Date |
Text |
2020-01-02 11:48:50 | 2ND REVIEW |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUEFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROL-AND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH. |
| |
| 1. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| |
| 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE |
| INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| TO THE TOP OF THE GRIPPING SURFACE |
| !!!GRAB BARS SHALL BE SHOWN TO BE MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE FROM FINISHED FLOOR.!! |
| |
| |
| 2. PROVIDE DETAIL SHOWING CLEAR FLOOR SPACE FOR TOILET |
| AND LAVATORY WITH DIMENSIONS CLEAR FLOOR SPACE SHALL |
| EXTEND UNDER FIXTURES. PER FBC ACC 606.2, 604.3.1, |
| 305.5, 305.3 |
| !! THE CLEAR FLOOR SPACE IS SHOW PLEASE INCLUDE THE |
| DIMENSIONS!!3. SHT LS -1 ALL THE BATHROOMS ARE LABELED |
| UNISEX THE PLUMBING CODE REQUIRES SEPARATE FACILITIES |
| FOR EACH SEX AT LEAST 2 OF THE UNISEX SHALL BE LABELED |
| FEMALE AND MALE 1 FOR EACH LOCATED IN SAME LOCATION. |
| PER FBC PL 403.2 |
| |
| 5. PROVIDE OCCUPANT LOAD. PER WPB AMEND TO FBC 107.2.1 |
| !!RESPONE LEETER STATAED IT WAS LOCATED ON SHEET T-1 I |
| COULD NOT FIND THE OCCUPANT LOAD I FOUND OCCUPANCY TYPE |
| BUT NOT LOAD.!! |
| |
| |
| |
| |
| 8. A WATER FOUNTAIN IS REQUIRED SHOW COMPLIANCE WITH |
| FBC ACC 602.2, 602.4, 602.7, PER FBC PL TABLE 403.1 |
| !!A HIGH LOW WATER FOUNTAIN IS REQUIRED OR TWO |
| FOUNTAINS IN ORDER TO COMPLY WITH FBC ACC 211.2 MINIMUM |
| NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE |
| PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 |
| THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY |
| WITH 602.7. |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES |
| (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT |
| OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| |
| 10. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO |
| FBC 107.3.5.1.3(13) |
| |
| 11. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| NEW COMMENTS: |
| |
| 1. SHT. P-1 NOTE #4 HUBLESS PVC IS NOT AN APPROVED TYPE |
| OF PIPING SYSTEM DO YOU MEAN TO SAY HUBLESS CAST IRON |
| OR SCH 40 PVC PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 2. SHT. P-1 NOTE #8 STATES THE WATER HEATER SHALL |
| COMPLY WITH FBC 2014 THE CURRENT CODE IN AFFECT SHALL |
| BE FBC 2017 PLEASE CORRECT NOTE ON PLAN. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 3. THE DOORS ON THE BATHROOMS SHALL BE ON THE OPPOSITE |
| SIDE AWAY FROM THE TOILET. PER FBC ACC 604.8.1.2 |
| |
| 4. THE KITCHEN SINKS SHALL COMPLY WITH FBC ACC 804.3.1 |
| PLEASE SHOW CLEAR FLOOR SPACE AT KITCHEN SINK. |
| |
| 5. SHT. P-2 SERVICE SINK NOT SHOWN ON SANITARY |
| ISOMETRIC. . PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. A RECIRCULATION ON THE HOT WATER SYSTEM IS REQUIRED. |
| PER FBC PL 607.2 |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |