2019-12-05 14:47:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19101152 |
| 12/5/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1 & M-2: FIRE/SMOKE DAMPERS MISSING AT THE |
| O/A DUCT CONNECTIONS INTO THE EXISTING SHAFTS- SECTION |
| 607.5.3 FBC M. |
| |
| 2) THE SUBMITTED AC CALULATIONS ARE BASED ON ACCA |
| MANUAL J WHICH IS THE CALCULATION METHOD ALLOWED FOR |
| RESIDENTIAL SYSTEMS. PLEASE REVIEW SECTION C403.2.1 FBC |
| EC WHICH REQUIRES DESIGN LOADS TO BE DETERMINED IN |
| ACCORDANCE WITH ANS/ASHRAE/ACCA STANDARD 183 OR ACCA |
| MANUAL N. |
| |
| 3) COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS- PLEASE |
| COMPLY. 6) THE $150,000 VALUE FOR THE PROPOSED PROJECT |
| APPEARS UNDERVALUED FOR THE SCOPE OF WORK SHOWN ON THE |
| PLANS. PLEASE PROVIDE BONAFIDE CONTRACTS AND/OR |
| ESTIMATES THAT INCLUDE THE LABOR, MATERIALS, EQUIPMENT, |
| INTERIOR FINISHES, DESIGN FEES, AND OVERHEAD AND |
| PROFIT- SECTION 109.3 WPB. |
| |
| 4) M-2: CLARIFY IF THERE IS AN ABOVE CEILING RETURN AIR |
| PLENUM AND PLACE A NOTE ON THE PLAN IF APPLICABLE - SEE |
| SECTION 602 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |