Plan Review Notes For Permit 19101062 |
Permit Number |
19101062 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-11-21 10:44:01 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PLANS NEED TO SIGNED AND DATED. | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN | | PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS | | 471.003(2)(H); 471.025; FBC 107.2.1 | | | | 2) PAGE E-1 SHOWS GROUNDING DETAIL WITH NO WIRE SIZES. | | | | |
|