Plan Review Notes
Plan Review Notes For Permit 19101064
Permit Number 19101064
Review Stop E
Sequence Number 1
Notes
Date Text
2019-12-04 10:44:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. LOAD CALCULATION INDICATES THAT A CONNECTED LOAD OF
 388.05 AMPS, AND A MINIMUM SERVICE SIZE OF 407 AMPS IS
 REQUIRED. THE RISER DIAGRAM SPECIFIES USING 500 KCMIL
 COPPER FOR THIS SERVICE. THIS WIRE IS RATED FOR 380
 AMPS AND IS THEREFORE UNDERSIZED FOR THE APPLICATION.
 PROVIDE CORRECTION. NEC310.15(B)(16)
 4. LOAD CALCULATION INDICATES THAT A CONNECTED LOAD OF
 388.05 AMPS, AND A MINIMUM SERVICE SIZE OF 407 AMPS IS
 REQUIRED. IF A MINIMUM SIZE OF 407 AMPS IS REQUIRED FOR
 SERVICE, WHY IS A 400 AMP SERVICE BEING INSTALLED?
 PROVIDE CLARIFICATION AND CORRECTIONS AS NEEDED. NEC
 110.3, 215.2, 230.79, 408.30, 701.4,
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746