2019-11-01 10:56:17 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101152 |
| ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE |
| CONT: BUILTMORE CONTRACTING/ CBC |
| TEL: 561-331-1476 |
| E-MAIL: INFO: BUILTMORECONTRACTING.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE COVERSHEET LIST THIS PROJECT AS A LEVEL II |
| ALTERATION. PLEASE NOTE THE LAST PERMITTED AND BUSINESS |
| TAX RECEIPT FOR THE CORNER OCCUPANT WAS A RESTAURANT. |
| THIS MAKES THE PROJECT A CHANGE OF OCCUPANCY UNDER THE |
| 2017 EXISTING BUILDING CODE CHAPTER 10 AND SECTION |
| 1001.3.1. PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OR GROUP OF A |
| PORTION OF AN EXISTING BUILDING IS CHANGED, SECTION |
| 1012 SHALL APPLY. |
| |
| 2) THE LIFE SAFETY SHEET LS102: |
| 2A) ON THE GROUND FLOOR DETAIL THE OCCUPANT LOAD FACTOR |
| IS BEING TAKEN AT 30 SQ. FT. PER OCCUPANT. IN THE |
| OCCUPANT LOAD CALCULATIONS THE SAME OCCUPANT LOAD |
| FACTOR OF 30 SQ. FT. PER OCCUPANT IS USED. PLEASE |
| UPDATE THE PLANS TO 60 SQ. FT. PER OCCUPANT LOAD |
| FACTOR. THIS IS A CHANGE TO THE 2017 FBC-B BLACK LINED |
| IN MARGIN, TABLE 1004.1.2 SEE MERCANTILE. |
| |
| 2B) BOTH THE 3/32 INCH SCALE AND 3/16 INCH SCALE PLANS |
| HAVE BEEN SHRUNK, THEY HAVE BEEN SHRUNK OVER 50% OF THE |
| VALUE SCALE INDICATED ON THE PLANS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION |
| 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER. |
| 2C)EGRESS REQUIREMENTS-MERCANTILE : NEW OCCUPANCY |
| 2C)(1) EXIT ACCESS TRAVEL IS GIVEN TABLE 1016.1 UPDATE |
| PLANS TO THE 2017 FBC-B |
| 2C)(2) THE MINIMUM CLEAR WIDTH REQUIREMENTS FOR THE |
| 2017 FBC-BUILDING ARE NOT GIVEN. |
| 2C)(3) THE CAPACITY FACTOR FOR LEVEL/ RAMP REQUIREMENTS |
| FOR THE 2017 FBC-BUILDING ARE NOT GIVEN. |
| 2C)(4) THE CAPACITY FACTOR FOR STAIRS REQUIREMENTS FOR |
| THE 2017 FBC-BUILDING ARE NOT GIVEN. |
| 2C)(5) THE COMMON PATH OF TRAVEL REQUIREMENTS FOR THE |
| 2017 FBC-BUILDING ARE NOT GIVEN. |
| COMMON PATH OF TRAVEL FOR THE BASEMENT CANNOT BE |
| DETERMINED SINCE THE PLANS ARE NOT DRAWN TO SCALE AS |
| INDICATED ON THE PLANS. 2017 FBC-B TABLE 1006.2.1. & |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2D) SINCE THE BASEMENT PLAN IS NOT TO SCALE AND THE |
| WALK IN COOLER IS INDICATED NOT IN THE SCOPE OF WORK, |
| THE SQ. F.T OF THE BASEMENT CANNOT BE DETERMINED NOR |
| THE OCCUPANT LOAD. VERTICAL ACCESSIBILITY MAYBE A |
| REQUIREMENT IF THE OCCUPANT LOAD IS GREATER THAN 5 |
| OCCUPANTS. 2017 FBC-ACCESSIBILITY CODE SECTION 201.1.1. |
| 2E) THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY |
| FOR A RESIDENT INSPECTOR. WE WILL BE E-MAILING THE |
| LISTED CONTACT THE GUIDELINES POLICIES AND FORMS TO BE |
| FILED OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR |
| REVIEW AND APPROVAL. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION. |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT: |
| 9:08 AM WED. OCT. 30/2019 |
| |
| 2F) THE COVERSHEET UNDER THE HEADING BUILDING |
| INFORMATION LIST THE CONSTRUCTION TYPE AS : II-B. |
| PLEASE REVIEW SHEET S-2 INFILL OF THE 1ST FLOOR AND |
| SECTION 1 ON S-1 SHOWS WOOD FRAMING AND ONE LAYER OF |
| 3/4 INCH PLYWOOD DECKING. THE 2017 FBC-B SECTION 603.1 |
| ALLOWABLE COMBUSTIBLE MATERIALS IN TYPE I AND II |
| CONSTRUCTION. THIS SECTION DOES NOT LIST FLOOR FRAMING |
| AT ALL, NOT EVEN FOR FIRE RETARDANT TREATED WOOD. |
| |
| 2G) THE PLAN IS ALSO SILENT AS TO THE REQUIREMENTS OF |
| HORIZONTAL FIRE BARRIERS FOR THE BASEMENT TO 1ST FLOOR |
| AND 1ST FLOOR TO THE 2ND FLOOR. PLEASE SHOW HOW |
| COMPLIANCE WITH TABLE 707.3.10 WILL BE MET. NOTE THERE |
| IS A 2ND FLOOR INFILL THAT WILL ALSO NEED TO BE SHOWN |
| ON THE PLANS. |
| |
| 3) SHEET A101: |
| 3A) IN THE BASEMENT PLAN WALL IDENTIFICATION TAGS ARE |
| GIVEN BUT THERE IS NO LEGEND ON THIS SHEET FOR |
| REFERENCE. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| 3B) IN THE BASEMENT THERE ARE 2 DOORS WITH |
| IDENTIFICATION TAGS, NO RATINGS BUT NO LEGEND OR DOOR |
| SCHEDULE FOR THIS PAGE. 107.2.1.2. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| 3C) THERE ARE 2 DOORS IN THE STAIRWELL LABELED D2 THEY |
| DO NOT COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE FOR |
| DOORS IN SERIES. 404.2.6. |
| 4) SHEETS D102, A102 & S-2 RECONFIGURED STAIRWAY A |
| DISCREPANCY IN PLANS. SHEET D102 INDICATES A NORTH |
| STAIRWAY TO BE RECONFIGURED. SHEET A102 SHOWS THE NEW |
| RECONFIGURED STAIR. THE STRUCTURAL SHEET S-2 SHOWS THE |
| NORTH STAIRWELL AS THE D102 SHEET (ORIGINAL |
| CONFIGURATION) AND NEW STAIRWELL WALL PARTITIONS. THERE |
| IS A COMMENT ON THE STRUCTURAL SHEET NOT A PART OF THIS |
| SCOPE OF WORK. SHEET A102 INDICATES THE CONTRACTOR IS |
| TO COORDINATE CONSTRUCTION DETAILS AND SEQUENCING AND |
| SPECIAL REQUIREMENTS OF THE JURISDICTION HAVING |
| AUTHORITY PRIOR TO COMMENCING WORK. |
| PLEASE NOTE THE STATE OF FLORIDA IS A STATE WIDE CODE |
| AND IT IS THE DESIGNER OF RECORD THAT DESIGNS AND |
| PROVIDES LIVE LOADS, DEAD LOADS AND THE CONSTRUCTION |
| MATERIAL TO BE USED IN THE DESIGN OF THE NEW STAIRWAY. |
| FL. ADMINISTRATIVE CODE 61G1-23.015 (2) THE ARCHITECT |
| IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL |
| PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| FL. ADMINISTRATIVE CODE 61G1-23.015 RESPONSIBLE |
| SUPERVISING CONTROL OVER ARCHITECTURAL PRACTICE OUTSIDE |
| OF THE ARCHITECT'S OFFICE. |
| 5) SHEET A102 1ST FLOOR PLAN: |
| 5A) THE 1ST FLOOR PLAN DOES NOT IDENTIFY DOORS, THE |
| PLAN IDENTIFIES DOOR TYPES. THERE ARE NUMEROUS DOORS |
| THAT DO NOT MEET THE FBC-ACCESS. CODE 404.2.4 |
| MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING |
| CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH |
| 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL |
| WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR |
| SIDE CLEARANCE. |
| PLEASE IDENTIFY EACH DOOR WITH SEPARATE NOMENCLATURE TO |
| BE ABLE TO IDENTIFY DEFICIENCIES. |
| |
| 5B) PLEASE PROVIDE A FLOOR PLAN WITH THE KIOSK LAYOUT |
| AND COLUMNS TO ENSURE COMPLIANCE OR THE LIFE SAFETY |
| PLAN TO SCALE TO ENSURE COMPLIANCE WITH 1018.3 & 1018.4 |
| OF THE 2017 FBC-B. |
| |
| 6) PROVIDE ADDITIONAL INFORMATION FOR THE PROPOSED 6" X |
| 6" ALUMINUM COLUMN. INDICATE IF THIS IS A LOAD BEARING |
| COLUMN SUPPORTING ANY GRAVITY LOADS OR IS ONLY FOR |
| RESISTING THE LATERAL WINDLOADS ON THE STOREFRONTS THAT |
| WILL BE ATTACHED TO IT. FBC 107.2.1 |
| |
| 7) PROVIDE A STRUCTURAL ANALYSIS OF THE EXISTING |
| SUSPENDED CONCRETE SLAB THAT IS TO BE REMOVED TO |
| ACCOMMODATE THE PROPOSED ADA ACCESSIBLE RAMP. FBC |
| 107.2.1.2 |
| |
| 8) THE PROPOSED RAMP IS REQUIRED TO HAVE A MINIMUM 60" |
| CLEAR LENGTH LANDING AT THE TOP AND BOTTOM. PROVIDE |
| DIMENSIONS ON THE PLANS TO SHOW COMPLIANCE. FBC |
| ACCESSIBILITY SECTION 405.7.3 |
| |
| 9) THE PLANS DO NOT APPEAR TO SHOW ADEQUATE CLEAR SPACE |
| BETWEEN THE EXISTING WALL AND THE BOTTOM OF THE RAMP |
| RUN IN ORDER TO ACCESS THE LANDING. FBC ACCESSIBILITY |
| SECTION 405.7 REQUIRES THE LANDING TO BE 60" X 60" |
| MINIMUM WHEN THERE IS A CHANGE IN DIRECTION AT THE |
| LANDING. |
| |
| 10) THE RE-ROUTED INTERIOR EXIT STAIRWAY DOES NOT LEAD |
| DIRECTLY TO THE EXTERIOR OF THE BUILDING. IT APPEARS |
| THAT YOU INTEND TO USE AN EXIT PASSAGEWAY TO EXTEND THE |
| STAIRWAY TO THE EXTERIOR OF THE BUILDING. THE EXIT |
| PASSAGEWAY IS REQUIRED TO COMPLY WITH THE FOLLOWING |
| CODE SECTIONS. |
| FBC 1023.1 GENERAL. INTERIOR EXIT STAIRWAYS AND RAMPS |
| SERVING AS AN EXIT COMPONENT IN A MEANS OF EGRESS |
| SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS |
| SECTION. INTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE |
| ENCLOSED AND LEAD DIRECTLY TO THE EXTERIOR OF THE |
| BUILDING OR SHALL BE EXTENDED TO THE EXTERIOR OF THE |
| BUILDING WITH AN EXIT PASSAGEWAY CONFORMING TO THE |
| REQUIREMENTS OF SECTION 1024, EXCEPT AS PERMITTED IN |
| SECTION 1028.1. AN INTERIOR EXIT STAIRWAY OR RAMP SHALL |
| NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS OF |
| EGRESS AND A CIRCULATION PATH. |
| |
| 10A) 1023.3.1 EXTENSION. |
| WHERE INTERIOR EXIT STAIRWAYS AND RAMPS ARE EXTENDED TO |
| AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT |
| PASSAGEWAY, THE INTERIOR EXIT STAIRWAY AND RAMP SHALL |
| BE SEPARATED FROM THE EXIT PASSAGEWAY BY A FIRE BARRIER |
| CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR A |
| HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 711, OR BOTH. THE FIRE-RESISTANCE RATING SHALL |
| BE NOT LESS THAN THAT REQUIRED FOR THE INTERIOR EXIT |
| STAIRWAY AND RAMP. A FIRE DOOR ASSEMBLY COMPLYING WITH |
| SECTION 716.5 SHALL BE INSTALLED IN THE FIRE BARRIER TO |
| PROVIDE A MEANS OF EGRESS FROM THE INTERIOR EXIT |
| STAIRWAY AND RAMP TO THE EXIT PASSAGEWAY. OPENINGS IN |
| THE FIRE BARRIER OTHER THAN THE FIRE DOOR ASSEMBLY ARE |
| PROHIBITED. PENETRATIONS OF THE FIRE BARRIER ARE |
| PROHIBITED. |
| EXCEPTIONS: |
| -1.PENETRATIONS OF THE FIRE BARRIER IN ACCORDANCE WITH |
| SECTION 1023.5 SHALL BE PERMITTED. |
| -2.SEPARATION BETWEEN AN INTERIOR EXIT STAIRWAY OR RAMP |
| AND THE EXIT PASSAGEWAY EXTENSION SHALL NOT BE REQUIRED |
| WHERE THERE ARE NO OPENINGS INTO THE EXIT PASSAGEWAY |
| EXTENSION. |
| |
| 10B) 1024.2 WIDTH. |
| THE REQUIRED CAPACITY OF EXIT PASSAGEWAYS SHALL BE |
| DETERMINED AS SPECIFIED IN SECTION 1005.1 BUT THE |
| MINIMUM WIDTH SHALL BE NOT LESS THAN 44 INCHES (1118 |
| MM), EXCEPT THAT EXIT PASSAGEWAYS SERVING AN OCCUPANT |
| LOAD OF LESS THAN 50 SHALL BE NOT LESS THAN 36 INCHES |
| (914 MM) IN WIDTH. THE MINIMUM WIDTH OR REQUIRED |
| CAPACITY OF EXIT PASSAGEWAYS SHALL BE UNOBSTRUCTED. |
| |
| 10C) 1024.5 OPENINGS. |
| EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN |
| ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. |
| EXCEPT AS PERMITTED IN SECTION 402.8.7, OPENINGS IN |
| EXIT PASSAGEWAYS OTHER THAN UNPROTECTED EXTERIOR |
| OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE EXIT PASSAGEWAY. |
| WHERE AN INTERIOR EXIT STAIRWAY OR RAMP IS EXTENDED TO |
| AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT |
| PASSAGEWAY, THE EXIT PASSAGEWAY SHALL COMPLY WITH |
| SECTION 1023.3.1. |
| ELEVATORS SHALL NOT OPEN INTO AN EXIT PASSAGEWAY. |
| |
| 10D) 1024.6 PENETRATIONS. |
| PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE |
| PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY |
| FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT |
| PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL |
| NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| EXCEPTION: MEMBRANE PENETRATIONS SHALL BE PERMITTED ON |
| THE OUTSIDE OF THE EXIT PASSAGEWAY. SUCH PENETRATIONS |
| SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.3.2. |
| |
| 10E) 1024.7 VENTILATION. |
| EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION |
| AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF |
| THE FOLLOWING: |
| -1.THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR |
| TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE |
| EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS |
| REQUIRED FOR SHAFTS. |
| -2.WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN |
| THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN |
| DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE |
| DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL |
| BE CONVEYED THROUGH DUCTS ENCLOSED |
| IN CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| -3.WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND |
| DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE |
| BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH |
| CONSTRUCTION AS REQUIRED FOR SHAFTS. |
| IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED |
| CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR |
| MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY |
| OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR |
| SHAFT ENCLOSURES. |
| EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE |
| INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS. |
| |
| 11) IDENTIFY ALL EXISTING BUILDING SYSTEMS AND ALL |
| PROPOSED SYSTEMS THAT ARE OR WILL BE LOCATED ABOVE THE |
| 2 HR FIRE RESISTANCE RATED CEILING OF THE EXIT |
| PASSAGEWAY. INCLUDING BUT NOT LIMITED TO PLUMBING THAT |
| COULD LEAK AND COMPROMISE THE HORIZONTAL GYPSUM WALL |
| BOARD SHAFT ASSEMBLY CEILING. FBC 107.2.1 |
| |
| 12) SPECIFY THE CLEAR WIDTH OF THE EXISTING EXTERIOR |
| EXIT ACCESS. FBC 1028.2 |
| |
| 13) THE EXISTING GATE AT THE TERMINATION OF THE |
| EXTERIOR EXIT ACCESS SWINGS OUT INTO THE ALLEYWAY. IT |
| WILL HAVE TO BE RELOCATED SO THAT IT DOES NOT SWING |
| PAST THE PROPERTY LINE. FBC 3202.2 &1028.5 |
| |
| 14) THERE WILL NEED TO BE SIGNS POSTED AT THIS EXIT |
| INTO THE ALLEYWAY STATING THAT THIS IS AN EMERGENCY |
| EXIT AND IT IS NOT TO BE BLOCKED. FBC FBC 1028.5 |
| |
| 15) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| MULLIONS, STORE FRONTS AND EXTERIOR DOOR TYPES. |
| |
| 16) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW |
| COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS |
| PROVIDED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |