2019-12-31 13:04:22BUILDING REVIEW COMMENTS:
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101085
 ADD: 471 SPENSER AVE.
 CONT: ATLANTIC REAL ESTATE & BUILDING
 TEL: 561-602-3295
 E-MAIL: [email protected]
  
 FIRST REVIEW DATE: TUES. NOV. 26/2019
 ACTION: DENIED
  
 SECOND REVIEW: DECEMBER 31, 2019
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) OK
  
 2A) OK
  
 2B) OK
  
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD / GROSS
 2 ND REVIEW - PLEASE PROVIDE THE TOTAL OCCUPANT LOAD ON
 LIFE SAFETY SHEET BASED OFF THE SQ. FOOTAGE AND B
 OCCUPANCY.
 GENERAL DATA:
 INDICATE IF NON-SPRINKLED
 STATE TOTAL AREA UNDER AIR AND TOTAL AREA NEW OUTDOOR
 -THIS DATA IS NEEDED BECAUSE IT WILL BE PRINTED ON THE
 NEW CERTIFICATE OF OCCUPANCY
  
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS
 2 ND REVIEW ? PLEASE ADJUST WIND CRITERIA TO MATCH FROM
 SHEET S-1 AND S-2. THEY SHOW CONFLICTING DATA.
 SHEET S-3 IS CORRECT FOR WIND SPEED OF VULT 170 MPH AND
 ASD SHOULD 132 MPH.
 PLEASE ADJUST SHEET S-3 BUILDING CODE TABLE NUMBER 6
 AND 7. THE DATA SHOULD MATCH THE CONSTRUCTION TYPE
 SELECTED. SHEET S-1 STATES VB AND SHEET S-3 STATES 1A.
  
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 2 ND REVIEW - NEW PLANS SHOW PARKING LOT. IS THE
 PARKING LOT BEING RE-STRIPED?
 THIS WOULD BE UNDER SEPARATE PERMIT AND THE ADA SPOTS
 NEED TO SHOW ACCESS AISLE AND ACCESSIBLE ROUTE INTO THE
 BUILDING.
  
 ALSO, REMOVE LANDSCAPE SHEETS AS LANDSCAPING WOULD BE
 UNDER A SEPARATE PERMIT.
  
 3)-3C) OK
  
  
 4) SHEET A-3 THE PROPOSED FLOOR PLAN:
 2 ND REVIEW - SHEET A-3 AT DOOR 113 AND 114 SAYS SEE
 DETAIL ON D-1. SINCE THERE IS NO D-1, PLEASE UPADTE THE
 REFERENCE TO THE DETAIL THAT NUMBER AND SHEET WHERE IT
 CAN BE FOUND.
  
 4C)- 4G) OK
  
 4H)
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 2 ND REVIEW ? DETAIL OF HOW THE FOUNTAIN MEETS 307 AND
 602 OF ACCESSIBILITY CODE.
 ALSO, COMPLY WITH PLUMBING SECTION 410.3 FOR HI-LOW.
  
 4I)-4Y) OK
  
 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE
 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY
 OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT
 THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO
 DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS.
 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS
 REVIEW CYCLE.
 2 ND REVIEW ? DECORATIVE AWNINGS TO BE SUBMITTED UNDER
 SEPARATE PERMIT. PLEASE ADD NOTE AND PROVIDE ALL
 ATTACHMENT WITH THAT PERMIT.
  
 4BB) SEE ABOVE
  
 5)- 6 OK
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  