Plan Review Notes For Permit 19101052
Permit Number 19101052
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-10-23 09:57:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A SITE REVIEW WAS CONDUCTED AND FOUND THE FOLLOWING
 WHICH IS NOT ADDRESS NOR INDICATED ON THE SUBMITTED
 PLAN SETS:
  
 ? PER FLORIDA ACCESSIBILITY CODE AND THE AMERICANS WITH
 DISABILITIES ACT (ADA) ALL FACILITIES SHALL BE
 ACCESSIBLE TO PERSONS WITH DISABILITIES. THE FLOOR OF
 THE BUILDING IS UNEVEN WITH SEVERAL AREAS OF DIFFERENT
 TYPES OF FLOORING MATERIALS. THE NORTH ROOM OF THE
 BUILDING HAS AREAS THAT ARE FILLED IN WITH PLYWOOD,
 SOME AREAS THAT ARE BARE CONCRETE AND OTHERS HAVE
 REMNANTS OF MUD SET TILE FLOORING. THERE ARE NUMEROUS
 TRIPPING HAZARDS AND THE FLOOR WILL NEED AN EXTENSIVE
 AMOUNT OF WORK IN ORDER TO MEET FLORIDA ACCESSIBILITY
 REQUIREMENTS FOR AN ACCESSIBLE ROUTE. THE SOUTH PORTION
 OF THE BUILDING APPEARS TO BE A NEWER ADDITION AND THE
 FLOOR ELEVATION IS APPROXIMATELY 6 TO 8 INCHES HIGHER
 THAN THE OLDER NORTH PART. THIS CHANGE IN ELEVATION
 WOULD REQUIRE ACCESSIBLE RAMPS.
 ? METAL SHORING JACKS. THE ROOF AND CEILING OF THE
 FRONT ROOM ARE WOOD FRAME AND THE LARGE WOODEN BEAM
 THAT RUNS DOWN THE CENTER OF THE NORTH ROOM IS SHORED
 UP WITH METAL SHORING JACKS THIS BEAM HAS EXTENSIVE
 TERMITE DAMAGE IN SOME AREAS. SOME OF THE CEILING
 JOISTS ALSO HAVE VISIBLE TERMITE DAMAGE. THE PROPOSED
 USE OF THE SPACE WITH LOW LIGHT LEVELS, STROBE LIGHTS,
 AND DISORIENTING SOUNDS, MAY CAUSE PATRONS TO IMPACT
 THE SHORING AND POTENTIALLY CAUSE LATERAL MOVEMENT OF
 THE SHORING AND REMOVAL OF SUPPORT FOR THE WOODEN BEAM.
 ? FLAME RETARDANT TREATMENT OF CURTAINS. FLAME
 RETARDANT TREATMENT CERTIFICATE FOR THE CURTAIN FABRIC
 MUST BE PROVIDED TO SHOW THAT THE SPREAD OF FLAME WILL
 NOT POSE UNACCEPTABLE RISK TO OCCUPANTS AS THEY LEAVE
 THE BUILDING IN AN EMERGENCY. THIS IS THE SAME
 REQUIREMENT THAT APPLIES TO TENTS.
 ? PLYWOOD PANEL WALLS ATTACHMENT TO CEILING JOISTS. WE
 COULD NOT DETERMINE HOW THE 2X4S THAT SUPPORT THE
 PLYWOOD PANEL WALLS ARE ATTACHED TO THE CEILING JOISTS.
 WE WERE ABLE TO MOVE ONE OF THE WALLS BY PUSHING ON IT
 WITH VERY LITTLE FORCE. THE PROPOSED USE OF THE SPACE
 WITH LOW LIGHT LEVELS, STROBE LIGHTS, AND DISORIENTING
 SOUNDS, MAY CAUSE PATRONS TO IMPACT THE PLYWOOD WALL
 PANELS AND POTENTIALLY DETACH THEM FROM THE CEILING
 JOISTS AND CAUSE THE WALL PANELS TO FALL. ALSO, THE
 CEILING JOISTS WERE NOT INTENDED TO CARRY THE TORQUE
 (TWISTING) FORCE OF A 12 FOOT LONG LEVER WITH A PERSON
 RUNNING INTO IT.
 ? IN THE EVENT OF AN EMERGENCY THE LIGHTING MUST TURN
 ON AND PROVIDE SUFFICIENT LIGHTING LEVELS FOR SAFE
 EGRESS. THERE ARE ONLY TWO EXISTING FOUR FOOT
 FLORESCENT LIGHTING FIXTURES IN THE NORTH ROOM. THEY DO
 NOT PROVIDE ADEQUATE LIGHTING FOR THAT AREA.
 ? EACH EXIT SHALL BE MARKED BY ILLUMINATED EXIT SIGNS.
 THE EXIT LIGHTS ARE NOT FUNCTIONING AT THIS TIME. SOME
 WERE JUST HANGING BY THE ELECTRICAL CONNECTION.
 ? STORED MATERIALS. THERE ARE SOME MATERIALS STORED IN
 THE SOUTH ROOM OF THE BUILDING THAT IS BLOCKING ONE OF
 THE EXITS AND EXIT PATHS.
 ? CONSTRUCTION SITE. THE BUILDING APPEARS TO BE A
 CONSTRUCTION SITE RATHER THAN A SHELL BUILDING READY
 FOR OCCUPANCY.
 ? PLAN REVIEW. PLEASE ADDRESS ALL PLAN REVIEW COMMENTS
 ENTERED UNDER PERMIT APPLICATION # 19101052.
  
  
 1) THIS EVENT/BUILDING IS DEFINED IN THE FLORIDA FIRE
 PREVENTION CODE AS A SPECIAL AMUSEMENT BUILDING AND AN
 ASSEMBLY OCCUPANCY:
  
 3.3.29.10* SPECIAL AMUSEMENT BUILDING. A BUILDING THAT
 IS
 TEMPORARY, PERMANENT, OR MOBILE AND CONTAINS A DEVICE
 OR
 SYSTEM THAT CONVEYS PASSENGERS OR PROVIDES A WALKWAY
 ALONG,
 AROUND, OR OVER A COURSE IN ANY DIRECTION AS A FORM OF
 AMUSEMENT ARRANGED SO THAT THE EGRESS PATH IS NOT
 READILY
 APPARENT DUE TO VISUAL OR AUDIO DISTRACTIONS OR AN
 INTENTIONALLY
 CONFOUNDED EGRESS PATH, OR IS NOT READILY AVAILABLE DUE
 TO THE
 MODE OF CONVEYANCE THROUGH THE BUILDING OR STRUCTURE.
  
 3.3.183.3* ASSEMBLY OCCUPANCY. AN OCCUPANCY (1) USED
 FOR A
 GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR SIMILAR USES; OR (2) USED AS A
 SPECIAL
 AMUSEMENT BUILDING, REGARDLESS OF OCCUPANT LOAD.
  
 PER NFPA 1 CH 20 FIRE SPRINKLERS ARE REQUIRED.
  
 20.1.4.2* AUTOMATIC SPRINKLERS. EVERY SPECIAL AMUSEMENT
 BUILDING,
 OTHER THAN BUILDINGS OR STRUCTURES NOT EXCEEDING 10 FT
 (3050 MM) IN
 HEIGHT AND NOT EXCEEDING 160 FT2 (15 M2) IN AGGREGATE
 HORIZONTAL
 PROJECTION, SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM INSTALLED AND MAINTAINED IN
 ACCORDANCE
 WITH SECTION 13.3.
  
 ADDITIONAL REQUIREMENTS:
  
 20.1.4.4 SMOKE DETECTION. WHERE THE NATURE OF THE
 SPECIAL
 AMUSEMENT BUILDING IS SUCH THAT IT OPERATES IN REDUCED
 LIGHTING LEVELS,
 THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED AUTOMATIC
 SMOKE DETECTION SYSTEM IN ACCORDANCE WITH SECTION 13.7.
 [101:12.4.8.4; 101: 13.4.8.4]
 20.1.4.5 ALARM INITIATION. ACTUATION OF ANY SMOKE
 DETECTION SYSTEM
 DEVICE SHALL SOUND AN ALARM AT A CONSTANTLY ATTENDED
 LOCATION ON THE
 PREMISES. [101: 12.4.8.5, 101: 13.4.8.5]
 20.1.4.6 ILLUMINATION. ACTUATION OF THE AUTOMATIC
 SPRINKLER SYSTEM,
 OR ANY OTHER SUPPRESSION SYSTEM, OR ACTUATION OF A
 SMOKE DETECTION
 SYSTEM HAVING AN APPROVED VERIFICATION OR CROSS-ZONING
 OPERATION
 CAPABILITY SHALL PROVIDE FOR THE FOLLOWING:
 (1) INCREASE IN ILLUMINATION IN THE MEANS OF EGRESS TO
 THAT REQUIRED
 BY SECTION 14.12
 (2) TERMINATION OF ANY CONFLICTING OR CONFUSING SOUNDS
 AND VISUALS
 [101: 12.4.8.6; 101: 13.4.8.6]
 20.1.4.7 EXIT MARKING.
 20.1.4.7.1 EXIT MARKING SHALL BE IN ACCORDANCE WITH
 SECTION 14.14.
 [101: 12.4.8.7.1; 101: 13.4.8.7.1]
 20.1.4.7.2 FLOOR PROXIMITY EXIT SIGNS SHALL BE PROVIDED
 IN ACCORDANCE
 WITH 14.14.1.6. [101: 12.4.8.7.2; 101: 13.4.8.7.2]
 20.1.4.7.3* IN SPECIAL AMUSEMENT BUILDINGS WHERE MAZES,
 MIRRORS, OR
 OTHER DESIGNS ARE USED TO CONFOUND THE EGRESS PATH,
 APPROVED
 DIRECTIONAL EXIT MARKING THAT BECOMES APPARENT IN AN
 EMERGENCY SHALL
 BE PROVIDED.
  
 IN AN EFFORT TO CONSIDER ALTERNATIVES TO THE ABOVE
 REQUIREMENTS, THE SITE FINDINGS NEED TO BE ADDRESSED
 AND CORRECTED.
  
  
  
 2) ADDITIONALLY, PER NFPA 101 CH 7 MEANS OF EGRESS, THE
 FLOOR WALKING SERFACE SHALL MEET THE FOLLOWING:
  
 7.1.6 WALKING SURFACES IN THE MEANS OF EGRESS.
 7.1.6.1 GENERAL.
 7.1.6.1.1 WALKING SURFACES IN THE MEANS OF EGRESS SHALL
 COMPLY
 WITH 7.1.6.2 THROUGH 7.1.6.4.
 7.1.6.1.2 APPROVED EXISTING WALKING SURFACES SHALL BE
 PERMITTED.
 7.1.6.2 CHANGES IN ELEVATION. ABRUPT CHANGES IN
 ELEVATION OF
 WALKING SURFACES SHALL NOT EXCEED ? IN. (6.3 MM).
 CHANGES IN
 ELEVATION EXCEEDING ? IN. (6.3 MM), BUT NOT EXCEEDING ?
 IN. (13
 MM), SHALL BE BEVELED WITH A SLOPE OF 1 IN 2. CHANGES
 IN ELEVATION
 EXCEEDING ? IN. (13 MM) SHALL BE CONSIDERED A CHANGE IN
 LEVEL
 AND SHALL BE SUBJECT TO THE REQUIREMENTS OF 7.1.7.
 7.1.6.3 LEVEL.
 7.1.6.3.1 WALKING SURFACES SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
 (1) WALKING SURFACES SHALL BE NOMINALLY LEVEL.
 (2) THE SLOPE OF A WALKING SURFACE IN THE DIRECTION OF
 TRAVEL SHALL
 NOT EXCEED 1 IN 20, UNLESS THE RAMP REQUIREMENTS OF
 7.2.5 ARE
 MET.
 (3) THE SLOPE PERPENDICULAR TO THE DIRECTION OF TRAVEL
 SHALL NOT
 EXCEED 1 IN 48.
 7.1.7 CHANGES IN LEVEL IN MEANS OF EGRESS.
 7.1.7.1 CHANGES IN LEVEL IN MEANS OF EGRESS SHALL BE
 ACHIEVED BY
 AN APPROVED MEANS OF EGRESS WHERE THE ELEVATION
 DIFFERENCE
 EXCEEDS 21 IN. (535 MM).
 7.1.7.2* CHANGES IN LEVEL IN MEANS OF EGRESS NOT IN
 EXCESS OF 21
 IN. (535 MM) SHALL BE ACHIEVED EITHER BY A RAMP
 COMPLYING WITH
 THE REQUIREMENTS OF 7.2.5 OR BY A STAIR COMPLYING WITH
 THE
 REQUIREMENTS OF 7.2.2.
 7.1.7.2.1 WHERE A RAMP IS USED TO MEET THE REQUIREMENTS
 OF
 7.1.7.2, THE PRESENCE AND LOCATION OF RAMPED PORTIONS
 OF WALKWAYS
 SHALL BE READILY APPARENT.
 7.1.7.2.2 WHERE A STAIR IS USED TO MEET THE
 REQUIREMENTS OF 7.1.7.2,
 THE TREAD DEPTH OF SUCH STAIR SHALL BE NOT LESS THAN 13
 IN. (330 MM).
 7.1.7.2.3 TREAD DEPTH IN INDUSTRIAL EQUIPMENT ACCESS
 AREAS AS
 PROVIDED IN 40.2.5.3 SHALL BE PERMITTED.
 7.1.7.2.4 THE PRESENCE AND LOCATION OF EACH STEP SHALL
 BE READILY
 APPARENT.
  
 3) BASED ON THE ABOVE SITE CONDITIONS AND PROPOSED
 AMUSEMENT USE, THE FOLLOWING MEANS OF EGRESS
 REQUIRMENTS SHALL BE MET:
  
 7.1.9 IMPEDIMENTS TO EGRESS. ANY DEVICE OR ALARM
 INSTALLED TO
 RESTRICT THE IMPROPER USE OF A MEANS OF EGRESS SHALL BE
 DESIGNED
 AND INSTALLED SO THAT IT CANNOT, EVEN IN CASE OF
 FAILURE, IMPEDE OR
 PREVENT EMERGENCY USE OF SUCH MEANS OF EGRESS, UNLESS
 OTHERWISE
 PROVIDED IN 7.2.1.6 AND CHAPTERS 18, 19, 22, AND 23.
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
 7.1.10.2 FURNISHINGS AND DECORATIONS IN MEANS OF
 EGRESS.
 7.1.10.2.1 NO FURNISHINGS, DECORATIONS, OR OTHER
 OBJECTS SHALL
 OBSTRUCT EXITS OR THEIR ACCESS THERETO, EGRESS THERE
 FROM, OR
 VISIBILITY THEREOF.
 7.1.10.2.2 NO OBSTRUCTION BY RAILINGS, BARRIERS, OR
 GATES SHALL
 DIVIDE THE MEANS OF EGRESS INTO SECTIONS APPURTENANT TO
 INDIVIDUAL
 ROOMS, APARTMENTS, OR OTHER OCCUPIED SPACES. WHERE THE
 AUTHORITY
 HAVING JURISDICTION FINDS THE REQUIRED PATH OF TRAVEL
 TO BE
 OBSTRUCTED BY FURNITURE OR OTHER MOVABLE OBJECTS, THE
 AUTHORITY
 SHALL BE PERMITTED TO REQUIRE THAT SUCH OBJECTS BE
 SECURED OUT OF
 THE WAY OR SHALL BE PERMITTED TO REQUIRE THAT RAILINGS
 OR OTHER
 PERMANENT BARRIERS BE INSTALLED TO PROTECT THE PATH OF
 TRAVEL AGAINST
 ENCROACHMENT.
 7.1.10.2.3 MIRRORS SHALL NOT BE PLACED ON EXIT DOOR
 LEAVES. MIRRORS
 SHALL NOT BE PLACED IN OR ADJACENT TO ANY EXIT IN SUCH
 A MANNER AS
 TO CONFUSE THE DIRECTION OF EGRESS.
  
  
 PLEASE PROVIDE DETAILS OF EACH MEANS OF EGRESS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  