2020-01-17 07:01:08 | PLAN REVIEW - NFIP | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | | | RESULTS: DENIED | | | | PLEASE REFERENCE 2ND ELEVATION CERTIFICATE SUBMITTED | | FOR REVIEW ON 12/30/2019 | | | | 1. SECTION A9 (B) - STATE NUMBER OF FLOOD VENTS. | | | | 2. SECTION A9 (C) - PROVIDE NET AREA OF FLOOD OPENINGS | | IN A9 (B) ABOVE. | | | | 3. SECTION A9 (D) - ENGINEERED FLOOD OPENINGS - NO | | SEE NOTE ON PLAN PAGE A-1 - SMART VENT MODEL 1540-520 | | TO BE INSTALLED. | | IF SMART VENT'S ARE INSTALLED, PROVIDE EVALUATION | | REPORT ISSUED BY THE INTERNATIONAL CODE COUNCIL | | EVALUATION SERVICE. (ICC ES) | | | | IF NON-ENGINEERED VENTS ARE INSTALLED, PROVIDE DETAIL | | REVIEWED AND APPROVED BY DESIGNER OF RECORD. |
|