Plan Review Notes For Permit 19101274 |
Permit Number |
19101274 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-02-05 09:47:22 | LIGHT POLES | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1) PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE DETAILS | | FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH WIND | | LOADS. SHOW THE WIND DESIGN PARAMETERS USED FOR DESIGN | | (CODE VERSION, WIND SPEED, RISK CATEGORY ETC.) ON THE | | DRAWING FBC 1609.1 | | 2) FOUNDATION DRAWING HAS BEEN PROVIDED - LIGHT POLE | | DETAILS (POLE AND ATTACHMENTS TO FOUNDATION) HAVE NOT | | BEEN PROVIDED. | | 3) PLEASE PROVIDE A COMPLETED BUILDING PERMIT | | APPLICATION FROM A CONTRACTOR LICENSED TO INSTALL THE | | CONCRETE FOUNDATION. |
|