Plan Review Notes
Plan Review Notes For Permit 19101052
Permit Number 19101052
Review Stop B
Sequence Number 3
Notes
Date Text
2019-10-25 13:55:59CONDITIONAL APPROVAL
  
 RICHARD GATHRIGHT AND MYSELF CONDUCTED A SITE VISIT ON
 10/25/19 AND FOUND THAT MOST OF THE ITEMS HAD BEEN
 CORRECTED. IN LIEU OF THE FIRE SPRINKLER SYSTEM AND
 FIRE ALARM REQUIREMENTS, THE OWNER/OPERATOR OF THE
 TEMPORARY (ONE WEEK) HAUNTED HOUSE ATTRACTION HAS
 AGREED TO LIMIT THE NUMBER OF PERSONS THAT WILL BE IN
 THE BUILDING AT ONE TIME AS SET BY THE CITY FIRE
 DEPARTMENT, HAVE TWO SECURITY GUARDS POSTED AT THE
 FRONT AND TWO AT THE REAR EXISTS, HAVE THE EIGHT STAFF
 MEMBERS TRAINED IN SAFETY PROCEDURES WITH CITY FIRE
 DEPARTMENT STAFF PRESENT AND AGREED TO HAVE THE CITY
 FIRE DEPARTMENT PERIODICALLY MONITOR THE OPERATIONS.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 OPENING.
 1) THE FIRE DEPARTMENT'S REQUIREMENTS.
 2) THE EAST EXIT FROM THE NORTH ROOM OF THE BUILDING TO
 THE SOUTH ROOM IS REQUIRED TO HAVE AN ACCESSIBLE RAMP.
 3) PLACE A DIRECTIONAL EXIT SIGN ON THE EAST WALL NEAR
 THE CENTER OF THE FRONT ROOM TO DIRECT OCCUPANTS TO THE
 REAR EXITS. THE REAR EXIT SIGNS ARE NOT VISIBLE IN THIS
 AREA.
 4) NO SMOKING IS TO BE ALLOWED IN THE ATTRACTION. PLACE
 SIGN AT ENTRANCE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved