2020-01-28 14:14:13 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 3RD REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. THE HOT WATER DISTRIBUTION SYSTEM PROVIDED EXCEEDS |
| THE MAXIMUM LENGTH OF 50 FEET FROM HEAT SOURCE TO |
| FIXTURES ALLOWED BY FBC PL 607.2.1. PER WPB FBC |
| 107.2.1, PROVIDE A RECIRCULATED OR HEAT TRACED SYSTEM |
| PIPING EXTENDING THE HEAT SOURCE TO COMPLY. PROVIDE |
| PIPING, VALVES, PUMP, SCHEDULES/SPECS AND DETAILS FOR |
| SYSTEM I.E. RECIRCULATING PUMP. |
| 2. HOT WATER SHALL BE INSULATED PER FBC EC C404.4. |
| PROVIDE SPECIFICATION FOR HOT WATER INSULATION. |
| 3. THE SPECIFIED A.O. SMITH DEL-30 WATER HEATER IS NOT |
| A BOTTOM FED HEATER AS INDICATED IN THE DETAIL ON P-2. |
| PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, REVISE |
| DETAIL PROPERLY DETAILING THE PIPING ARRANGEMENT FOR |
| THE SPECIFIED WATER HEATER. THE DETAIL SHALL NOTE |
| VALVES AS WELL AS THERMAL EXPANSION CONTROL AS REQUIRED |
| BY FBC PL 607.3. NOTE THE PAN DRAIN AND T&P DISCHARGE |
| SHALL BE ROUTED TO THE MOP SINK AS INDICATED IN YOUR |
| NOTE AT THE WATER HEATER LOCATION. |
| 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| ANCHOR DETAIL FOR THE WALL MOUNTED WATER HEATER SUPPORT |
| INDICATED IN YOUR NOTE AT THE WATER HEATER LOCATION. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19101152 300 CLEMATIS ST |