Plan Review Notes
Plan Review Notes For Permit 19101207
Permit Number 19101207
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-11-05 16:44:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF ACCESS GATES. FD
 REQUIRES SITE ACCESS FOR EMERGENCY OR OTHER APPLICABLE
 INCIDENTS.
  
 PER NFPA 1
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT
  
  
 PLEASE PROVIDE A MINIMUM OF 2 - 10' GATES THAT IS
 EASILY ACCESSIBLE FROM A ROADWAY.
  
  
  
 2) KNOX PADLOCKS ARE RECOMMENDED FOR EACH GATE FOR EASE
 OF 24HR ENTRY AND SITE SECURITY.
  
  
  
 3) IT APPEARS THAT THE FENCE WILL RESTIRCT ACCESS TO
 FIRE HYDRANTS.
  
 FIRE HYDRANTS SHALL BE ACCESSIBLE FROM THE RAODWAY AT
 ALL TIMES.
  
 PLEASE PROVIDE DETAILS AND LOCATIONS OF ALL FIRE
 HYDRANTS AND PROVIDE FOR ACCESS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  