2019-12-03 14:57:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 19101152 300 CLEMATIS ST |
| |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1.RE: PLAN SHEET A102; THE FOUR BATHROOMS PREVIOUSLY |
| NOT IN SCOPE HAVE BEEN RECONFIGURED TO COMPLY WITH FBC |
| ACC. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE SIZED |
| SANITARY WASTE/VENT AND HOT/COLD WATER RISER DIAGRAMS |
| AND PLAN VIEW ROUTING SHOWING HOW THE RECONFIGURATIONS |
| WILL BE ACCOMMODATED. INDICATE POINTS OF CONNECTION TO |
| EXISTING. INCLUDE THE DRINKING FOUNTAIN. |
| 2. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW LOCATION |
| AND TYPE OF EXISTING SOURCE OF HOT WATER, OR PROVIDE |
| SOURCE TO COMPLY WITH FBC PL 607.1. IF NEW SOURCE IS |
| REQUIRED THEN PROVIDE WATER HEATER SCHEDULE SHOWING |
| PRESSURE RATINGS, CAPACITY AND ELECTRICAL |
| CHARACTERISTICS AND SHOW LOCATION(S) ON PLANS AND |
| INTEGRATE INTO WATER RISER DIAGRAM. IF STORAGE TANK |
| TYPE, PROVIDE DETAIL SHOWING COMPLIANCE WITH FBC PL |
| CHAPTER 5 AND WITH FBC PL 607.3. PER WPB FBC 107.2.1 |
| AND 107.3.5.1.3, PROVIDE SUPPORT DETAIL IF CEILING HUNG |
| OR WALL MOUNTED. |
| 3. PER FBC PL 416.5 PROVIDE TEMPERED WATER FROM THE |
| LAVATORIES THROUGH AN APPROVED WATER-TEMPERATURE |
| LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| 4. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE FIXTURE |
| SCHEDULE INDICATING WATER SUPPLY REQUIREMENTS. INDICATE |
| WATER CLOSET TYPE, I.E. FLOOR MOUNTED OR WALL HUNG, |
| TANK TYPE OR AUTOMATIC FLUSH VALVE. CONFIRM THAT WATER |
| SUPPLY AND SANITARY CONNECTION CONFIGURATIONS ARE |
| COMPATIBLE. |
| 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE |
| PLUMBING FIXTURE SCHEDULE SHOWING COMPLIANCE WITH FBC |
| PL 604.3, INDICATING WATER SUPPLY REQUIREMENTS. |
| INDICATE WATER CLOSET TYPE, I.E. FLOOR MOUNTED OR WALL |
| HUNG, TANK TYPE OR AUTOMATIC FLUSH VALVE. CONFIRM THAT |
| WATER SUPPLY AND SANITARY CONNECTION CONFIGURATIONS ARE |
| COMPATIBLE. |
| 6. AS MAINTENANCE MAY BE ACCESSING THE ROOM WITH THE |
| SERVICE SINK BY PASSING THROUGH THE RECONFIGURED MEN?S |
| ADA BATHROOM, PER FBC 1210.3, THE WATER CLOSET IN SAID |
| ROOM SHALL BE ENCLOSED IN A WHEELCHAIR ACCESSIBLE |
| COMPARTMENT COMPLYING WITH FBC ACC 604.8.1.1 TO PROVIDE |
| PRIVACY FOR THE OCCUPANT. ADDITIONALLY, PROVIDE A SIDE |
| WALL SCREEN AT THE URINAL FOR THE SAME REASON. |
| 7. IT IS NOTED THAT THE DOOR FOR THE WOMEN?S |
| RECONFIGURED ADA BATHROOM IS LOCATED DIRECTLY IN FRONT |
| OF THE WATER CLOSET. THIS IS NOT PROHIBITED IN |
| RENOVATION AS NOTED IN FBC ACC 604.8.1.6 AND ADVISORY |
| 604.8.1.6 AS WELL AS ADVISORY 604.3.2 BUT SHOULD BE |
| CONSIDERED WHERE FEASIBLE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19101152 300 CLEMATIS ST |
| |
| |
| |
| |
| |