Plan Review Notes
Plan Review Notes For Permit 19101085
Permit Number 19101085
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-10-31 15:24:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET T 1 - THERE IS AN INDICATION OF AAN OCCUPANCY
 CLASS AS BUSINESS.
  
 BISINESS MAY HAVE BEEN THE EXISTING; HOWEVER, THE NEW
 OCCUPANCY APPEARS TO BE ASSEMBLY.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 2) IF # 1 IS ASSEMBLY THAN A A CHANGE OF OCCUPANY SHALL
 BE INDICATED.
  
 PLEASE PROVIDE IF THE CHANGE OF OCCUPANCY IS
 APPLICABLE.
  
  
  
 3) SHEET LS 1 - THE ARE NO INDICATIONS SOF OCCUPANCY
 LOAD AND THE DISTRIBUTION TO THE EXITS TO ENSURE THE
 EXITS CAN HANDLE THE PROPOSED OCCUPANCY LOAD.
  
 PER NFPA 101
  
 7.3 CAPACITY OF MEANS OF EGRESS.
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY,
 BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE
 SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF.
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF
 PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED
 TO THAT USE
 BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED
 IN TABLE
 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B).
 WHERE BOTH
 GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME
 OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE
 GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO
 THE USE FOR
 WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY
 APPLYING THE NET
 AREA FIGURE TO THE NET AREA OF THE PORTION OF THE
 BUILDING DEVOTED TO
 THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) SHEET LS 1 - IS IT THE INTENTION TO LATER SUBDIVIDE
 THE SPACE? IF SO, THERE MAY NOT BE SUFFICIENT EXIT
 LOCATION TO ALLOW FOR THREE SEPARATE SPACES.
  
 PLEASE REIVEW AND PROVIDE DETAILS
  
  
  
 5) SHEET LS 1 & E 1 - THERE ARE INDICATIONS OF EXIT &
 EMERGENCY LIGHTS ON LS 1; HOWEVER, THE E 1 SHEET DOES
 NOT INDICATE THEM.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
 6) SHEET LS 1 - THERE ARE INDICATIONS OF TWO KITCHENS;
 HOWEVER, THERE IS NO EQUIPMENT INDICATED.
  
 PLEASE PROVIDE DETAILS AND/OR JUSTIFY.
  
  
 7) THERE ARE NO INDICATIONS OF A DOOR SCHDULE INCLUDING
 BUT NOT LIMITED EXIT HARDWARE/HANDLES/ LOCKS/LATCHES.
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 PLEASE PROVIDE THE INDICATED DOOR SCHEDULE WITH
 HARDWARE THAT IS APPLICABLE TO THE OCCUPANCY.
  
  
 8) THERE ARE NO INDICATION OF THE NEW OCCUPANCY CLASS,
 AND FIRE SPRINKLER AND FIRE ALARM MAY BE REQUIRED, IF
 ASSEMBLY, NFPA 101 CHAPTER 12 APPLIES.
  
 12.3.5 EXTINGUISHMENT REQUIREMENTS.
 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE
 FOLLOWING
 ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 12.3.5.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY
 OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE
 ASSEMBLY
 OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7 AS FOLLOWS (SEE ALSO 12.1.6, 12.2.6, 12.3.2, AND
 12.3.6):
 (1) THROUGHOUT THE STORY CONTAINING THE ASSEMBLY
 OCCUPANCY
 (2) THROUGHOUT ALL STORIES BELOW THE STORY CONTAINING
 THE
 ASSEMBLY OCCUPANCY
 (3) IN THE CASE OF AN ASSEMBLY OCCUPANCY LOCATED BELOW
 THE LEVEL
 OF EXIT DISCHARGE, THROUGHOUT ALL STORIES INTERVENING
 BETWEEN
 THAT STORY AND THE LEVEL OF EXIT DISCHARGE, INCLUDING
 THE LEVEL
 OF EXIT DISCHARGE
  
 12.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 12.3.4.1 GENERAL.
 12.3.4.1.1 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS OF
 MORE
 THAN 300 AND ALL THEATERS WITH MORE THAN ONE
 AUDIENCE-VIEWING
 ROOM SHALL BE PROVIDED WITH AN APPROVED FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH 9.6.1 AND 12.3.4, UNLESS OTHERWISE
 PERMITTED BY
 12.3.4.1.2.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL