2019-11-22 14:29:22 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1 INDICATE ON PLANS LOCATIONS OF GATES WITH | | SIZES. | | | | FBC B 3306.1 PLEASE PROVIDE SPECIFIC DETAILS FOR | | PROTECTION OF PEDESTRIANS INCLUDING THE SAFE GUARDS | | DURING CONSTRUCTION OF THE FOLLOWING CODE SECTIONS: | | FBC B 3306.2 WALKWAYS | | FBC B 3306.3 DIRECTIONAL BARRICADES | | FBC B 3306.4 CONSTRUCTION RAILINGS | | FBC B 3306.5/3306.6 BARRIERS | | FBC B 3306.7 COVERED WALKWAYS | | FBC B 3307 PROTECTION OF ADJOINING PROPERTY |
|