Date |
Text |
2019-11-14 13:35:52 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1) THIS IS AN ADDITION AND LEVEL 2 ALTERATION (SEC. |
| 504.1 FBC-EXISTING BUILDING). PLANS SHOW REMOVING |
| WINDOW FROM BEDROOM #2 TO ALLOW FOR THE GARAGE |
| ENCLOSURE. ACCORDING TO CITY RECORDS PERMIT #14011326, |
| THIS WINDOW WAS THE BEDROOM EGRESS WINDOW. SPECIFY THE |
| TYPE AND SIZE OF THE OTHER WINDOWS TO REMAIN IN THIS |
| BEDROOM TO VERIFY COMPLIANCE WITH EGRESS. SEC. R310.2.1 |
| FBC-RESIDENTIAL. |
| |
| 2) ROOF FRAMING PLAN SHOWS AN ATTIC ACCESS WITH PULL |
| DOWN LADDER. IT LOOKS LIKE THE ATTIC IS GOING TO BE |
| USED FOR STORAGE. REVISE THE ROOF LIVE LOADS SPECIFIED |
| ON THE PROJECT DATA ON SHEET 2.1. NOTE: INCLUDE THE |
| ATTIC LIVE LOAD AS REQUIRED BY SEC. R301.5 |
| FBC-RESIDENTIAL AND CLEARLY SPECIFY THE TOP CHORD LIVE |
| AND DEAD LOADS AND THE BOTTOM CHORD LIVE AND DEAD |
| LOADS. |
| |
| 3- NEW CORNER COLUMNS SHOWN ON SHEET 2.1 ARE NOT CLEAR. |
| ARE THEY C-2 TYPE COLUMNS?. SEC. 107.2.1 CITY |
| AMENDMENTS. CLEARLY IDENTIFY COLUMN TYPE. |
| |
| 4- TYPICAL GABLE END WALL SECTION ON SHEET 5.1: PROVIDE |
| COMPLETE SPECIFICATIONS FOR THE FASTENERS AT THE TOP |
| AND BOTTOM OF 2X6 GABLE END WALL. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 5- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE |
| EXISTING BEDROOMS AS REQUIRED BY SEC. R315.1 |
| FBC-RESIDENTIAL. |
| |
| 6- ARCHITECT OF RECORD TO SPECIFY ROOF TILE FASTENING |
| AS REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL) |
| |
| A) ROOF TILE. |
| |
| B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| CITY POLICY FOR ALL ROOFING PERMITS. |
| |
| C) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| |
| D) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| |
| E)PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| (INCLUDING ALL PRODUCT APPROVALS ALREADY SUBMITTED) AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |