Plan Review Notes
Plan Review Notes For Permit 19101085
Permit Number 19101085
Review Stop B
Sequence Number 1
Notes
Date Text
2019-11-26 10:54:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101085
 ADD: 471 SPENSER AVE.
 CONT: ATLANTIC REAL ESTATE & BUILDING
 TEL: 561-602-3295
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 26/2019
 ACTION: DENIED
  
 1A) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 1B) PLEASE NOTE AT TIME OF PERMIT APPLICATION THERE WAS
 NO ROOFING CONTRACTOR SIGNED ON. THE CGC IS CURRENTLY
 NOT LICENSED AS ROOFING CONTRACTOR BUT IS ELIGIBLE FOR
 EXAM, APPLICATION IN PROGRESS.
  
 1C) NOTICE ONLY, SUB-CONTRACTORS TO PAY THEIR PORTION
 OF THE SUB-PERMIT VALUES LISTED FOR EACH SUB-PERMIT.
  
 1D) PLEASE NOTE THE ARCHITECTS SEAL IS ENLARGED LARGER
 THAN THE FLORIDA ADMINISTRATIVE CODE ALLOWS. ARCHITECT.
 61G1-16.002(1) BOTH SEALS SHALL BE APPROXIMATELY 2" IN
 DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES
 SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA?
 AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT?.
  
 1E) THE ARCHITECTS SIGNATURE IS A COPY NOT AN ORIGINAL
 SIGNATURE. FL ADMIN CODE 61G16.003(1) ARCHITECTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003.
  
  
 2A) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE
 LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN
 STATES IT IS THE FIRE PROTECTION PLAN, WHICH IS IT? IF
 THE PLAN IS THE FIRE PROTECTION PLAN SHOWING, NEW FIRE
 SPRINKLER SYSTEM, OR AN EXISTING FIRE SPRINKLER SYSTEM,
 OR A RECONFIGURED FIRE SPRINKLER SYSTEM? WITH THE
 EXISTING WALL SYSTEM IN PLACE, THE FIRE SPRINKLER
 LAYOUT WOULDN?T HAVE HAD PROPER COVERAGE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE
 LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN
 STATES IT IS THE FIRE PROTECTION PLAN. IF THE PLAN IS
 TO BE THE LIFE SAFETY PLAN THEN THERE IS REQUIRED
 INFORMATION MISSING ON THE PLAN.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED 2017
 FBC-B TABLE 504.3, TABLE 504.4 AND TABLE 506.2.
  
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD / GROSS
 MEANS OF EGRESS
 EXIT
 EXIT DISCHARGE
 MAXIMUM COMMON PATH OF TRAVEL
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS
 NEW BUILDING ENVELOPE REQUIREMENTS
  
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 PARKING/ ACCESS AISLE
  
 3) DEMO PLAN:
 3A) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS
 THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND
 ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. WITHIN
 THE BREEZEWAYS IT WOULD APPEAR THE WALLS WOULD BE CBS
 BEARING WALLS. THE INTERIOR DEMO FLOOR PLAN IT WOULD
 APPEAR THAT 57 % OF THE BEARING WALLS ARE PROPOSED TO
 BE REMOVED. SHEET 004 INDICATES PRE-STRESSED CONCRETE,
 ROOF TRUSSES W/ CONCRETE DECK. PLEASE CLARIFY NOTE.
 WHAT TYPE OF ROOF FRAMING IS THERE, BAR JOIST, WOOD OR
 METAL TRUSSES, WHICH WAY DO THEY RUN AND WHAT TYPE OF
 ROOF DECK, IS THERE A B-DECK WITH ROOF TOP INSULATION,
 B-DECK WITH LIGHT WEIGHT CONCRETE, A PRE-STRESSED
 CONCRETE DECK, OR POURED CONCRETE DECKING SYSTEM? SHEET
 A-3 DOES SHOW 4 AREAS WHERE A 12X8 INCH PIER IS TO BE
 INSTALLED? IS THE PIER GOING TO HAVE A COLUMN PLACED ON
 TOP OF THE PIER? THERE IS NO INFORMATION AS TO THE NEW
 PIER WILL REQUIRE A FOUNDATION, NOR WHAT THE PIER IS TO
 BE CONSTRUCTED FROM?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, BEFORE
 THE REMOVAL OF THE BREEZEWAY WALLS, WALLS MAYBE BEARING
 WALLS, ADDITIONAL STEEL MAYBE REQUIRED BEFORE THE WALL
 COULD BE REMOVED.
  
 3B)(1) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS
 THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND
 ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. SHEET
 A-3 THE PROPOSED FLOOR PLAN SHOWS A NEW WINDOW/ DOOR
 OPINING (10?X8?) THIS OPENING IS NOT SHOWN ON THE DEMO
 PLAN. AGAIN DEPENDING ON WHICH WAY THE ROOF FRAMING
 MEMBERS ARE RUNNING ADDITIONAL RE-ENFORCING MAYBE
 REQUIRED OVER THE OPENING AT THE BEAM LEVEL.107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3B)(2) THIS SAME PROPOSED NEW WINDOW/ DOOR OPENING THE
 STRUCTURAL PLANS DO NOT INDICATE THE NEED FOR VERTICAL
 RE-ENFORCEMENT ON BOTH SIDES OF THE DOORWAY. THIS WOULD
 BE PART OF THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM). 2017 FBC-B SECTION 2103.4 METAL REINFORCEMENT.
 MASONRY CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS
 OF SECTIONS 2104.1.1 AND 2104.1.2 AND WITH TMS 602/ACI
 530.1/ASCE 6.
  
 3C) THE DEMO PLAN ALSO INDICATES TO ENCLOSE (4)
 SKYLIGHTS WITH 2X6 JOIST AND METAL DECKING. THE
 STRUCTURAL SHEET S-1 DOES NOT HAVE ANY INFORMATION ON
 THE ROOF FRAMING MEMBERS, SECTION, THICKNESS, JOIST
 SPACING, ALLOWABLE ROOF LIVE LOADS AND DEAD LOADS,
 ANCHORING TO THE EXISTING ROOF FRAMING AND THE TYPE OF
 ROOF DECKING GAUGE AND ANCHORING OF THE DECK TO ROOF
 FRAMING MEMBERS. THE PLAN DOES NOT PROVIDE WHAT TYPE OF
 DECKING WILL BE ABOVE THE B DECK. 2017 FBC-B 2211.5
 ROOF SYSTEM DESIGN. STEEL BAR JOIST SHALL COMPLY WITH
 2207.2 DESIGN OF THE 2017 FBC-B.
  
 4) SHEET A-3 THE PROPOSED FLOOR PLAN:
 4A) FOR BOTH THE INFILL OF THE BREEZEWAY THE PLANS CALL
 OUT THE USE OF A DOUBLE 2X10 ABOVE WINDOWS AND WINDOW/
 DOOR WAY. SIMPSON STRONG TIE HANGER HUC2-210 DOUBLE 2
 INCH BY 10 INCH CONCEALED FACE MOUNT HANGER. THE PLANS
 DO NOT PROVIDE A DETAIL IF THE HEADER IS TO GO TIGHT TO
 THE CONCRETE BEAM, ASSUMED YES. IF SO WHEN THE
 CONCEALED FACE HANGER IS ANCHORED TO THE CMU UNITS HOW
 ARE THE HEADERS GOING TO BE PUT INTO THE CONCEALED FACE
 HANGER, THERE IS NO ROOM TO INSTALL THE 2X10S?
 107.2.1.2 ADDITIONAL INFORMATION AS TO HOW THE PROCESS
 WILL OCCUR.
  
 4B) THE SAME OPENING DEPICTED WITH THE USE OF A DOUBLE
 2X10, CONCEALED HANGERS FOR THE NEW FRONT DOOR ENTRY.
 THE PLANS STATE THIS WILL BE A 10 FOOT WIDE OPENING
 WHEREAS THE OTHER 4 OPENINGS ARE A 7 FOOT 4 INCH
 OPENING. THE PLANS ARE SILENT AS TO HOW THE HEADER IS
 TO BE ANCHORED MIDPOINT FOR HORIZONTAL DEFLECTION, THIS
 SYSTEM IS TO BE PART OF THE MAIN WIND FORCE RESISTING
 SYSTEM?
  
 2017 FBC-B 1604.8.2 STRUCTURAL WALLS. WALLS THAT
 PROVIDE VERTICAL LOAD-BEARING RESISTANCE OR LATERAL
 SHEAR RESISTANCE FOR A PORTION OF THE STRUCTURE SHALL
 BE ANCHORED TO THE ROOF AND TO ALL FLOORS AND MEMBERS
 THAT PROVIDE LATERAL SUPPORT FOR THE WALL OR THAT ARE
 SUPPORTED BY THE WALL. THE CONNECTIONS SHALL BE CAPABLE
 OF RESISTING THE HORIZONTAL FORCES SPECIFIED IN SECTION
 1.4.5 OF ASCE 7 FOR WALLS OF STRUCTURES ASSIGNED TO
 SEISMIC DESIGN CATEGORY A AND TO SECTION 12.11 OF ASCE
 7 FOR WALLS OF STRUCTURES ASSIGNED TO ALL OTHER SEISMIC
 DESIGN CATEGORIES. REQUIRED ANCHORS IN MASONRY WALLS OF
 HOLLOW UNITS OR CAVITY WALLS SHALL BE EMBEDDED IN A
 REINFORCED GROUTED STRUCTURAL ELEMENT OF THE WALL. SEE
 SECTIONS 1609 FOR WIND DESIGN REQUIREMENTS AND 1613 FOR
 EARTHQUAKE DESIGN REQUIREMENTS.
  
