2019-12-31 15:07:012ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19101085
 12/31/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS LISTED BELOW FROM THE 1ST REVIEW STILL EXIST-
 PLEASE COMPLY.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 8) REFER TO SECTION C103.1.1.1.2 FBC EC: THE ARCHITECT
 SHALL PROVIDE HIS REGSITRATION NUMBER ON THE
 CERTIFICATIONS PAGE 4 OF THE ENERGYGAUGE COMPLIANCE
 REPORT. (PLEASE NOTE THAT THE INPUT DATA REPORT IS
 MISSING FROM THE ENERGYGAUGE COMPLIANCE SUBMITTAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  