2019-11-19 12:00:14 | PLAN REVIEW - MECHANICAL |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. IDENTIFICATION AND LOCATION OF ACU'S ON MECH. PLAN |
| ARE IN CONFLICT WITH IDENTIFICATION AND LOCATION OF |
| ACU'S ON PLAN PAGE A-1 FLOOR PLAN. PLEASE CLARIFY. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PROVIDE DETAIL AND PRODUCT APPROVAL OF MECHANICAL |
| STANDS TO BE USED TO ELEVATE MECH. EQUIPMENT ABOVE DFE. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE MECHANICAL STAND SUBMITTALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| INSERT CORRECTED PAGES INTO |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| DETACHED. |
| |
| |
| |
| |
| |
| |