2019-12-31 13:04:22 | BUILDING REVIEW COMMENTS: |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101085 |
| ADD: 471 SPENSER AVE. |
| CONT: ATLANTIC REAL ESTATE & BUILDING |
| TEL: 561-602-3295 |
| E-MAIL: [email protected] |
| |
| FIRST REVIEW DATE: TUES. NOV. 26/2019 |
| ACTION: DENIED |
| |
| SECOND REVIEW: DECEMBER 31, 2019 |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) OK |
| |
| 2A) OK |
| |
| 2B) OK |
| |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD / GROSS |
| 2 ND REVIEW - PLEASE PROVIDE THE TOTAL OCCUPANT LOAD ON |
| LIFE SAFETY SHEET BASED OFF THE SQ. FOOTAGE AND B |
| OCCUPANCY. |
| GENERAL DATA: |
| INDICATE IF NON-SPRINKLED |
| STATE TOTAL AREA UNDER AIR AND TOTAL AREA NEW OUTDOOR |
| -THIS DATA IS NEEDED BECAUSE IT WILL BE PRINTED ON THE |
| NEW CERTIFICATE OF OCCUPANCY |
| |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS |
| 2 ND REVIEW ? PLEASE ADJUST WIND CRITERIA TO MATCH FROM |
| SHEET S-1 AND S-2. THEY SHOW CONFLICTING DATA. |
| SHEET S-3 IS CORRECT FOR WIND SPEED OF VULT 170 MPH AND |
| ASD SHOULD 132 MPH. |
| PLEASE ADJUST SHEET S-3 BUILDING CODE TABLE NUMBER 6 |
| AND 7. THE DATA SHOULD MATCH THE CONSTRUCTION TYPE |
| SELECTED. SHEET S-1 STATES VB AND SHEET S-3 STATES 1A. |
| |
| ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| 2 ND REVIEW - NEW PLANS SHOW PARKING LOT. IS THE |
| PARKING LOT BEING RE-STRIPED? |
| THIS WOULD BE UNDER SEPARATE PERMIT AND THE ADA SPOTS |
| NEED TO SHOW ACCESS AISLE AND ACCESSIBLE ROUTE INTO THE |
| BUILDING. |
| |
| ALSO, REMOVE LANDSCAPE SHEETS AS LANDSCAPING WOULD BE |
| UNDER A SEPARATE PERMIT. |
| |
| 3)-3C) OK |
| |
| |
| 4) SHEET A-3 THE PROPOSED FLOOR PLAN: |
| 2 ND REVIEW - SHEET A-3 AT DOOR 113 AND 114 SAYS SEE |
| DETAIL ON D-1. SINCE THERE IS NO D-1, PLEASE UPADTE THE |
| REFERENCE TO THE DETAIL THAT NUMBER AND SHEET WHERE IT |
| CAN BE FOUND. |
| |
| 4C)- 4G) OK |
| |
| 4H) |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| 2 ND REVIEW ? DETAIL OF HOW THE FOUNTAIN MEETS 307 AND |
| 602 OF ACCESSIBILITY CODE. |
| ALSO, COMPLY WITH PLUMBING SECTION 410.3 FOR HI-LOW. |
| |
| 4I)-4Y) OK |
| |
| 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE |
| 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY |
| OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT |
| THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO |
| DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS. |
| 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS |
| REVIEW CYCLE. |
| 2 ND REVIEW ? DECORATIVE AWNINGS TO BE SUBMITTED UNDER |
| SEPARATE PERMIT. PLEASE ADD NOTE AND PROVIDE ALL |
| ATTACHMENT WITH THAT PERMIT. |
| |
| 4BB) SEE ABOVE |
| |
| 5)- 6 OK |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |