Plan Review Notes
Plan Review Notes For Permit 19101085
Permit Number 19101085
Review Stop E
Sequence Number 2
Notes
Date Text
2019-12-31 08:19:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. PROVIDE
 LOCATION OF ANY ELECTRICAL PANELS LOCATED INSIDE THE
 UNITS. NEC 215.5; WPB FBC 107.2.1 (RISER DIAGRAM IS NOT
 ACCURATE. IF THIS IS A SINGLE PHASE SERVICE, THE
 VOLTAGE WOULD BE 120/240. IF THIS IS A THREE PHASE
 SERVICE, THE VOLTAGE WOULD BE 120/208. THE PROPER
 VOLTAGE MUST BE STATED AND USED IN THE LOAD
 CALCULATION. FEEDERS SHOULD BE SIZED PER NEC 215.2.
 PROVIDE CORRECITON.)
  
 NEW COMMENT:
  
 5. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. THIS LOAD CALCULATION SHOULD
 INCLUDE A CALCULAITON FOR THE INDIVIDUAL PANELS, AND
 ALSO A TOTAL CALCULATION FOR THE SERVICE. NEC 215.2,
 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  