Plan Review Notes
Plan Review Notes For Permit 19101085
Permit Number 19101085
Review Stop M
Sequence Number 1
Notes
Date Text
2019-11-25 15:14:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19101085
 11/25/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE AC EQUIPMENT SCHEDULES ON THE
 PLAN- SECTION 107.2.1 WPB & SECTION C403.1 FBC EC.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC EC.
  
 3) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR OF THE 5-TON AC SYSTEMS PER SECTION 606.2.1 FBC-M.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S PERFORMANCE DATA INDICATES THE AIR
 HANDLERS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR. PLEASE SHOW THE LOCATIONS OF THE DEVICES
 WITH SYMBOLS ON THE PLAN, AND PROVIDE CONTROLS
 OPERATION AND SUPERVISORY INFORMATION- SECTIONS 606.4 &
 606.4.1 FBC M.
  
 4) M-1: REFER TO SECTION 809.2 FBC EX AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 5) M-1: SHOW HOW VENTILATION AIR (O/A) IS BEING
 PROVIDED TO THE OCCUPANTS IN THE OFFICE SPACES- SECTION
 401.2 FBC M. IF USING MECHANICAL VENTILATION, SHOW THE
 O/A DUCT RUN AND AIR INLET LOCATIONS WITH REQUIRED
 CLEARANCES PER - SECTION 401.4 FBC M.
  
 6) M-1: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR
 GRAVITY, SHALL BE PROVIDED FOR O/A DUCTS- SECTION
 C403.2.4.3 FBC EC.
  
 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE AC CONDENSERS WITH REQUIRED CLEARANCES, AND
 PROVIDE ENGINEERED DETAILS FOR INSTALLATIONS. IF ROOF
 STANDS ARE TO BE USED, SUBMIT A FL. PRODUCT APPROVAL,
 OR MIAMI-DADE NOA.
  
 8) REFER TO SECTION C103.1.1.1.2 FBC EC: THE ARCHITECT
 SHALL PROVIDE HIS REGSITRATION NUMBER ON THE
 CERTIFICATIONS PAGE 4 OF THE ENERGYGAUGE COMPLIANCE
 REPORT.
  
 9) THE COMPLIANCE DATA IN THE ENERGYGAUGE REPORT
 INDICATES TWO 3-TON SYSTEMS IN THE SOUTH, HOWEVER THE
 PLA N INDICATS ONE 5-TON SYSTEM. PLEASE CORRECT- SCTION
 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  