2020-02-11 07:42:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101152
 ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE
 CONT: BUILTMORE CONTRACTING/ CBC
 TEL: 561-331-1476
 E-MAIL: INFO: BUILTMORECONTRACTING.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PLAN
 REVIEW COMMENTS
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 2E) (ADDITIONAL INFORMATION REQUIRED. SUBMIT A LETTER
 FROM THE DESIGNER OF RECORD LISTING THE SPECIFIC
 STRUCTURAL ITEMS THAT WILL BE INSPECTED BY THE SPECIAL
 INSPECTOR. NOTE: THE FORMS THAT WERE SUBMITTED ARE
 ACCEPTABLE.) THE REQUIRED SPECIAL INSPECTOR
 (STRUCTURAL) FORMS HAVE NOT BEEN SUBMITTED. (REPEAT
 COMMENT) PER OUR DISCUSSION A SPECIAL INSPECTOR WILL BE
 REQUIRED TO INSPECT THE STRUCTURAL WORK FOR THIS
 PROJECT. THIS WILL INCLUDE CUTTING AND REPLACING OF THE
 SLAB AT THE NEW RAMP AND THE STRUCTURAL STEEL WELDS.
 THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY FOR A
 RESIDENT INSPECTOR. WE WILL BE E-MAILING THE LISTED
 CONTACT THE GUIDELINES POLICIES AND FORMS TO BE FILED
 OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW
 AND APPROVAL.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION.
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT:
 9:08 AM WED. OCT. 30/2019
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED. A SPECIAL INSPECTOR IS REQUIRED TO MONITOR
 THIS WORK.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 10A) COMPLIED.
  
 10C) COMPLIED.
  
 10D) COMPLIED.
  
 10E) N/A
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 NEW COMMENTS.
  
 17) (THE LIMITATIONS FOR THE HYDRO BAN WATERPROOFING
 STATE THAT IT IS NOT TO BE USED AS A PRIMARY ROOFING
 MEMBRANE OVER OCCUPIED SPACE. THERE IS OCCUPIED SPACE
 BELOW THIS AREA.) SUBMIT TWO SETS OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 LIQUID WATER-PROOFING MATERIAL THAT WILL BE USED AT THE
 EXTERIOR ADA RAMP. FBC 107.2.1.2
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) (THE DOCUMENTS THAT WERE SUBMITTED WERE DIGITALLY
 SIGNED. ONLY ELECTRONICALLY SUBMITTED PLANS ARE ALLOWED
 TO BE SIGNED DIGITALLY. THE PAPER CALCULATION DOCUMENTS
 ARE REQUIRED TO BE PHYSICALLY SIGNED, DATED AND SEALED
 AS NOTED IN THE ORIGINAL COMMENTS.) THE ORIGINAL
 STRUCTURAL CALCULATIONS THAT INCLUDED THE NEW STEEL
 BEAM SUPPORTING CONCRETE SLAB, ALUMINUM MULLION DESIGN
 AND STAIR INFILL WERE NOT SIGNED, SEALED AND DATED BY
 THE ENGINEER AS REQUIRED BY 61G15-23.003. ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH
 MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE
 PROVISIONS OF SECTION 471.025, F.S., AND RULE
 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED
 AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 23) COMPLIED.
  
 24) AN IMPACT FEE REVIEW IS REQUIRED. SEE IMPACT REVIEW
 STOP FOR ADDITIONAL INFORMATION.
  
 25) THERE IS AN EXTERIOR FIXED GLASS STOREFRONT PANEL
 (S6) SHOWN ON SHEET A102, IN THE WINDOW SCHEDULE ON
 SHEET A601 AND THE STRUCTURAL SHEETS. A FRAMED
 PARTITION WALL IS SHOWN AT THIS LOCATION IN DETAIL 6 ON
 SHEET A401. GLAZING IS NOT ALLOWED IN THIS AREA WHICH
 IS AT A 90 DEGREE ANGLE TO THE EXIT PATH FROM THE EXIT
 PASSAGEWAY. A FIRE ON THE FIRST FLOOR COULD POTENTIALLY
 COMPROMISE THE EXIT. FBC 1023.7
  
 26) THE EXIT DOOR AT THE END OF THE EXIT PASSAGEWAY
 APPEARS TO HAVE THE MINIMUM REQUIRED 32" CLEARANCE
 BETWEEN THE FACE OF THE OPEN DOOR TO THE OFFSET IN THE
 OPPOSITE WALL. THERE IS NO ROOM FOR ERROR WITH THIS
 DESIGN. A SUGGESTION WOULD BE TO MOVE THE DOOR FURTHER
 INTO THE EXIT PASSAGEWAY AND CHANGE THE DOOR TO SWING
 OUT TO THE WALL IN FRONT OF THE SPRINKLER STAND PIPE.
 THIS WOULD PROVIDE A BETTER FLOW OF TRAFFIC FROM THE
 EXIT PASSAGEWAY AT THE EXIT DISCHARGE. FBC 1010.1.1 &
 1028.1
  
 27) NEW COMMENT. IT HAS BEEN BROUGHT TO MY ATTENTION
 THAT ADDITIONAL ACCESSIBLE ENTRANCES TO THIS TENANT
 SPACE MAY BE REQUIRED. SECTION 206.4.1 OF THE 2017
 FLORIDA BUILDING CODE ACCESSIBILITY PUBLIC ENTRANCES.
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. THERE ARE THREE PUBLIC ENTRANCES
 SHOWN ON THE PLANS. THEREFORE, TWO OF THEM ARE REQUIRED
 TO COMPLY WITH 404. IF DOCUMENTATION IS PROVIDED
 SHOWING 20 PERCENT DISPROPORTIONALITY TO THE COST OF
 THE OVERALL ALTERATION, THEN THE ONE ACCESSIBLE
 ENTRANCE MAY MEET THE REQUIREMENTS. SEE FBC
 ACCESSIBILITY SECTION 202.4
  
 28) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW
 COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS
 PROVIDED.
  
  
  
  
  
  
  