Plan Review Notes For Permit 19101274 |
Permit Number |
19101274 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-09 16:53:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC B 1609, SHEET L-9, REVISE PLAN TO INCLUDE WIND | | DESIGN CRITERIA. | | | | 2. ENGINEERING FOR THE LIGHT POLE AND ARM WERE NOT | | PROVIDED; PLEASE PROVIDE. DELEGATED ENGINEERING IS TO | | BE REVIEWED BY SEOR, FAC61G15. | | | | |
|