Plan Review Notes For Permit 19101085 |
Permit Number |
19101085 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-12-31 15:07:01 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #19101085 | | 12/31/2019 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENTS LISTED BELOW FROM THE 1ST REVIEW STILL EXIST- | | PLEASE COMPLY. | | | | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | AC SYSTEMS- SECTION C403.2.1 FBC EC. | | | | 8) REFER TO SECTION C103.1.1.1.2 FBC EC: THE ARCHITECT | | SHALL PROVIDE HIS REGSITRATION NUMBER ON THE | | CERTIFICATIONS PAGE 4 OF THE ENERGYGAUGE COMPLIANCE | | REPORT. (PLEASE NOTE THAT THE INPUT DATA REPORT IS | | MISSING FROM THE ENERGYGAUGE COMPLIANCE SUBMITTAL. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|