2019-11-26 10:54:41 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19101085 |
| ADD: 471 SPENSER AVE. |
| CONT: ATLANTIC REAL ESTATE & BUILDING |
| TEL: 561-602-3295 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. NOV. 26/2019 |
| ACTION: DENIED |
| |
| 1A) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED |
| ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| FOUND ON THEIR WEBSITE: |
| |
| HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| RENOVATION.HTML |
| |
| THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| [email protected]. THE INFORMATION SHOULD BE IN PDF |
| FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| |
| 1B) PLEASE NOTE AT TIME OF PERMIT APPLICATION THERE WAS |
| NO ROOFING CONTRACTOR SIGNED ON. THE CGC IS CURRENTLY |
| NOT LICENSED AS ROOFING CONTRACTOR BUT IS ELIGIBLE FOR |
| EXAM, APPLICATION IN PROGRESS. |
| |
| 1C) NOTICE ONLY, SUB-CONTRACTORS TO PAY THEIR PORTION |
| OF THE SUB-PERMIT VALUES LISTED FOR EACH SUB-PERMIT. |
| |
| 1D) PLEASE NOTE THE ARCHITECTS SEAL IS ENLARGED LARGER |
| THAN THE FLORIDA ADMINISTRATIVE CODE ALLOWS. ARCHITECT. |
| 61G1-16.002(1) BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA? |
| AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT?. |
| |
| 1E) THE ARCHITECTS SIGNATURE IS A COPY NOT AN ORIGINAL |
| SIGNATURE. FL ADMIN CODE 61G16.003(1) ARCHITECTS. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE |
| ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST |
| AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC |
| 61G1-16.003. |
| |
| |
| 2A) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE |
| LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN |
| STATES IT IS THE FIRE PROTECTION PLAN, WHICH IS IT? IF |
| THE PLAN IS THE FIRE PROTECTION PLAN SHOWING, NEW FIRE |
| SPRINKLER SYSTEM, OR AN EXISTING FIRE SPRINKLER SYSTEM, |
| OR A RECONFIGURED FIRE SPRINKLER SYSTEM? WITH THE |
| EXISTING WALL SYSTEM IN PLACE, THE FIRE SPRINKLER |
| LAYOUT WOULDN?T HAVE HAD PROPER COVERAGE. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2B) SHEET 002 IS INDICATED IN THE TITLEBLOCK AS THE |
| LIFE SAFETY PLAN WHEREAS IN THE GRAPHICS THE PLAN |
| STATES IT IS THE FIRE PROTECTION PLAN. IF THE PLAN IS |
| TO BE THE LIFE SAFETY PLAN THEN THERE IS REQUIRED |
| INFORMATION MISSING ON THE PLAN. |
| |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1OF THE ADMINISTRATIVE CODE 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED 2017 |
| FBC-B TABLE 504.3, TABLE 504.4 AND TABLE 506.2. |
| |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD / GROSS |
| MEANS OF EGRESS |
| EXIT |
| EXIT DISCHARGE |
| MAXIMUM COMMON PATH OF TRAVEL |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| |
| STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS |
| NEW BUILDING ENVELOPE REQUIREMENTS |
| |
| ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| PARKING/ ACCESS AISLE |
| |
| 3) DEMO PLAN: |
| 3A) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS |
| THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND |
| ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. WITHIN |
| THE BREEZEWAYS IT WOULD APPEAR THE WALLS WOULD BE CBS |
| BEARING WALLS. THE INTERIOR DEMO FLOOR PLAN IT WOULD |
| APPEAR THAT 57 % OF THE BEARING WALLS ARE PROPOSED TO |
| BE REMOVED. SHEET 004 INDICATES PRE-STRESSED CONCRETE, |
| ROOF TRUSSES W/ CONCRETE DECK. PLEASE CLARIFY NOTE. |
| WHAT TYPE OF ROOF FRAMING IS THERE, BAR JOIST, WOOD OR |
| METAL TRUSSES, WHICH WAY DO THEY RUN AND WHAT TYPE OF |
| ROOF DECK, IS THERE A B-DECK WITH ROOF TOP INSULATION, |
| B-DECK WITH LIGHT WEIGHT CONCRETE, A PRE-STRESSED |
| CONCRETE DECK, OR POURED CONCRETE DECKING SYSTEM? SHEET |
| A-3 DOES SHOW 4 AREAS WHERE A 12X8 INCH PIER IS TO BE |
| INSTALLED? IS THE PIER GOING TO HAVE A COLUMN PLACED ON |
| TOP OF THE PIER? THERE IS NO INFORMATION AS TO THE NEW |
| PIER WILL REQUIRE A FOUNDATION, NOR WHAT THE PIER IS TO |
| BE CONSTRUCTED FROM? |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, BEFORE |
| THE REMOVAL OF THE BREEZEWAY WALLS, WALLS MAYBE BEARING |
| WALLS, ADDITIONAL STEEL MAYBE REQUIRED BEFORE THE WALL |
| COULD BE REMOVED. |
| |
| 3B)(1) PALM BEACH COUNTY GEO MAPPING/ GOOGLE MAPS SHOWS |
| THERE IS 3 INDIVIDUAL BUILDINGS WITH 2 BREEZE WAYS AND |
| ONE COVERED ROOF SYSTEM OVER THE WHOLE BUILDING. SHEET |
| A-3 THE PROPOSED FLOOR PLAN SHOWS A NEW WINDOW/ DOOR |
| OPINING (10?X8?) THIS OPENING IS NOT SHOWN ON THE DEMO |
| PLAN. AGAIN DEPENDING ON WHICH WAY THE ROOF FRAMING |
| MEMBERS ARE RUNNING ADDITIONAL RE-ENFORCING MAYBE |
| REQUIRED OVER THE OPENING AT THE BEAM LEVEL.107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3B)(2) THIS SAME PROPOSED NEW WINDOW/ DOOR OPENING THE |
| STRUCTURAL PLANS DO NOT INDICATE THE NEED FOR VERTICAL |
| RE-ENFORCEMENT ON BOTH SIDES OF THE DOORWAY. THIS WOULD |
| BE PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| SYSTEM). 2017 FBC-B SECTION 2103.4 METAL REINFORCEMENT. |
| MASONRY CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS |
| OF SECTIONS 2104.1.1 AND 2104.1.2 AND WITH TMS 602/ACI |
| 530.1/ASCE 6. |
| |
| 3C) THE DEMO PLAN ALSO INDICATES TO ENCLOSE (4) |
| SKYLIGHTS WITH 2X6 JOIST AND METAL DECKING. THE |
| STRUCTURAL SHEET S-1 DOES NOT HAVE ANY INFORMATION ON |
| THE ROOF FRAMING MEMBERS, SECTION, THICKNESS, JOIST |
| SPACING, ALLOWABLE ROOF LIVE LOADS AND DEAD LOADS, |
| ANCHORING TO THE EXISTING ROOF FRAMING AND THE TYPE OF |
| ROOF DECKING GAUGE AND ANCHORING OF THE DECK TO ROOF |
| FRAMING MEMBERS. THE PLAN DOES NOT PROVIDE WHAT TYPE OF |
| DECKING WILL BE ABOVE THE B DECK. 2017 FBC-B 2211.5 |
| ROOF SYSTEM DESIGN. STEEL BAR JOIST SHALL COMPLY WITH |
| 2207.2 DESIGN OF THE 2017 FBC-B. |
| |
| 4) SHEET A-3 THE PROPOSED FLOOR PLAN: |
| 4A) FOR BOTH THE INFILL OF THE BREEZEWAY THE PLANS CALL |
| OUT THE USE OF A DOUBLE 2X10 ABOVE WINDOWS AND WINDOW/ |
| DOOR WAY. SIMPSON STRONG TIE HANGER HUC2-210 DOUBLE 2 |
| INCH BY 10 INCH CONCEALED FACE MOUNT HANGER. THE PLANS |
| DO NOT PROVIDE A DETAIL IF THE HEADER IS TO GO TIGHT TO |
| THE CONCRETE BEAM, ASSUMED YES. IF SO WHEN THE |
| CONCEALED FACE HANGER IS ANCHORED TO THE CMU UNITS HOW |
| ARE THE HEADERS GOING TO BE PUT INTO THE CONCEALED FACE |
| HANGER, THERE IS NO ROOM TO INSTALL THE 2X10S? |
| 107.2.1.2 ADDITIONAL INFORMATION AS TO HOW THE PROCESS |
| WILL OCCUR. |
| |
| 4B) THE SAME OPENING DEPICTED WITH THE USE OF A DOUBLE |
| 2X10, CONCEALED HANGERS FOR THE NEW FRONT DOOR ENTRY. |
| THE PLANS STATE THIS WILL BE A 10 FOOT WIDE OPENING |
| WHEREAS THE OTHER 4 OPENINGS ARE A 7 FOOT 4 INCH |
| OPENING. THE PLANS ARE SILENT AS TO HOW THE HEADER IS |
| TO BE ANCHORED MIDPOINT FOR HORIZONTAL DEFLECTION, THIS |
| SYSTEM IS TO BE PART OF THE MAIN WIND FORCE RESISTING |
| SYSTEM? |
| |
| 2017 FBC-B 1604.8.2 STRUCTURAL WALLS. WALLS THAT |
| PROVIDE VERTICAL LOAD-BEARING RESISTANCE OR LATERAL |
| SHEAR RESISTANCE FOR A PORTION OF THE STRUCTURE SHALL |
| BE ANCHORED TO THE ROOF AND TO ALL FLOORS AND MEMBERS |
| THAT PROVIDE LATERAL SUPPORT FOR THE WALL OR THAT ARE |
| SUPPORTED BY THE WALL. THE CONNECTIONS SHALL BE CAPABLE |
| OF RESISTING THE HORIZONTAL FORCES SPECIFIED IN SECTION |
| 1.4.5 OF ASCE 7 FOR WALLS OF STRUCTURES ASSIGNED TO |
| SEISMIC DESIGN CATEGORY A AND TO SECTION 12.11 OF ASCE |
| 7 FOR WALLS OF STRUCTURES ASSIGNED TO ALL OTHER SEISMIC |
| DESIGN CATEGORIES. REQUIRED ANCHORS IN MASONRY WALLS OF |
| HOLLOW UNITS OR CAVITY WALLS SHALL BE EMBEDDED IN A |
| REINFORCED GROUTED STRUCTURAL ELEMENT OF THE WALL. SEE |
| SECTIONS 1609 FOR WIND DESIGN REQUIREMENTS AND 1613 FOR |
| EARTHQUAKE DESIGN REQUIREMENTS. |
| |
| 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND |
| THEIR CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| THE TOTAL LATERAL FORCE SHALL BE DISTRIBUTED TO THE |
| VARIOUS VERTICAL ELEMENTS OF THE LATERAL |
| FORCE-RESISTING SYSTEM IN PROPORTION TO THEIR |
| RIGIDITIES, CONSIDERING THE RIGIDITY OF THE HORIZONTAL |
| BRACING SYSTEM OR DIAPHRAGM. RIGID ELEMENTS ASSUMED NOT |
| TO BE A PART OF THE LATERAL FORCE-RESISTING SYSTEM ARE |
| PERMITTED TO BE INCORPORATED INTO BUILDINGS PROVIDED |
| THEIR EFFECT ON THE ACTION OF THE SYSTEM IS CONSIDERED |
| AND PROVIDED FOR IN THE DESIGN. A DIAPHRAGM IS RIGID |
| FOR THE PURPOSE OF DISTRIBUTION OF STORY SHEAR AND |
| TORSIONAL MOMENT WHEN THE LATERAL DEFORMATION OF THE |
| DIAPHRAGM IS LESS THAN OR EQUAL TO TWO TIMES THE |
| AVERAGE STORY DRIFT. WHERE REQUIRED BY ASCE 7, |
| PROVISIONS SHALL BE MADE FOR THE INCREASED FORCES |
| INDUCED ON RESISTING ELEMENTS OF THE STRUCTURAL SYSTEM |
| RESULTING FROM TORSION DUE TO ECCENTRICITY BETWEEN THE |
| CENTER OF APPLICATION OF THE LATERAL FORCES AND THE |
| CENTER OF RIGIDITY OF THE LATERAL FORCE RESISTING |
| SYSTEM. |
| |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS, SECTION 1610 FOR LATERAL SOIL LOADS AND SECTION |
| 1613 FOR EARTHQUAKE LOADS. |
| 4C) THE FLOOR PLAN DOES NOT PROVIDE A DETAIL FOR THE |
| PROPOSED KITCHEN, NOT A BREAK AREA. PLEASE NOTE WITH |
| THE DESIGNATION OF A KITCHEN THE MEANS OF EGRESS |
| THROUGH A KITCHEN IS PROHIBITED. PLEASE REVIEW SECTION |
| 1016.2.(5) EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| PURPOSES. |
| |
| 4D) THE FLOOR PLAN DOES NOT INDICATE IF ANY AND OR ALL |
| OF THE MEANS OF EGRESS ARE AN ACCESSIBLE ENTRY. PLEASE |
| SHOW COMPLIANCE WITH; |
| 2017 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. |
| (DOORWAYS) |
| IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY |
| ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS |
| CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE |
| EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR |
| CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING |
| SUCH ENTRANCES OR EXITS SHALL BE REMOVED. |
| |
| 4E) 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017 ACCESS. |
| CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES |
| REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60 |
| PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404. |
| |
| 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| BUILDING CODE (2003 EDITION). |
| |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| |
| 4F) SIGNAGE 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 |
| ENTRANCES. WHERE NOT ALL ENTRANCES COMPLY WITH 404, |
| ENTRANCES COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE |
| INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH |
| 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT |
| INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING |
| WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT |
| COMPLY WITH 404. |
| |
| 4G) PLEASE PROVIDE A DETAIL OF THE KITCHEN CABINETS, |
| COUNTER HEIGHT, IF THERE IS A SINK AND ASSOCIATED |
| APPLIANCES. ACCESSIBILITY REQUIREMENTS CANNOT BE |
| DETERMINED AT THIS TIME. NO INFORMATION WAS PROVIDED. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 4H) THE FLOOR PLAN IS MISSING THE REQUIRED DRINKING |
| FOUNTAIN IN COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY |
| CODE SECTION 211.2 MINIMUM NUMBER. NO FEWER THAN TWO |
| DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE |
| DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| |
| 4I) THE FLOOR PLAN SHOWS 6 NEW UNISEX RESTROOMS BUT |
| THERE IS NO DETAIL OF THE UNISEX AND OR ACCESSIBLE |
| RESTROOMS. COMPLIANCE WITH THESE ACCESSIBILITY |
| REQUIREMENTS CANNOT BE ACHIEVED. |
| WATER CLOSET. |
| 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| PERPENDICULAR FROM THE REAR WALL. |
| |
| 4J) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE |
| WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER |
| CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY |
| NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE |
| ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT |
| OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER |
| FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE |
| REQUIRED WATER CLOSET CLEARANCE. |
| |
| 4K) 606 LAVATORIES AND SINKS. |
| 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR SPACE. A |
| CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| WITH 306 SHALL BE PROVIDED. |
| EXCEPTIONS: |
| 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| BARS. |
| |
| 4L) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4M) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| MINIMUM. |
| |
| 4N) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| |
| 4O) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| |
| 4P) GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE |
| SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| |
| 4Q) 2017 ACCESSIBILITY CODE 604.5.2 REAR WALL. THE REAR |
| WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM |
| AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610 |
| MM) MINIMUM ON THE OTHER SIDE. |
| |
| |
| |
| 4R) TOILET PAPER DISPENSERS. 2017 FBC-ACCESS. CODE |
| 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY |
| WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A TYPE |
| THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW |
| CONTINUOUS PAPER FLOW. |
| |
| 4S) THE FLOOR PLAN SHOWS 4 NEW 4X3 FOOT SKYLIGHTS. |
| PLEASE NOTE THE PROPOSED NEW SKYLIGHTS ARE NOT |
| REFLECTED ON THE ROOF TOP PLAN. PLEASE PROVIDE |
| INFORMATION ON THE CUTTING IN OF THE SKYLIGHT, IF THERE |
| IS ADDITIONAL FRAMING REQUIRED FOR THE SKYLIGHT. |
| WITHOUT HAVING ANY INFORMATION ON THE SKYLIGHT, PLEASE |
| PROVIDE THE PRODUCT APPROVAL SHOWING THE MOUNTING OF |
| THE SKYLIGHT, LARGE MISSILE IMPACT TESTING AND |
| ASSOCIATED PRESSURES FOR THE SKYLIGHT. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 4T) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (F) SKYLIGHTS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 4U) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 4V) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 4W) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 4X) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 4Y) PLEASE NOTE THE WIND DESIGN CRITERIA IS NOT GIVEN |
| FOR THE ENCLOSED BUILDING. NOR IS THE ASSOCIATED |
| PRESSURES FOR ZONES 1,2,3,4 & 5. PLEASE PROVIDE |
| COMPLIANCE WITH 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 4Z) AT THE FRONT ENTRY THE PLAN SHOWS NEW DECORATIVE |
| 2X2 STUCCO COLUMNS NO DETAILS PROVIDED. 107.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 4AA) THE FLOOR PLAN SHOWS A NEW PROPOSED COVERED ENTRY |
| OF 24?X10?. THE S-1 HAS A FEW DETAILS OF THIS AREA, BUT |
| THERE ARE (2) COVERED AREA APPROXIMATELY 14?X7? WITH NO |
| DESIGN CRITERIA OR PLANS PROVIDED FOR THESE AREAS. |
| 107.2.1.2. CODE COMPLIANCE CANNOT BE REVIEWED FOR THIS |
| REVIEW CYCLE. |
| |
| 4BB) THE FLOOR PLAN ALSO INDICATES THERE ARE (2) 4?X12? |
| STRUCTURAL AWNINGS. NO DESIGN CRITERIA OR PLANS |
| PROVIDED FOR THESE AREAS. 107.2.1.2. CODE COMPLIANCE |
| CANNOT BE REVIEWED FOR THIS REVIEW CYCLE. |
| 5) SHEET S-1: |
| 5A) THE PLAN SHOWS FOOTINGS AND SIMPSON STRONG-TIE |
| ABU66Z POST BASE BUT THERE IS NO MENTION OF THE ANCHOR |
| TO BE USED TO ANCHOR THE POST BASE TO THE FOUNDATION. |
| PART OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) |
| PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE POST BASE. |
| |
| 5B) THE ELEVATION SHOW THE POST TO BE A 6X6 LVL WOOD |
| POST. THE PLANS DO NOT INDICATE WHERE POST BASE IS IN |
| RELATION TO GRADE, AND IF THE END OF THE WOOD LVL IS IN |
| COMPLIANCE WITH THE 2017 FBC-B SECTIONS: |
| 2304.12.2 OTHER LOCATIONS. WOOD USED IN THE LOCATIONS |
| SPECIFIED IN SECTIONS 2304.12.2.1 THROUGH 2304.12.2.5 |
| SHALL BE NATURALLY DURABLE WOOD OR PRESERVATIVE-TREATED |
| WOOD IN ACCORDANCE WITH AWPA U1. PRESERVATIVE-TREATED |
| WOOD USED IN INTERIOR LOCATIONS SHALL BE PROTECTED WITH |
| TWO COATS OF URETHANE, SHELLAC, LATEX EPOXY OR VARNISH |
| UNLESS WATER-BORNE PRESERVATIVES ARE USED. PRIOR TO |
| APPLICATION OF THE PROTECTIVE FINISH, THE WOOD SHALL BE |
| DRIED IN ACCORDANCE WITH THE MANUFACTURER?S |
| RECOMMENDATIONS. |
| 2304.12.2.2 POSTS OR COLUMNS. POSTS OR COLUMNS |
| SUPPORTING PERMANENT STRUCTURES AND SUPPORTED BY A |
| CONCRETE OR MASONRY SLAB OR FOOTING THAT IS IN DIRECT |
| CONTACT WITH THE EARTH SHALL BE OF NATURALLY DURABLE OR |
| PRESERVATIVE-TREATED WOOD. |
| EXCEPTION: POSTS OR COLUMNS THAT ARE NOT EXPOSED TO THE |
| WEATHER, ARE SUPPORTED BY CONCRETE PIERS OR METAL |
| PEDESTALS PROJECTED AT LEAST 1 INCH (25 MM) ABOVE THE |
| SLAB OR DECK AND 8 INCHES (203 MM) ABOVE EXPOSED EARTH |
| AND ARE SEPARATED BY AN IMPERVIOUS MOISTURE BARRIER. |
| |
| 5C) THE PORTICO ELEVATION IT WOULD APPEAR TO HAVE A |
| RAISED WOOD DECK WHEREAS SHEET A-3 INDICATES A PORTICO |
| WITH PAVER DECK. 107.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED. DISCREPANCY IN PLANS. |
| |
| 6) ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED |
| ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD, |
| STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF |
| ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF |
| HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT |
| NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL |
| INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE |
| FOUND ON THEIR WEBSITE: |
| HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| RENOVATION.HTML |
| THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| [email protected]. THE INFORMATION SHOULD BE IN PDF |
| FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| |
| 7) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN |
| SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND |
| REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE |
| THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW |
| PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |