Plan Review Notes
Plan Review Notes For Permit 19101061
Permit Number 19101061
Review Stop B
Sequence Number 4
Notes
Date Text
2022-03-01 11:08:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19101061
 ADD: 1101 N. CONGRESS AVE. WEST PALM BEACH LIFT STATION
 # 76
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1040 (1111)
 CONTACT: RANDY ERYSTHEE/ PUBLIC UTILITIES DIR.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. MARCH 01/2022
 ACTION: DENIED
  
 1) THIS REVIEW RESIDENT INSPECTOR FORMS COMPLETED WITH
 EXCEPTION NO CONTRACTOR SIGNATURE ON FORMS NOR NO CGC
 CONTRACTOR SIGNED ONTO THE PERMIT APPLICATION.
  
 3RD REVIEW. NOTED RESPONSE THAT ONCE A CONTRACTOR IS
 HIRED/ CONTRACTED WITH BY THE CITY OF WEST PALM BEACH
 THE RESIDENT INSPECTOR FORMS WILL BE SIGNED AND
 RETURNED TO THE BUILDING DEPARTMENT AND REVIEWED AND
 APPROVED BEFORE PERMIT ISSUANCE. THE TYPE OF STRUCTURAL
 REPAIRS ON THE LIFT STATION AND WET WELL WILL LEND
 ITSELF BETTER FOR A RESIDENT INSPECTOR. MONDAY FEB.
 03/2020 I SPOKE WITH OUR ASSISTANT BUILDING OFFICIAL
 RICHARD GATHRIGHT AFTER SPEAKING WITH MR. RANDY
 ERYSTHEE ABOUT 3RD PARTY INSPECTIONS. MR. ERYSTHEE
 ASKED IF THE CITY INSPECTORS COULD DO THE STRUCTURAL
 INSPECTIONS. MR. GATHRIGHT AND I MET WITH THE CHIEF
 BUILDING INSPECTOR THIS MORNING ABOUT CITY INSPECTORS
 DOING THIS TYPE OF INSPECTIONS. BOTH THE CHIEF BUILDING
 INSPECTOR AND MR. GATHRIGHT AGREED THAT THIS TYPE OF
 RESTORATION WORK WOULD REQUIRE A 3RD PARTY INSPECTION
 SERVICE (RESIDENT INSPECTOR) THAT COULD STAY ONSITE
 THROUGHOUT THE DURATION OF THE RESTORATION WORK. THE
 FORMS SENT TO MR. RANDY ERYSTHEE WILL NEED TO BE
 COMPLETED SIGNED BY ALL PARTIES AND RETURNED TO THE
 BUILDING DEPARTMENT BEFORE THE PERMIT CAN BE ISSUED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 110.3.9. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE
 MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION
 110. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF
 RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 BOOKLET: GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING THRESHOLD/ SPECIAL INSPECTORS AND RESIDENT
 INSPECTORS
 BOOKLET AND FORMS FOR RESIDENT INSPECTOR WERE E-MAILED
 TO:
 E-MAIL: [email protected] SENT ON 11/25 & 26/2019 FOR
 LIFT STATIONS 47 & 76.
 PAGES 9-13 DEAL WITH RESIDENT INSPECTORS
 PAGES 14-16 RESIDENT INSPECTOR FORMS. FORMS WILL NEED
 TO BE SIGNED BY ALL INTERESTED PARTIES AND SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE PERMIT ISSUANCE.
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 2A) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2B) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS:
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & ROOF HATCHES.
  
 3) 4TH REVIEW. SHEET S-3 LIST THE PRODUCTS TO BE USED
 IN THE STRUCTURAL REPAIRS. PLEASE PROVIDE THE PRODUCT
 DATA SHEETS AND MSDS SHEETS FOR ALL OF THE PRODUCTS
 THAT ARE GOING TO BE USED IN THE STRUCTURAL REPAIRS
 PRIORITIES AND PROCEDURES.
 PLEASE PROVIDE HOW THESE CHEMICALS ARE GOING TO BE
 STORED. HOW THE TOOLS WILL BE CLEANED AND HOW THE
 CHEMICAL WASTE FROM THE SIKA SYSTEM WILL BE DISPOSED.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  