2019-12-19 17:01:35 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101152 |
| ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE |
| CONT: BUILTMORE CONTRACTING/ CBC |
| TEL: 561-331-1476 |
| E-MAIL: INFO: BUILTMORECONTRACTING.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PLAN |
| REVIEW COMMENTS |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 2E) PER OUR DISCUSSION A SPECIAL INSPECTOR WILL BE |
| REQUIRED TO INSPECT THE STRUCTURAL WORK FOR THIS |
| PROJECT. THIS WILL INCLUDE TO CUTTING AND REPLACING OF |
| THE SLAB AT THE NEW RAMP AND THE STRUCTURAL STEEL |
| WELDS. THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY |
| FOR A RESIDENT INSPECTOR. WE WILL BE E-MAILING THE |
| LISTED CONTACT THE GUIDELINES POLICIES AND FORMS TO BE |
| FILED OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR |
| REVIEW AND APPROVAL. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION. |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT: |
| 9:08 AM WED. OCT. 30/2019 |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) PARTIALLY COMPLIED. THE ENGINEER NEEDS TO EVALUATE |
| IF AND HOW THE CUTTING AND REMOVAL OF THE SUSPENDED |
| CONCRETE SLAB WILL AFFECT THE EXISTING RETAINING AND |
| BEARING WALL ON EITHER SIDE OF THE OPENING. SUBMIT TWO |
| SETS OF THE ENGINEER'S REPORT ADDRESSING THIS ISSUE. |
| PROVIDE A STRUCTURAL ANALYSIS OF THE EXISTING SUSPENDED |
| CONCRETE SLAB THAT IS TO BE REMOVED TO ACCOMMODATE THE |
| PROPOSED ADA ACCESSIBLE RAMP. FBC 107.2.1.2 |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) PARTIALLY COMPLIED.THE RE-ROUTED INTERIOR EXIT |
| STAIRWAY DOES NOT LEAD DIRECTLY TO THE EXTERIOR OF THE |
| BUILDING. IT APPEARS THAT YOU INTEND TO USE AN EXIT |
| PASSAGEWAY TO EXTEND THE STAIRWAY TO THE EXTERIOR OF |
| THE BUILDING. THE EXIT PASSAGEWAY IS REQUIRED TO COMPLY |
| WITH THE FOLLOWING CODE SECTIONS. |
| FBC 1023.1 GENERAL. INTERIOR EXIT STAIRWAYS AND RAMPS |
| SERVING AS AN EXIT COMPONENT IN A MEANS OF EGRESS |
| SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS |
| SECTION. INTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE |
| ENCLOSED AND LEAD DIRECTLY TO THE EXTERIOR OF THE |
| BUILDING OR SHALL BE EXTENDED TO THE EXTERIOR OF THE |
| BUILDING WITH AN EXIT PASSAGEWAY CONFORMING TO THE |
| REQUIREMENTS OF SECTION 1024, EXCEPT AS PERMITTED IN |
| SECTION 1028.1. AN INTERIOR EXIT STAIRWAY OR RAMP SHALL |
| NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS OF |
| EGRESS AND A CIRCULATION PATH. |
| |
| 10A) 1023.3.1 EXTENSION. |
| WHERE INTERIOR EXIT STAIRWAYS AND RAMPS ARE EXTENDED TO |
| AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT |
| PASSAGEWAY, THE INTERIOR EXIT STAIRWAY AND RAMP SHALL |
| BE SEPARATED FROM THE EXIT PASSAGEWAY BY A FIRE BARRIER |
| CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR A |
| HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 711, OR BOTH. THE FIRE-RESISTANCE RATING SHALL |
| BE NOT LESS THAN THAT REQUIRED FOR THE INTERIOR EXIT |
| STAIRWAY AND RAMP. A FIRE DOOR ASSEMBLY COMPLYING WITH |
| SECTION 716.5 SHALL BE INSTALLED IN THE FIRE BARRIER TO |
| PROVIDE A MEANS OF EGRESS FROM THE INTERIOR EXIT |
| STAIRWAY AND RAMP TO THE EXIT PASSAGEWAY. OPENINGS IN |
| THE FIRE BARRIER OTHER THAN THE FIRE DOOR ASSEMBLY ARE |
| PROHIBITED. PENETRATIONS OF THE FIRE BARRIER ARE |
| PROHIBITED. |
| EXCEPTIONS: |
| -1.PENETRATIONS OF THE FIRE BARRIER IN ACCORDANCE WITH |
| SECTION 1023.5 SHALL BE PERMITTED. |
| -2.SEPARATION BETWEEN AN INTERIOR EXIT STAIRWAY OR RAMP |
| AND THE EXIT PASSAGEWAY EXTENSION SHALL NOT BE REQUIRED |
| WHERE THERE ARE NO OPENINGS INTO THE EXIT PASSAGEWAY |
| EXTENSION. |
| |
| 10C) SOME TYPE OF GATE WILL BE REQUIRED AT THE STAIRWAY |
| THAT LEADS FROM THE EXIT PASSAGEWAY TO THE BASEMENT TO |
| PREVENT OCCUPANTS FROM MISTAKING THEM AS EXIT STAIRS. |
| 1024.5 OPENINGS. |
| EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN |
| ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. |
| EXCEPT AS PERMITTED IN SECTION 402.8.7, OPENINGS IN |
| EXIT PASSAGEWAYS OTHER THAN UNPROTECTED EXTERIOR |
| OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE EXIT PASSAGEWAY. |
| WHERE AN INTERIOR EXIT STAIRWAY OR RAMP IS EXTENDED TO |
| AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT |
| PASSAGEWAY, THE EXIT PASSAGEWAY SHALL COMPLY WITH |
| SECTION 1023.3.1. |
| ELEVATORS SHALL NOT OPEN INTO AN EXIT PASSAGEWAY. |
| |
| 10D) NOT ADDRESSED. 1024.6 PENETRATIONS. |
| PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE |
| PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY |
| FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT |
| PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL |
| NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| EXCEPTION: MEMBRANE PENETRATIONS SHALL BE PERMITTED ON |
| THE OUTSIDE OF THE EXIT PASSAGEWAY. SUCH PENETRATIONS |
| SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.3.2. |
| |
| 10E) VENTILATION FOR THE EXIT PASSAGEWAY HAS NOT BEEN |
| ADDRESSED. 1024.7 VENTILATION. |
| EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION |
| AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF |
| THE FOLLOWING: |
| -1.THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR |
| TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE |
| EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS |
| REQUIRED FOR SHAFTS. |
| -2.WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN |
| THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN |
| DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE |
| DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL |
| BE CONVEYED THROUGH DUCTS ENCLOSED |
| IN CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| -3.WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND |
| DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE |
| BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH |
| CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED |
| CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR |
| MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY |
| OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR |
| SHAFT ENCLOSURES. |
| EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE |
| INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS. |
| |
| 11) YOUR RESPONSE TO THIS COMMENT INDICATES THAT THERE |
| WILL BE CONDENSATE LINES WHICH HAVE A POTENTIAL TO LEAK |
| ABOVE THE CEILING OF THE EXIT PASSAGEWAY. YOU WILL HAVE |
| TO PROVIDE AN ASSEMBLY EVALUATION REPORT FOR A FIRE |
| RATED CEILING ASSEMBLY THAT WILL NOT BE COMPROMISED BY |
| A WATER LEAK THAT IS ACCEPTABLE TO THE BUILDING |
| OFFICIAL. IDENTIFY ALL EXISTING BUILDING SYSTEMS AND |
| ALL PROPOSED SYSTEMS THAT ARE OR WILL BE LOCATED ABOVE |
| THE 2 HR FIRE RESISTANCE RATED CEILING OF THE EXIT |
| PASSAGEWAY. INCLUDING BUT NOT LIMITED TO PLUMBING THAT |
| COULD LEAK AND COMPROMISE THE HORIZONTAL GYPSUM WALL |
| BOARD SHAFT ASSEMBLY CEILING. FBC 107.2.1 |
| |
| 12) COMPLIED. |
| |
| 13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16) COMPLIED. |
| |
| 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW |
| COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS |
| PROVIDED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |