Date |
Text |
2019-11-25 15:14:42 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19101085 |
| 11/25/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: PROVIDE AC EQUIPMENT SCHEDULES ON THE |
| PLAN- SECTION 107.2.1 WPB & SECTION C403.1 FBC EC. |
| |
| 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEMS- SECTION C403.2.1 FBC EC. |
| |
| 3) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| AIR OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1 FBC-M. |
| PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR |
| HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| SUPPLY AIR. PLEASE SHOW THE LOCATIONS OF THE DEVICES |
| WITH SYMBOLS ON THE PLAN, AND PROVIDE CONTROLS |
| OPERATION AND SUPERVISORY INFORMATION- SECTIONS 606.4 & |
| 606.4.1 FBC M. |
| |
| 4) M-1: REFER TO SECTION 809.2 FBC EX AND PROVIDE |
| MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE |
| THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF |
| OUTDOOR AIR. |
| |
| 5) M-1: SHOW HOW VENTILATION AIR (O/A) IS BEING |
| PROVIDED TO THE OCCUPANTS IN THE OFFICE SPACES- SECTION |
| 401.2 FBC M. IF USING MECHANICAL VENTILATION, SHOW THE |
| O/A DUCT RUN AND AIR INLET LOCATIONS WITH REQUIRED |
| CLEARANCES PER - SECTION 401.4 FBC M. |
| |
| 6) M-1: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR |
| GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS- SECTION |
| C403.2.4.3 FBC EC. |
| |
| 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| OF THE AC CONDENSERS WITH REQUIRED CLEARANCES, AND |
| PROVIDE ENGINEERED DETAILS FOR INSTALLATIONS. IF ROOF |
| STANDS ARE TO BE USED, SUBMIT A FL. PRODUCT APPROVAL, |
| OR MIAMI-DADE NOA. |
| |
| 8) REFER TO SECTION C103.1.1.1.2 FBC EC: THE ARCHITECT |
| SHALL PROVIDE HIS REGSITRATION NUMBER ON THE |
| CERTIFICATIONS PAGE 4 OF THE ENERGYGAUGE COMPLIANCE |
| REPORT. |
| |
| 9) THE COMPLIANCE DATA IN THE ENERGYGAUGE REPORT |
| INDICATES TWO 3-TON SYSTEMS IN THE SOUTH, HOWEVER THE |
| PLA N INDICATS ONE 5-TON SYSTEM. PLEASE CORRECT- SCTION |
| 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |