2020-01-28 09:45:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101152
 ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE
 CONT: BUILTMORE CONTRACTING/ CBC
 TEL: 561-331-1476
 E-MAIL: INFO: BUILTMORECONTRACTING.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 2E) THE REQUIRED SPECIAL INSPECTOR (STRUCTURAL) FORMS
 HAVE NOT BEEN SUBMITTED. (REPEAT COMMENT) PER OUR
 DISCUSSION A SPECIAL INSPECTOR WILL BE REQUIRED TO
 INSPECT THE STRUCTURAL WORK FOR THIS PROJECT. THIS WILL
 INCLUDE CUTTING AND REPLACING OF THE SLAB AT THE NEW
 RAMP AND THE STRUCTURAL STEEL WELDS. THIS BUILDING AND
 THE SCOPE OF WORK WILL QUALIFY FOR A RESIDENT
 INSPECTOR. WE WILL BE E-MAILING THE LISTED CONTACT THE
 GUIDELINES POLICIES AND FORMS TO BE FILED OUT AND
 RETURNED TO THE BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION.
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT:
 9:08 AM WED. OCT. 30/2019
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED. A SPECIAL INSPECTOR IS REQUIRED TO MONITOR
 THIS WORK.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 10A) COMPLIED.
  
 10C) COMPLIED.
  
 10D) COMPLIED.
  
 10E) N/A
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 NEW COMMENTS.
  
 17) SUBMIT TWO SETS OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 LIQUID WATER-PROOFING MATERIAL THAT WILL BE USED AT THE
 EXTERIOR ADA RAMP. FBC 107.2.1.2
  
 18) ON SHEET S-2 THE EXIT DOOR AT THE EXIT PASSAGEWAY
 HAS A NOTE THAT REFERS TO SHEET S-3. THERE WAS NOT A
 SHEET S-3 IN THE PLANS. PLEASE CLARIFY. FBC 107.2.1
  
 19) SPECIFY THE DOOR SIZES, CAPACITY AND OCCUPANT LOADS
 FOR THE DOOR AT THE FOOT OF THE STAIRS TO THE EXIT
 PASSAGEWAY AND THE EXIT DOOR OF THE EXIT PASSAGEWAY.
 FBC 107.2.1
  
 20) THE SECTION 11/A501 AT THE NEW STRUCTURAL ADA RAMP
 DID NOT GET REVISED TO REFLECT THE MODIFICATIONS TO THE
 EXISTING 12" SLAB. PLEASE CORRECT. FBC 107.2.1
  
 21) THE PRODUCT APPROVAL (NOA NO. 14-0513.03) FOR DOOR
 D-11 HAS A MAXIMUM NEGATIVE DESIGN LOAD OF -75.0 PSF.
 THIS WILL NOT MEET THE REQUIRED NEGATIVE DESIGN LOAD OF
 -83.2 PSF THAT IS SPECIFIED ON SHEET A201. FBC 107.3.4
  
 22) THE ORIGINAL STRUCTURAL CALCULATIONS THAT INCLUDED
 THE NEW STEEL BEAM SUPPORTING CONCRETE SLAB, ALUMINUM
 MULLION DESIGN AND STAIR INFILL WERE NOT SIGNED, SEALED
 AND DATED BY THE ENGINEER AS REQUIRED BY 61G15-23.003.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 23) SEPARATE PERMITS WILL BE REQUIRED FOR ITEMS SUCH AS
 AWNINGS, EXTERIOR SIGNS, RIGHT OF WAY PERMITS, ETC.
  
 24) AN IMPACT FEE REVIEW IS REQUIRED. SEE IMPACT REVIEW
 STOP FOR ADDITIONAL INFORMATION.
  
 25) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW
 COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS
 PROVIDED.
  
  
  
  
  
  
  
  
  
  