 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND
 THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 THE TOTAL LATERAL FORCE SHALL BE DISTRIBUTED TO THE
 VARIOUS VERTICAL ELEMENTS OF THE LATERAL
 FORCE-RESISTING SYSTEM IN PROPORTION TO THEIR
 RIGIDITIES, CONSIDERING THE RIGIDITY OF THE HORIZONTAL
 BRACING SYSTEM OR DIAPHRAGM. RIGID ELEMENTS ASSUMED NOT
 TO BE A PART OF THE LATERAL FORCE-RESISTING SYSTEM ARE
 PERMITTED TO BE INCORPORATED INTO BUILDINGS PROVIDED
 THEIR EFFECT ON THE ACTION OF THE SYSTEM IS CONSIDERED
 AND PROVIDED FOR IN THE DESIGN. A DIAPHRAGM IS RIGID
 FOR THE PURPOSE OF DISTRIBUTION OF STORY SHEAR AND
 TORSIONAL MOMENT WHEN THE LATERAL DEFORMATION OF THE
 DIAPHRAGM IS LESS THAN OR EQUAL TO TWO TIMES THE
 AVERAGE STORY DRIFT. WHERE REQUIRED BY ASCE 7,
 PROVISIONS SHALL BE MADE FOR THE INCREASED FORCES
 INDUCED ON RESISTING ELEMENTS OF THE STRUCTURAL SYSTEM
 RESULTING FROM TORSION DUE TO ECCENTRICITY BETWEEN THE
 CENTER OF APPLICATION OF THE LATERAL FORCES AND THE
 CENTER OF RIGIDITY OF THE LATERAL FORCE RESISTING
 SYSTEM.
  
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS, SECTION 1610 FOR LATERAL SOIL LOADS AND SECTION
 1613 FOR EARTHQUAKE LOADS.
 4C) THE FLOOR PLAN DOES NOT PROVIDE A DETAIL FOR THE
 PROPOSED KITCHEN, NOT A BREAK AREA. PLEASE NOTE WITH
 THE DESIGNATION OF A KITCHEN THE MEANS OF EGRESS
 THROUGH A KITCHEN IS PROHIBITED. PLEASE REVIEW SECTION
 1016.2.(5) EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 4D) THE FLOOR PLAN DOES NOT INDICATE IF ANY AND OR ALL
 OF THE MEANS OF EGRESS ARE AN ACCESSIBLE ENTRY. PLEASE
 SHOW COMPLIANCE WITH;
 2017 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES.
 (DOORWAYS)
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY
 ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS
 CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE
 EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR
 CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING
 SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
  
 4E) 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017 ACCESS.
 CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4F) SIGNAGE 2017 FBC-ACCESSIBILITY CODE SECTION 216.6
 ENTRANCES. WHERE NOT ALL ENTRANCES COMPLY WITH 404,
 ENTRANCES COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
 INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING
 WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT
 COMPLY WITH 404.
  
 4G) PLEASE PROVIDE A DETAIL OF THE KITCHEN CABINETS,
 COUNTER HEIGHT, IF THERE IS A SINK AND ASSOCIATED
 APPLIANCES. ACCESSIBILITY REQUIREMENTS CANNOT BE
 DETERMINED AT THIS TIME. NO INFORMATION WAS PROVIDED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4H) THE FLOOR PLAN IS MISSING THE REQUIRED DRINKING
 FOUNTAIN IN COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY
 CODE SECTION 211.2 MINIMUM NUMBER. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 4I) THE FLOOR PLAN SHOWS 6 NEW UNISEX RESTROOMS BUT
 THERE IS NO DETAIL OF THE UNISEX AND OR ACCESSIBLE
 RESTROOMS. COMPLIANCE WITH THESE ACCESSIBILITY
 REQUIREMENTS CANNOT BE ACHIEVED.
 WATER CLOSET.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 4J) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 4K) 606 LAVATORIES AND SINKS.
 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 EXCEPTIONS:
 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE
 PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK
 TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET
 BARS.
  
 4L) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4M) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS
 FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED
 METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS
 MINIMUM.
  
 4N) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 4O) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4P) GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 4Q) 2017 ACCESSIBILITY CODE 604.5.2 REAR WALL. THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE.
  
  
  
 4R) TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE
 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE
 THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
 4S) THE FLOOR PLAN SHOWS 4 NEW 4X3 FOOT SKYLIGHTS.
 PLEASE NOTE THE PROPOSED NEW SKYLIGHTS ARE NOT
 REFLECTED ON THE ROOF TOP PLAN. PLEASE PROVIDE
 INFORMATION ON THE CUTTING IN OF THE SKYLIGHT, IF THERE
 IS ADDITIONAL FRAMING REQUIRED FOR THE SKYLIGHT.
 WITHOUT HAVING ANY INFORMATION ON THE SKYLIGHT, PLEASE
 PROVIDE THE PRODUCT APPROVAL SHOWING THE MOUNTING OF
 THE SKYLIGHT, LARGE MISSILE IMPACT TESTING AND
 ASSOCIATED PRESSURES FOR THE SKYLIGHT. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4T) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 4U) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 4V) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4W) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4X) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4Y) PLEASE NOTE THE WIND DESIGN CRITERIA IS NOT GIVEN
 FOR THE ENCLOSED BUILDING. NOR IS THE ASSOCIATED
 PRESSURES FOR ZONES 1,2,3,4 & 5. PLEASE PROVIDE
 COMPLIANCE WITH 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE
 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY
 OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT
 THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO
 DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS.
 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS
 REVIEW CYCLE.
  
 4BB) THE FLOOR PLAN ALSO INDICATES THERE ARE (2) 4?X12?
 STRUCTURAL AWNINGS. NO DESIGN CRITERIA OR PLANS
 PROVIDED FOR THESE AREAS. 107.2.1.2. CODE COMPLIANCE
 CANNOT BE REVIEWED FOR THIS REVIEW CYCLE.
 5) SHEET S-1:
 5A) THE PLAN SHOWS FOOTINGS AND SIMPSON STRONG-TIE
 ABU66Z POST BASE BUT THERE IS NO MENTION OF THE ANCHOR
 TO BE USED TO ANCHOR THE POST BASE TO THE FOUNDATION.
 PART OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM)
 PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE POST BASE.
  
 5B) THE ELEVATION SHOW THE POST TO BE A 6X6 LVL WOOD
 POST. THE PLANS DO NOT INDICATE WHERE POST BASE IS IN
 RELATION TO GRADE, AND IF THE END OF THE WOOD LVL IS IN
 COMPLIANCE WITH THE 2017 FBC-B SECTIONS:
 2304.12.2 OTHER LOCATIONS. WOOD USED IN THE LOCATIONS
 SPECIFIED IN SECTIONS 2304.12.2.1 THROUGH 2304.12.2.5
 SHALL BE NATURALLY DURABLE WOOD OR PRESERVATIVE-TREATED
 WOOD IN ACCORDANCE WITH AWPA U1. PRESERVATIVE-TREATED
 WOOD USED IN INTERIOR LOCATIONS SHALL BE PROTECTED WITH
 TWO COATS OF URETHANE, SHELLAC, LATEX EPOXY OR VARNISH
 UNLESS WATER-BORNE PRESERVATIVES ARE USED. PRIOR TO
 APPLICATION OF THE PROTECTIVE FINISH, THE WOOD SHALL BE
 DRIED IN ACCORDANCE WITH THE MANUFACTURER?S
 RECOMMENDATIONS.
 2304.12.2.2 POSTS OR COLUMNS. POSTS OR COLUMNS
 SUPPORTING PERMANENT STRUCTURES AND SUPPORTED BY A
 CONCRETE OR MASONRY SLAB OR FOOTING THAT IS IN DIRECT
 CONTACT WITH THE EARTH SHALL BE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
 EXCEPTION: POSTS OR COLUMNS THAT ARE NOT EXPOSED TO THE
 WEATHER, ARE SUPPORTED BY CONCRETE PIERS OR METAL
 PEDESTALS PROJECTED AT LEAST 1 INCH (25 MM) ABOVE THE
 SLAB OR DECK AND 8 INCHES (203 MM) ABOVE EXPOSED EARTH
 AND ARE SEPARATED BY AN IMPERVIOUS MOISTURE BARRIER.
  
 5C) THE PORTICO ELEVATION IT WOULD APPEAR TO HAVE A
 RAISED WOOD DECK WHEREAS SHEET A-3 INDICATES A PORTICO
 WITH PAVER DECK. 107.2.1.2 ADDITIONAL INFORMATION
 REQUIRED. DISCREPANCY IN PLANS.
  
 6) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 7) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  