 1 HOUR FIRE RATED WALL. THE VAV 18-19
 WHEN PENETRATING THE 1 HOUR FIRE RATED WALLS SHOWS FIRE
 DAMPERS. WHEN VIEWING THE VAV 18-13 WHEN THIS DUCT
 PENETRATES THE BACK WALL OF THE SERVER ROOM, 1 HOUR
 FIRE RATED WALL OF THERE IS NO FIRE DAMPER AS REQUIRED
 BY THE 2017 FBC-B SECTIONS 717.5 WHERE REQUIRED AND
 717.5.4 FIRE PARTITIONS.
  
 2A) SHEET M-210 MAKES REFERENCE TO A NEW MECHANICAL
 EQUIPMENT STAND AND REFERS TO DETAILS ON SHEET M-410.
 PLEASE NOTE THAT IN THE ORIGINAL PERMIT DOCUMENTS THAT
 WERE REVIEWED AND APPROVED THERE WAS NO SUCH SHEET
 LABELED M-410.
 PLEASE PROVIDE A DETAIL FOR THIS NEW ROOF TOP
 CONDENSER. IF THIS EQUIPMENT STAND IS A PREFABRICATED
 STAND THEN WILL NEED TO MEET THE REQUIREMENTS FOR
 COMPONENTS AND CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 2B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2C) 1510.10 MECHANICAL UNITS / CLEARANCES BELOW RAISED
 A/C UNITS. ROOF MOUNTED MECHANICAL UNITS SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM)
 ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS
 EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS
 PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH
 TABLE 1510.10.
  
 3) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  