2019-12-16 14:47:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL COMPLY WITH NFPA 101, CH 7,
 MEANS OF EGRESS.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE
 ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED
 HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN
 THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY IN
 THE DIRECTION OF EGRESS.
 (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF
 EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
 7.2.1.5.7 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 KEY
 OPERATION SHALL BE PERMITTED, PROVIDED THAT THE KEY
 CANNOT BE
 REMOVED WHEN THE DOOR LEAF IS LOCKED FROM THE SIDE FROM
 WHICH
 EGRESS IS TO BE MADE.
 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE
 THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2,
 SHALL MEET ONE
 OF THE FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE
 BUILDING SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF
 THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO
 UNLOCK ALL
 STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH 7.2.1.5.8.1
  
  
  
 PETER LEDUC