2020-01-28 09:45:18 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101152 |
| ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE |
| CONT: BUILTMORE CONTRACTING/ CBC |
| TEL: 561-331-1476 |
| E-MAIL: INFO: BUILTMORECONTRACTING.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PLAN |
| REVIEW COMMENTS |
| 3RD REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 2E) THE REQUIRED SPECIAL INSPECTOR (STRUCTURAL) FORMS |
| HAVE NOT BEEN SUBMITTED. (REPEAT COMMENT) PER OUR |
| DISCUSSION A SPECIAL INSPECTOR WILL BE REQUIRED TO |
| INSPECT THE STRUCTURAL WORK FOR THIS PROJECT. THIS WILL |
| INCLUDE CUTTING AND REPLACING OF THE SLAB AT THE NEW |
| RAMP AND THE STRUCTURAL STEEL WELDS. THIS BUILDING AND |
| THE SCOPE OF WORK WILL QUALIFY FOR A RESIDENT |
| INSPECTOR. WE WILL BE E-MAILING THE LISTED CONTACT THE |
| GUIDELINES POLICIES AND FORMS TO BE FILED OUT AND |
| RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW AND |
| APPROVAL. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION. |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT: |
| 9:08 AM WED. OCT. 30/2019 |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. A SPECIAL INSPECTOR IS REQUIRED TO MONITOR |
| THIS WORK. |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 10A) COMPLIED. |
| |
| 10C) COMPLIED. |
| |
| 10D) COMPLIED. |
| |
| 10E) N/A |
| |
| 11) COMPLIED. |
| |
| 12) COMPLIED. |
| |
| 13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16) COMPLIED. |
| |
| NEW COMMENTS. |
| |
| 17) SUBMIT TWO SETS OF THE MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| LIQUID WATER-PROOFING MATERIAL THAT WILL BE USED AT THE |
| EXTERIOR ADA RAMP. FBC 107.2.1.2 |
| |
| 18) ON SHEET S-2 THE EXIT DOOR AT THE EXIT PASSAGEWAY |
| HAS A NOTE THAT REFERS TO SHEET S-3. THERE WAS NOT A |
| SHEET S-3 IN THE PLANS. PLEASE CLARIFY. FBC 107.2.1 |
| |
| 19) SPECIFY THE DOOR SIZES, CAPACITY AND OCCUPANT LOADS |
| FOR THE DOOR AT THE FOOT OF THE STAIRS TO THE EXIT |
| PASSAGEWAY AND THE EXIT DOOR OF THE EXIT PASSAGEWAY. |
| FBC 107.2.1 |
| |
| 20) THE SECTION 11/A501 AT THE NEW STRUCTURAL ADA RAMP |
| DID NOT GET REVISED TO REFLECT THE MODIFICATIONS TO THE |
| EXISTING 12" SLAB. PLEASE CORRECT. FBC 107.2.1 |
| |
| 21) THE PRODUCT APPROVAL (NOA NO. 14-0513.03) FOR DOOR |
| D-11 HAS A MAXIMUM NEGATIVE DESIGN LOAD OF -75.0 PSF. |
| THIS WILL NOT MEET THE REQUIRED NEGATIVE DESIGN LOAD OF |
| -83.2 PSF THAT IS SPECIFIED ON SHEET A201. FBC 107.3.4 |
| |
| 22) THE ORIGINAL STRUCTURAL CALCULATIONS THAT INCLUDED |
| THE NEW STEEL BEAM SUPPORTING CONCRETE SLAB, ALUMINUM |
| MULLION DESIGN AND STAIR INFILL WERE NOT SIGNED, SEALED |
| AND DATED BY THE ENGINEER AS REQUIRED BY 61G15-23.003. |
| ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY |
| SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| USED. |
| (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| NOT RENDER THE SIGNATURE ILLEGIBLE. |
| |
| 23) SEPARATE PERMITS WILL BE REQUIRED FOR ITEMS SUCH AS |
| AWNINGS, EXTERIOR SIGNS, RIGHT OF WAY PERMITS, ETC. |
| |
| 24) AN IMPACT FEE REVIEW IS REQUIRED. SEE IMPACT REVIEW |
| STOP FOR ADDITIONAL INFORMATION. |
| |
| 25) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW |
| COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS |
| PROVIDED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |