Plan Review Notes
Plan Review Notes For Permit 19101152
Permit Number 19101152
Review Stop B
Sequence Number 1
Notes
Date Text
2019-11-01 10:56:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101152
 ADD: 300 CLEMATIS ST. 1ST FLOOR SUITE
 CONT: BUILTMORE CONTRACTING/ CBC
 TEL: 561-331-1476
 E-MAIL: INFO: BUILTMORECONTRACTING.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE COVERSHEET LIST THIS PROJECT AS A LEVEL II
 ALTERATION. PLEASE NOTE THE LAST PERMITTED AND BUSINESS
 TAX RECEIPT FOR THE CORNER OCCUPANT WAS A RESTAURANT.
 THIS MAKES THE PROJECT A CHANGE OF OCCUPANCY UNDER THE
 2017 EXISTING BUILDING CODE CHAPTER 10 AND SECTION
 1001.3.1. PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OR GROUP OF A
 PORTION OF AN EXISTING BUILDING IS CHANGED, SECTION
 1012 SHALL APPLY.
  
 2) THE LIFE SAFETY SHEET LS102:
 2A) ON THE GROUND FLOOR DETAIL THE OCCUPANT LOAD FACTOR
 IS BEING TAKEN AT 30 SQ. FT. PER OCCUPANT. IN THE
 OCCUPANT LOAD CALCULATIONS THE SAME OCCUPANT LOAD
 FACTOR OF 30 SQ. FT. PER OCCUPANT IS USED. PLEASE
 UPDATE THE PLANS TO 60 SQ. FT. PER OCCUPANT LOAD
 FACTOR. THIS IS A CHANGE TO THE 2017 FBC-B BLACK LINED
 IN MARGIN, TABLE 1004.1.2 SEE MERCANTILE.
  
 2B) BOTH THE 3/32 INCH SCALE AND 3/16 INCH SCALE PLANS
 HAVE BEEN SHRUNK, THEY HAVE BEEN SHRUNK OVER 50% OF THE
 VALUE SCALE INDICATED ON THE PLANS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER.
 2C)EGRESS REQUIREMENTS-MERCANTILE : NEW OCCUPANCY
 2C)(1) EXIT ACCESS TRAVEL IS GIVEN TABLE 1016.1 UPDATE
 PLANS TO THE 2017 FBC-B
 2C)(2) THE MINIMUM CLEAR WIDTH REQUIREMENTS FOR THE
 2017 FBC-BUILDING ARE NOT GIVEN.
 2C)(3) THE CAPACITY FACTOR FOR LEVEL/ RAMP REQUIREMENTS
 FOR THE 2017 FBC-BUILDING ARE NOT GIVEN.
 2C)(4) THE CAPACITY FACTOR FOR STAIRS REQUIREMENTS FOR
 THE 2017 FBC-BUILDING ARE NOT GIVEN.
 2C)(5) THE COMMON PATH OF TRAVEL REQUIREMENTS FOR THE
 2017 FBC-BUILDING ARE NOT GIVEN.
 COMMON PATH OF TRAVEL FOR THE BASEMENT CANNOT BE
 DETERMINED SINCE THE PLANS ARE NOT DRAWN TO SCALE AS
 INDICATED ON THE PLANS. 2017 FBC-B TABLE 1006.2.1. &
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) SINCE THE BASEMENT PLAN IS NOT TO SCALE AND THE
 WALK IN COOLER IS INDICATED NOT IN THE SCOPE OF WORK,
 THE SQ. F.T OF THE BASEMENT CANNOT BE DETERMINED NOR
 THE OCCUPANT LOAD. VERTICAL ACCESSIBILITY MAYBE A
 REQUIREMENT IF THE OCCUPANT LOAD IS GREATER THAN 5
 OCCUPANTS. 2017 FBC-ACCESSIBILITY CODE SECTION 201.1.1.
 2E) THIS BUILDING AND THE SCOPE OF WORK WILL QUALIFY
 FOR A RESIDENT INSPECTOR. WE WILL BE E-MAILING THE
 LISTED CONTACT THE GUIDELINES POLICIES AND FORMS TO BE
 FILED OUT AND RETURNED TO THE BUILDING DEPARTMENT FOR
 REVIEW AND APPROVAL.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION.
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 FORMS WERE E-MAILED TO: BUILTMORECONTRACTING.COM SENT:
 9:08 AM WED. OCT. 30/2019
  
