2019-11-27 10:25:43 | 1ST REVIEW: 19101063 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. PROVIDE DETAIL FOR SLEEVE UNDER SLAB FOR STEEL SCH |
| 40 PIPE IT SHALL COMPLY WITH FBC FG 404.8.1 |
| |
| 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2017 FUEL GAS CODE SEC. 304. |
| |
| 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH, |
| SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL |
| GAS CODE SEC. 502 THRU 505. |
| |
| 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND |
| INSILLATION GUIDE FOR ALL GAS EQUIPMENT AND REGULATORS |
| TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, |
| AND FBC-2017 FUEL GAS SEC. 402.2 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |