2019-10-31 15:24:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET T 1 - THERE IS AN INDICATION OF AAN OCCUPANCY |
| CLASS AS BUSINESS. |
| |
| BISINESS MAY HAVE BEEN THE EXISTING; HOWEVER, THE NEW |
| OCCUPANCY APPEARS TO BE ASSEMBLY. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS. |
| |
| |
| 2) IF # 1 IS ASSEMBLY THAN A A CHANGE OF OCCUPANY SHALL |
| BE INDICATED. |
| |
| PLEASE PROVIDE IF THE CHANGE OF OCCUPANCY IS |
| APPLICABLE. |
| |
| |
| |
| 3) SHEET LS 1 - THE ARE NO INDICATIONS SOF OCCUPANCY |
| LOAD AND THE DISTRIBUTION TO THE EXITS TO ENSURE THE |
| EXITS CAN HANDLE THE PROPOSED OCCUPANCY LOAD. |
| |
| PER NFPA 101 |
| |
| 7.3 CAPACITY OF MEANS OF EGRESS. |
| 7.3.1 OCCUPANT LOAD. |
| 7.3.1.1 SUFFICIENT CAPACITY. |
| 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR |
| ANY STORY, |
| BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE |
| SUFFICIENT FOR THE |
| OCCUPANT LOAD THEREOF. |
| |
| 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| NUMBER OF |
| PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED |
| TO THAT USE |
| BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED |
| IN TABLE |
| 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B). |
| WHERE BOTH |
| GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME |
| OCCUPANCY, |
| CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| FIGURE TO THE |
| GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO |
| THE USE FOR |
| WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY |
| APPLYING THE NET |
| AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| BUILDING DEVOTED TO |
| THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 4) SHEET LS 1 - IS IT THE INTENTION TO LATER SUBDIVIDE |
| THE SPACE? IF SO, THERE MAY NOT BE SUFFICIENT EXIT |
| LOCATION TO ALLOW FOR THREE SEPARATE SPACES. |
| |
| PLEASE REIVEW AND PROVIDE DETAILS |
| |
| |
| |
| 5) SHEET LS 1 & E 1 - THERE ARE INDICATIONS OF EXIT & |
| EMERGENCY LIGHTS ON LS 1; HOWEVER, THE E 1 SHEET DOES |
| NOT INDICATE THEM. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| |
| |
| 6) SHEET LS 1 - THERE ARE INDICATIONS OF TWO KITCHENS; |
| HOWEVER, THERE IS NO EQUIPMENT INDICATED. |
| |
| PLEASE PROVIDE DETAILS AND/OR JUSTIFY. |
| |
| |
| 7) THERE ARE NO INDICATIONS OF A DOOR SCHDULE INCLUDING |
| BUT NOT LIMITED EXIT HARDWARE/HANDLES/ LOCKS/LATCHES. |
| |
| 7.2 MEANS OF EGRESS COMPONENTS. |
| 7.2.1 DOOR OPENINGS. |
| 7.2.1.1 GENERAL. |
| 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| CONFORM TO |
| THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE |
| SPECIAL |
| REQUIREMENTS OF 7.2.1. |
| |
| PLEASE PROVIDE THE INDICATED DOOR SCHEDULE WITH |
| HARDWARE THAT IS APPLICABLE TO THE OCCUPANCY. |
| |
| |
| 8) THERE ARE NO INDICATION OF THE NEW OCCUPANCY CLASS, |
| AND FIRE SPRINKLER AND FIRE ALARM MAY BE REQUIRED, IF |
| ASSEMBLY, NFPA 101 CHAPTER 12 APPLIES. |
| |
| 12.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE |
| FOLLOWING |
| ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY |
| AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH 9.7.1.1(1): |
| (1) DANCE HALLS |
| (2) DISCOTHEQUES |
| (3) NIGHTCLUBS |
| (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING |
| |
| 12.3.5.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY |
| OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE |
| ASSEMBLY |
| OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH SECTION |
| 9.7 AS FOLLOWS (SEE ALSO 12.1.6, 12.2.6, 12.3.2, AND |
| 12.3.6): |
| (1) THROUGHOUT THE STORY CONTAINING THE ASSEMBLY |
| OCCUPANCY |
| (2) THROUGHOUT ALL STORIES BELOW THE STORY CONTAINING |
| THE |
| ASSEMBLY OCCUPANCY |
| (3) IN THE CASE OF AN ASSEMBLY OCCUPANCY LOCATED BELOW |
| THE LEVEL |
| OF EXIT DISCHARGE, THROUGHOUT ALL STORIES INTERVENING |
| BETWEEN |
| THAT STORY AND THE LEVEL OF EXIT DISCHARGE, INCLUDING |
| THE LEVEL |
| OF EXIT DISCHARGE |
| |
| 12.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 12.3.4.1 GENERAL. |
| 12.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF |
| MORE |
| THAN 300 AND ALL THEATERS WITH MORE THAN ONE |
| AUDIENCE-VIEWING |
| ROOM SHALL BE PROVIDED WITH AN APPROVED FIRE ALARM |
| SYSTEM IN |
| ACCORDANCE WITH 9.6.1 AND 12.3.4, UNLESS OTHERWISE |
| PERMITTED BY |
| 12.3.4.1.2. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |