2019-11-15 08:21:06 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 19101300 |
| W. P. B. PERMIT: 19011155 |
| ADD: 250 S. AUSTRALIAN AVE. SUITE: 18TH FLOOR. |
| CONT: HEDRICK BROTHERS |
| TEL/ CONTACT: DARA NUNEZ |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. / NOV. 15TH/ 2019 |
| ACTION: DENIED |
| |
| 1) SHEET A.200 18TH FLOOR CONSTRUCTION PLAN NOW SHOWS |
| WALL TYPE R A 1 HOUR FIRE RATED WALL SURROUNDING THE |
| SERVER ROOM. SHEET A102 PARTITION TYPE SHOWS THIS WALL |
| TYPE R AS THE 1 HOUR FIRE RATED WALL. THE VAV 18-19 |
| WHEN PENETRATING THE 1 HOUR FIRE RATED WALLS SHOWS FIRE |
| DAMPERS. WHEN VIEWING THE VAV 18-13 WHEN THIS DUCT |
| PENETRATES THE BACK WALL OF THE SERVER ROOM, 1 HOUR |
| FIRE RATED WALL OF THERE IS NO FIRE DAMPER AS REQUIRED |
| BY THE 2017 FBC-B SECTIONS 717.5 WHERE REQUIRED AND |
| 717.5.4 FIRE PARTITIONS. |
| |
| 2A) SHEET M-210 MAKES REFERENCE TO A NEW MECHANICAL |
| EQUIPMENT STAND AND REFERS TO DETAILS ON SHEET M-410. |
| PLEASE NOTE THAT IN THE ORIGINAL PERMIT DOCUMENTS THAT |
| WERE REVIEWED AND APPROVED THERE WAS NO SUCH SHEET |
| LABELED M-410. |
| PLEASE PROVIDE A DETAIL FOR THIS NEW ROOF TOP |
| CONDENSER. IF THIS EQUIPMENT STAND IS A PREFABRICATED |
| STAND THEN WILL NEED TO MEET THE REQUIREMENTS FOR |
| COMPONENTS AND CLADDING. |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(G) PRE-ENGINEERED A/C STANDS |
| |
| 2B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 2C) 1510.10 MECHANICAL UNITS / CLEARANCES BELOW RAISED |
| A/C UNITS. ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) |
| ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS |
| EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS |
| PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH |
| TABLE 1510.10. |
| |
| 3) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |