2020-02-11 07:42:40 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101152 |
| ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE |
| CONT: BUILTMORE CONTRACTING/ CBC |
| TEL: 561-331-1476 |
| E-MAIL: INFO: BUILTMORECONTRACTING.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PLAN |
| REVIEW COMMENTS |
| 4TH REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 2E) (ADDITIONAL INFORMATION REQUIRED. SUBMIT A LETTER |
| FROM THE DESIGNER OF RECORD LISTING THE SPECIFIC |
| STRUCTURAL ITEMS THAT WILL BE INSPECTED BY THE SPECIAL |
| INSPECTOR. NOTE: THE FORMS THAT WERE SUBMITTED ARE |
| ACCEPTABLE.) THE REQUIRED SPECIAL INSPECTOR |
| (STRUCTURAL) FORMS HAVE NOT BEEN SUBMITTED. (REPEAT |
| COMMENT) PER OUR DISCUSSION A SPECIAL INSPECTOR WILL BE |
| REQUIRED TO INSPECT THE STRUCTURAL WORK FOR THIS |
| PROJECT. THIS WILL INCLUDE CUTTING AND REPLACING OF THE |
| SLAB AT THE NEW RAMP AND THE STRUCTURAL STEEL WELDS. |
| THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY FOR A |
| RESIDENT INSPECTOR. WE WILL BE E-MAILING THE LISTED |
| CONTACT THE GUIDELINES POLICIES AND FORMS TO BE FILED |
| OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW |
| AND APPROVAL. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION. |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT: |
| 9:08 AM WED. OCT. 30/2019 |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. A SPECIAL INSPECTOR IS REQUIRED TO MONITOR |
| THIS WORK. |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 10A) COMPLIED. |
| |
| 10C) COMPLIED. |
| |
| 10D) COMPLIED. |
| |
| 10E) N/A |
| |
| 11) COMPLIED. |
| |
| 12) COMPLIED. |
| |
| 13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16) COMPLIED. |
| |
| NEW COMMENTS. |
| |
| 17) (THE LIMITATIONS FOR THE HYDRO BAN WATERPROOFING |
| STATE THAT IT IS NOT TO BE USED AS A PRIMARY ROOFING |
| MEMBRANE OVER OCCUPIED SPACE. THERE IS OCCUPIED SPACE |
| BELOW THIS AREA.) SUBMIT TWO SETS OF THE MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| LIQUID WATER-PROOFING MATERIAL THAT WILL BE USED AT THE |
| EXTERIOR ADA RAMP. FBC 107.2.1.2 |
| |
| 18) COMPLIED. |
| |
| 19) COMPLIED. |
| |
| 20) COMPLIED. |
| |
| 21) COMPLIED. |
| |
| 22) (THE DOCUMENTS THAT WERE SUBMITTED WERE DIGITALLY |
| SIGNED. ONLY ELECTRONICALLY SUBMITTED PLANS ARE ALLOWED |
| TO BE SIGNED DIGITALLY. THE PAPER CALCULATION DOCUMENTS |
| ARE REQUIRED TO BE PHYSICALLY SIGNED, DATED AND SEALED |
| AS NOTED IN THE ORIGINAL COMMENTS.) THE ORIGINAL |
| STRUCTURAL CALCULATIONS THAT INCLUDED THE NEW STEEL |
| BEAM SUPPORTING CONCRETE SLAB, ALUMINUM MULLION DESIGN |
| AND STAIR INFILL WERE NOT SIGNED, SEALED AND DATED BY |
| THE ENGINEER AS REQUIRED BY 61G15-23.003. ENGINEERING |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH |
| MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE |
| PROVISIONS OF SECTION 471.025, F.S., AND RULE |
| 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED |
| AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL |
| ENGINEER IN RESPONSIBLE CHARGE. |
| (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE |
| USED. |
| (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE |
| REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| NOT RENDER THE SIGNATURE ILLEGIBLE. |
| |
| 23) COMPLIED. |
| |
| 24) AN IMPACT FEE REVIEW IS REQUIRED. SEE IMPACT REVIEW |
| STOP FOR ADDITIONAL INFORMATION. |
| |
| 25) THERE IS AN EXTERIOR FIXED GLASS STOREFRONT PANEL |
| (S6) SHOWN ON SHEET A102, IN THE WINDOW SCHEDULE ON |
| SHEET A601 AND THE STRUCTURAL SHEETS. A FRAMED |
| PARTITION WALL IS SHOWN AT THIS LOCATION IN DETAIL 6 ON |
| SHEET A401. GLAZING IS NOT ALLOWED IN THIS AREA WHICH |
| IS AT A 90 DEGREE ANGLE TO THE EXIT PATH FROM THE EXIT |
| PASSAGEWAY. A FIRE ON THE FIRST FLOOR COULD POTENTIALLY |
| COMPROMISE THE EXIT. FBC 1023.7 |
| |
| 26) THE EXIT DOOR AT THE END OF THE EXIT PASSAGEWAY |
| APPEARS TO HAVE THE MINIMUM REQUIRED 32" CLEARANCE |
| BETWEEN THE FACE OF THE OPEN DOOR TO THE OFFSET IN THE |
| OPPOSITE WALL. THERE IS NO ROOM FOR ERROR WITH THIS |
| DESIGN. A SUGGESTION WOULD BE TO MOVE THE DOOR FURTHER |
| INTO THE EXIT PASSAGEWAY AND CHANGE THE DOOR TO SWING |
| OUT TO THE WALL IN FRONT OF THE SPRINKLER STAND PIPE. |
| THIS WOULD PROVIDE A BETTER FLOW OF TRAFFIC FROM THE |
| EXIT PASSAGEWAY AT THE EXIT DISCHARGE. FBC 1010.1.1 & |
| 1028.1 |
| |
| 27) NEW COMMENT. IT HAS BEEN BROUGHT TO MY ATTENTION |
| THAT ADDITIONAL ACCESSIBLE ENTRANCES TO THIS TENANT |
| SPACE MAY BE REQUIRED. SECTION 206.4.1 OF THE 2017 |
| FLORIDA BUILDING CODE ACCESSIBILITY PUBLIC ENTRANCES. |
| IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| SHALL COMPLY WITH 404. THERE ARE THREE PUBLIC ENTRANCES |
| SHOWN ON THE PLANS. THEREFORE, TWO OF THEM ARE REQUIRED |
| TO COMPLY WITH 404. IF DOCUMENTATION IS PROVIDED |
| SHOWING 20 PERCENT DISPROPORTIONALITY TO THE COST OF |
| THE OVERALL ALTERATION, THEN THE ONE ACCESSIBLE |
| ENTRANCE MAY MEET THE REQUIREMENTS. SEE FBC |
| ACCESSIBILITY SECTION 202.4 |
| |
| 28) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW |
| COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS |
| PROVIDED. |
| |
| |
| |
| |
| |
| |
| |