Plan Review Notes
Plan Review Notes For Permit 19101085
Permit Number 19101085
Review Stop P
Sequence Number 2
Notes
Date Text
2020-01-02 11:48:502ND REVIEW
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUEFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL-AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC
  
 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE
 !!!GRAB BARS SHALL BE SHOWN TO BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR.!!
  
  
 2. PROVIDE DETAIL SHOWING CLEAR FLOOR SPACE FOR TOILET
 AND LAVATORY WITH DIMENSIONS CLEAR FLOOR SPACE SHALL
 EXTEND UNDER FIXTURES. PER FBC ACC 606.2, 604.3.1,
 305.5, 305.3
 !! THE CLEAR FLOOR SPACE IS SHOW PLEASE INCLUDE THE
 DIMENSIONS!!3. SHT LS -1 ALL THE BATHROOMS ARE LABELED
 UNISEX THE PLUMBING CODE REQUIRES SEPARATE FACILITIES
 FOR EACH SEX AT LEAST 2 OF THE UNISEX SHALL BE LABELED
 FEMALE AND MALE 1 FOR EACH LOCATED IN SAME LOCATION.
 PER FBC PL 403.2
  
 5. PROVIDE OCCUPANT LOAD. PER WPB AMEND TO FBC 107.2.1
 !!RESPONE LEETER STATAED IT WAS LOCATED ON SHEET T-1 I
 COULD NOT FIND THE OCCUPANT LOAD I FOUND OCCUPANCY TYPE
 BUT NOT LOAD.!!
  
  
  
  
 8. A WATER FOUNTAIN IS REQUIRED SHOW COMPLIANCE WITH
 FBC ACC 602.2, 602.4, 602.7, PER FBC PL TABLE 403.1
 !!A HIGH LOW WATER FOUNTAIN IS REQUIRED OR TWO
 FOUNTAINS IN ORDER TO COMPLY WITH FBC ACC 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 10. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 11. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 NEW COMMENTS:
  
 1. SHT. P-1 NOTE #4 HUBLESS PVC IS NOT AN APPROVED TYPE
 OF PIPING SYSTEM DO YOU MEAN TO SAY HUBLESS CAST IRON
 OR SCH 40 PVC PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. P-1 NOTE #8 STATES THE WATER HEATER SHALL
 COMPLY WITH FBC 2014 THE CURRENT CODE IN AFFECT SHALL
 BE FBC 2017 PLEASE CORRECT NOTE ON PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 3. THE DOORS ON THE BATHROOMS SHALL BE ON THE OPPOSITE
 SIDE AWAY FROM THE TOILET. PER FBC ACC 604.8.1.2
  
 4. THE KITCHEN SINKS SHALL COMPLY WITH FBC ACC 804.3.1
 PLEASE SHOW CLEAR FLOOR SPACE AT KITCHEN SINK.
  
 5. SHT. P-2 SERVICE SINK NOT SHOWN ON SANITARY
 ISOMETRIC. . PER WPB AMEND TO FBC 107.2.1
  
 6. A RECIRCULATION ON THE HOT WATER SYSTEM IS REQUIRED.
 PER FBC PL 607.2
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]