 2F) THE COVERSHEET UNDER THE HEADING BUILDING
 INFORMATION LIST THE CONSTRUCTION TYPE AS : II-B.
 PLEASE REVIEW SHEET S-2 INFILL OF THE 1ST FLOOR AND
 SECTION 1 ON S-1 SHOWS WOOD FRAMING AND ONE LAYER OF
 3/4 INCH PLYWOOD DECKING. THE 2017 FBC-B SECTION 603.1
 ALLOWABLE COMBUSTIBLE MATERIALS IN TYPE I AND II
 CONSTRUCTION. THIS SECTION DOES NOT LIST FLOOR FRAMING
 AT ALL, NOT EVEN FOR FIRE RETARDANT TREATED WOOD.
  
 2G) THE PLAN IS ALSO SILENT AS TO THE REQUIREMENTS OF
 HORIZONTAL FIRE BARRIERS FOR THE BASEMENT TO 1ST FLOOR
 AND 1ST FLOOR TO THE 2ND FLOOR. PLEASE SHOW HOW
 COMPLIANCE WITH TABLE 707.3.10 WILL BE MET. NOTE THERE
 IS A 2ND FLOOR INFILL THAT WILL ALSO NEED TO BE SHOWN
 ON THE PLANS.
  
 3) SHEET A101:
 3A) IN THE BASEMENT PLAN WALL IDENTIFICATION TAGS ARE
 GIVEN BUT THERE IS NO LEGEND ON THIS SHEET FOR
 REFERENCE. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
 3B) IN THE BASEMENT THERE ARE 2 DOORS WITH
 IDENTIFICATION TAGS, NO RATINGS BUT NO LEGEND OR DOOR
 SCHEDULE FOR THIS PAGE. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
 3C) THERE ARE 2 DOORS IN THE STAIRWELL LABELED D2 THEY
 DO NOT COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE FOR
 DOORS IN SERIES. 404.2.6.
 4) SHEETS D102, A102 & S-2 RECONFIGURED STAIRWAY A
 DISCREPANCY IN PLANS. SHEET D102 INDICATES A NORTH
 STAIRWAY TO BE RECONFIGURED. SHEET A102 SHOWS THE NEW
 RECONFIGURED STAIR. THE STRUCTURAL SHEET S-2 SHOWS THE
 NORTH STAIRWELL AS THE D102 SHEET (ORIGINAL
 CONFIGURATION) AND NEW STAIRWELL WALL PARTITIONS. THERE
 IS A COMMENT ON THE STRUCTURAL SHEET NOT A PART OF THIS
 SCOPE OF WORK. SHEET A102 INDICATES THE CONTRACTOR IS
 TO COORDINATE CONSTRUCTION DETAILS AND SEQUENCING AND
 SPECIAL REQUIREMENTS OF THE JURISDICTION HAVING
 AUTHORITY PRIOR TO COMMENCING WORK.
 PLEASE NOTE THE STATE OF FLORIDA IS A STATE WIDE CODE
 AND IT IS THE DESIGNER OF RECORD THAT DESIGNS AND
 PROVIDES LIVE LOADS, DEAD LOADS AND THE CONSTRUCTION
 MATERIAL TO BE USED IN THE DESIGN OF THE NEW STAIRWAY.
 FL. ADMINISTRATIVE CODE 61G1-23.015 (2) THE ARCHITECT
 IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL
 PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
 FL. ADMINISTRATIVE CODE 61G1-23.015 RESPONSIBLE
 SUPERVISING CONTROL OVER ARCHITECTURAL PRACTICE OUTSIDE
 OF THE ARCHITECT'S OFFICE.
 5) SHEET A102 1ST FLOOR PLAN:
 5A) THE 1ST FLOOR PLAN DOES NOT IDENTIFY DOORS, THE
 PLAN IDENTIFIES DOOR TYPES. THERE ARE NUMEROUS DOORS
 THAT DO NOT MEET THE FBC-ACCESS. CODE 404.2.4
 MANEUVERING CLEARANCES. DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE FOR
 SIDE CLEARANCE.
 PLEASE IDENTIFY EACH DOOR WITH SEPARATE NOMENCLATURE TO
 BE ABLE TO IDENTIFY DEFICIENCIES.
  
 5B) PLEASE PROVIDE A FLOOR PLAN WITH THE KIOSK LAYOUT
 AND COLUMNS TO ENSURE COMPLIANCE OR THE LIFE SAFETY
 PLAN TO SCALE TO ENSURE COMPLIANCE WITH 1018.3 & 1018.4
 OF THE 2017 FBC-B.
  
 6) PROVIDE ADDITIONAL INFORMATION FOR THE PROPOSED 6" X
 6" ALUMINUM COLUMN. INDICATE IF THIS IS A LOAD BEARING
 COLUMN SUPPORTING ANY GRAVITY LOADS OR IS ONLY FOR
 RESISTING THE LATERAL WINDLOADS ON THE STOREFRONTS THAT
 WILL BE ATTACHED TO IT. FBC 107.2.1
  
 7) PROVIDE A STRUCTURAL ANALYSIS OF THE EXISTING
 SUSPENDED CONCRETE SLAB THAT IS TO BE REMOVED TO
 ACCOMMODATE THE PROPOSED ADA ACCESSIBLE RAMP. FBC
 107.2.1.2
  
 8) THE PROPOSED RAMP IS REQUIRED TO HAVE A MINIMUM 60"
 CLEAR LENGTH LANDING AT THE TOP AND BOTTOM. PROVIDE
 DIMENSIONS ON THE PLANS TO SHOW COMPLIANCE. FBC
 ACCESSIBILITY SECTION 405.7.3
  
 9) THE PLANS DO NOT APPEAR TO SHOW ADEQUATE CLEAR SPACE
 BETWEEN THE EXISTING WALL AND THE BOTTOM OF THE RAMP
 RUN IN ORDER TO ACCESS THE LANDING. FBC ACCESSIBILITY
 SECTION 405.7 REQUIRES THE LANDING TO BE 60" X 60"
 MINIMUM WHEN THERE IS A CHANGE IN DIRECTION AT THE
 LANDING.
  
 10) THE RE-ROUTED INTERIOR EXIT STAIRWAY DOES NOT LEAD
 DIRECTLY TO THE EXTERIOR OF THE BUILDING. IT APPEARS
 THAT YOU INTEND TO USE AN EXIT PASSAGEWAY TO EXTEND THE
 STAIRWAY TO THE EXTERIOR OF THE BUILDING. THE EXIT
 PASSAGEWAY IS REQUIRED TO COMPLY WITH THE FOLLOWING
 CODE SECTIONS.
 FBC 1023.1 GENERAL. INTERIOR EXIT STAIRWAYS AND RAMPS
 SERVING AS AN EXIT COMPONENT IN A MEANS OF EGRESS
 SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION. INTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE
 ENCLOSED AND LEAD DIRECTLY TO THE EXTERIOR OF THE
 BUILDING OR SHALL BE EXTENDED TO THE EXTERIOR OF THE
 BUILDING WITH AN EXIT PASSAGEWAY CONFORMING TO THE
 REQUIREMENTS OF SECTION 1024, EXCEPT AS PERMITTED IN
 SECTION 1028.1. AN INTERIOR EXIT STAIRWAY OR RAMP SHALL
 NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS OF
 EGRESS AND A CIRCULATION PATH.
  
 10A) 1023.3.1 EXTENSION.
 WHERE INTERIOR EXIT STAIRWAYS AND RAMPS ARE EXTENDED TO
 AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT
 PASSAGEWAY, THE INTERIOR EXIT STAIRWAY AND RAMP SHALL
 BE SEPARATED FROM THE EXIT PASSAGEWAY BY A FIRE BARRIER
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR A
 HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. THE FIRE-RESISTANCE RATING SHALL
 BE NOT LESS THAN THAT REQUIRED FOR THE INTERIOR EXIT
 STAIRWAY AND RAMP. A FIRE DOOR ASSEMBLY COMPLYING WITH
 SECTION 716.5 SHALL BE INSTALLED IN THE FIRE BARRIER TO
 PROVIDE A MEANS OF EGRESS FROM THE INTERIOR EXIT
 STAIRWAY AND RAMP TO THE EXIT PASSAGEWAY. OPENINGS IN
 THE FIRE BARRIER OTHER THAN THE FIRE DOOR ASSEMBLY ARE
 PROHIBITED. PENETRATIONS OF THE FIRE BARRIER ARE
 PROHIBITED.
 EXCEPTIONS:
 -1.PENETRATIONS OF THE FIRE BARRIER IN ACCORDANCE WITH
 SECTION 1023.5 SHALL BE PERMITTED.
 -2.SEPARATION BETWEEN AN INTERIOR EXIT STAIRWAY OR RAMP
 AND THE EXIT PASSAGEWAY EXTENSION SHALL NOT BE REQUIRED
 WHERE THERE ARE NO OPENINGS INTO THE EXIT PASSAGEWAY
 EXTENSION.
  
 10B) 1024.2 WIDTH.
 THE REQUIRED CAPACITY OF EXIT PASSAGEWAYS SHALL BE
 DETERMINED AS SPECIFIED IN SECTION 1005.1 BUT THE
 MINIMUM WIDTH SHALL BE NOT LESS THAN 44 INCHES (1118
 MM), EXCEPT THAT EXIT PASSAGEWAYS SERVING AN OCCUPANT
 LOAD OF LESS THAN 50 SHALL BE NOT LESS THAN 36 INCHES
 (914 MM) IN WIDTH. THE MINIMUM WIDTH OR REQUIRED
 CAPACITY OF EXIT PASSAGEWAYS SHALL BE UNOBSTRUCTED.
  
 10C) 1024.5 OPENINGS.
 EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716.
 EXCEPT AS PERMITTED IN SECTION 402.8.7, OPENINGS IN
 EXIT PASSAGEWAYS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE EXIT PASSAGEWAY FROM NORMALLY OCCUPIED
 SPACES AND FOR EGRESS FROM THE EXIT PASSAGEWAY.
 WHERE AN INTERIOR EXIT STAIRWAY OR RAMP IS EXTENDED TO
 AN EXIT DISCHARGE OR A PUBLIC WAY BY AN EXIT
 PASSAGEWAY, THE EXIT PASSAGEWAY SHALL COMPLY WITH
 SECTION 1023.3.1.
 ELEVATORS SHALL NOT OPEN INTO AN EXIT PASSAGEWAY.
  
 10D) 1024.6 PENETRATIONS.
 PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE
 PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL
 NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
 EXCEPTION: MEMBRANE PENETRATIONS SHALL BE PERMITTED ON
 THE OUTSIDE OF THE EXIT PASSAGEWAY. SUCH PENETRATIONS
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.3.2.
  
 10E) 1024.7 VENTILATION.
 EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION
 AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF
 THE FOLLOWING:
 -1.THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR
 TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE
 EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS
 REQUIRED FOR SHAFTS.
 -2.WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED
 IN CONSTRUCTION AS REQUIRED FOR SHAFTS.
 -3.WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND
 DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH
 CONSTRUCTION AS REQUIRED FOR SHAFTS.
 IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR
 SHAFT ENCLOSURES.
 EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE
 INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS.
  
 11) IDENTIFY ALL EXISTING BUILDING SYSTEMS AND ALL
 PROPOSED SYSTEMS THAT ARE OR WILL BE LOCATED ABOVE THE
 2 HR FIRE RESISTANCE RATED CEILING OF THE EXIT
 PASSAGEWAY. INCLUDING BUT NOT LIMITED TO PLUMBING THAT
 COULD LEAK AND COMPROMISE THE HORIZONTAL GYPSUM WALL
 BOARD SHAFT ASSEMBLY CEILING. FBC 107.2.1
  
 12) SPECIFY THE CLEAR WIDTH OF THE EXISTING EXTERIOR
 EXIT ACCESS. FBC 1028.2
  
 13) THE EXISTING GATE AT THE TERMINATION OF THE
 EXTERIOR EXIT ACCESS SWINGS OUT INTO THE ALLEYWAY. IT
 WILL HAVE TO BE RELOCATED SO THAT IT DOES NOT SWING
 PAST THE PROPERTY LINE. FBC 3202.2 &1028.5
  
 14) THERE WILL NEED TO BE SIGNS POSTED AT THIS EXIT
 INTO THE ALLEYWAY STATING THAT THIS IS AN EMERGENCY
 EXIT AND IT IS NOT TO BE BLOCKED. FBC FBC 1028.5
  
 15) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS, STORE FRONTS AND EXTERIOR DOOR TYPES.
  
 16) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. ADDITIONAL PLAN REVIEW
 COMMENTS MAY BE GENERATED WHEN MORE INFORMATION IS
 PROVIDED.
  
  
  
  
  
  
  
  
  
  