2019-12-05 16:19:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19101061 |
| 12/5/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M4, M5, & M6: REFER TO SECTION 809.2 FBC EX |
| AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| OCCUPIED ROOMS AND SPACES PER TABLE 403.3.1.1 FBC M . |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 2) M5: PROVIDE AN EQUIPMENT SCHEDULE FOR THE AIR SUPPLY |
| FAN- SECTION 107.2.1 WPB. |
| |
| 3) M5: PROVIDE A GRAVITY OR MOTORIZED DAMPER FOR THE |
| O/A INLET- SECTION C403.2.4.3 FBC EC. |
| |
| 4) M5: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL. |
| PRODUCT APPROVAL AND/OR MIAMI-DADE NOA FOR THE LOUVERS- |
| SECTION 401.5 FBC M AND RULE 9N-3 FAC. |
| |
| 5) M5: PROVIDE MECHANICAL EXHAUST VENTILATION FOR THE |
| TOILET ROOM PER SECTION 1203.5.2.1 FBC B AND TABLE |
| 403.3.1.1 FBC M. |
| |
| 6) PLEASE SHOW COMPLIANCE WITH SECTION 309.1 FBC M |
| PRINTED BELOW: |
| INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE |
| PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS |
| CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT |
| LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE |
| FLOOR ON THE DESIGN HEATING DAY. THE INSTALLATION OF |
| PORTABLE SPACE HEATERS SHALL NOT BE USED TO ACHIEVE |
| COMPLIANCE WITH THIS SECTION. |
| EXCEPTIONS: |
| 1.INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT |
| ASSOCIATED WITH HUMAN COMFORT. |
| 2.GROUP F, H, S AND U OCCUPANCIES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |