2019-10-21 17:38:20 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| THE FOLLOWING ARE THE 2017 FLORIDA BUILDING CODE |
| REQUIREMENTS FOR A HAUNTED HOUSE ATTRACTION. |
| FBC SECTION 202 DEFINITIONS. SPECIAL AMUSEMENT |
| BUILDING. A SPECIAL AMUSEMENT BUILDING IS ANY TEMPORARY |
| OR PERMANENT BUILDING OR PORTION THEREOF THAT IS |
| OCCUPIED FOR AMUSEMENT, ENTERTAINMENT OR EDUCATIONAL |
| PURPOSES AND THAT CONTAINS A DEVICE OR SYSTEM THAT |
| CONVEYS PASSENGERS OR PROVIDES A WALKWAY ALONG, AROUND |
| OR OVER A COURSE IN ANY DIRECTION SO ARRANGED THAT THE |
| MEANS OF EGRESS PATH IS NOT READILY APPARENT DUE TO |
| VISUAL OR AUDIO DISTRACTIONS OR IS INTENTIONALLY |
| CONFOUNDED OR IS NOT READILY AVAILABLE BECAUSE OF THE |
| NATURE OF THE ATTRACTION OR MODE OF CONVEYANCE THROUGH |
| THE BUILDING OR STRUCTURE. |
| |
| FBC CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON |
| USE AND OCCUPANCY SPECIAL AMUSEMENT BUILDINGS |
| 1) 411.1 GENERAL. |
| SPECIAL AMUSEMENT BUILDINGS HAVING AN OCCUPANT LOAD OF |
| 50 OR MORE SHALL COMPLY WITH THE REQUIREMENTS FOR THE |
| APPROPRIATE GROUP A OCCUPANCY AND SECTIONS 411.1 |
| THROUGH 411.8. SPECIAL AMUSEMENT BUILDINGS HAVING AN |
| OCCUPANT LOAD OF LESS THAN 50 SHALL COMPLY WITH THE |
| REQUIREMENTS FOR A GROUP B OCCUPANCY AND SECTIONS 411.1 |
| THROUGH 411.8. |
| EXCEPTION: SPECIAL AMUSEMENT BUILDINGS OR PORTIONS |
| THEREOF THAT ARE WITHOUT WALLS OR A ROOF AND |
| CONSTRUCTED TO PREVENT THE ACCUMULATION OF SMOKE NEED |
| NOT COMPLY WITH THIS SECTION. |
| FOR FLAMMABLE DECORATIVE MATERIALS, SEE THE FLORIDA |
| FIRE PREVENTION CODE. |
| 411.2 DEFINITION. THE FOLLOWING TERM IS DEFINED IN |
| CHAPTER 2: SPECIAL AMUSEMENT BUILDING. |
| |
| 2) [F]411.3 AUTOMATIC FIRE DETECTION. |
| SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED WITH AN |
| AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH |
| SECTION 907. |
| |
| 3) [F]411.4 AUTOMATIC SPRINKLER SYSTEM. |
| SPECIAL AMUSEMENT BUILDINGS SHALL BE EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1. WHERE THE SPECIAL |
| AMUSEMENT BUILDING IS TEMPORARY, THE SPRINKLER WATER |
| SUPPLY SHALL BE OF AN APPROVED TEMPORARY MEANS. |
| EXCEPTION: AUTOMATIC SPRINKLERS ARE NOT REQUIRED WHERE |
| THE TOTAL FLOOR AREA OF A TEMPORARY SPECIAL AMUSEMENT |
| BUILDING IS LESS THAN 1,000 SQUARE FEET (93 M2) AND THE |
| EXIT ACCESS TRAVEL DISTANCE FROM ANY POINT TO AN EXIT |
| IS LESS THAN 50 FEET (15 240 MM). |
| |
| 4) [F]411.5 ALARM. |
| ACTUATION OF A SINGLE SMOKE DETECTOR, THE AUTOMATIC |
| SPRINKLER SYSTEM OR OTHER AUTOMATIC FIRE DETECTION |
| DEVICE SHALL IMMEDIATELY SOUND AN ALARM AT THE BUILDING |
| AT A CONSTANTLY ATTENDED LOCATION FROM WHICH EMERGENCY |
| ACTION CAN BE INITIATED INCLUDING THE CAPABILITY OF |
| MANUAL INITIATION OF REQUIREMENTS IN SECTION |
| 907.2.12.2. |
| |
| 5) [F]411.6 EMERGENCY VOICE/ALARM COMMUNICATIONS |
| SYSTEM. |
| AN EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTIONS 907.2.12 AND |
| 907.5.2.2, WHICH IS ALSO PERMITTED TO SERVE AS A PUBLIC |
| ADDRESS SYSTEM AND SHALL BE AUDIBLE THROUGHOUT THE |
| ENTIRE SPECIAL AMUSEMENT BUILDING. |
| |
| 6) 411.7 EXIT MARKING. |
| EXIT SIGNS SHALL BE INSTALLED AT THE REQUIRED EXIT OR |
| EXIT ACCESS DOORWAYS OF AMUSEMENT BUILDINGS IN |
| ACCORDANCE WITH THIS SECTION AND SECTION 1013. APPROVED |
| DIRECTIONAL EXIT MARKINGS SHALL ALSO BE PROVIDED. WHERE |
| MIRRORS, MAZES OR OTHER DESIGNS ARE UTILIZED THAT |
| DISGUISE THE PATH OF EGRESS TRAVEL SUCH THAT THEY ARE |
| NOT APPARENT, APPROVED AND LISTED LOW-LEVEL EXIT SIGNS |
| THAT COMPLY WITH SECTION 1013.5, AND DIRECTIONAL PATH |
| MARKINGS LISTED IN ACCORDANCE WITH UL 1994, SHALL BE |
| PROVIDED AND LOCATED NOT MORE THAN 8 INCHES (203 MM) |
| ABOVE THE WALKING SURFACE AND ON OR NEAR THE PATH OF |
| EGRESS TRAVEL. SUCH MARKINGS SHALL BECOME VISIBLE IN AN |
| EMERGENCY. THE DIRECTIONAL EXIT MARKING SHALL BE |
| ACTIVATED BY THE AUTOMATIC FIRE DETECTION SYSTEM AND |
| THE AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION 907.2.12.2. |
| |
| 7) 411.7.1 PHOTOLUMINESCENT EXIT SIGNS. |
| WHERE PHOTOLUMINESCENT EXIT SIGNS ARE INSTALLED, |
| ACTIVATING LIGHT SOURCE AND VIEWING DISTANCE SHALL BE |
| IN ACCORDANCE WITH THE LISTING AND MARKINGS OF THE |
| SIGNS. |
| |
| 8) 411.8 INTERIOR FINISH. THE INTERIOR FINISH SHALL BE |
| CLASS A IN ACCORDANCE WITH SECTION 803.1. |
| |
| IN ADDITION TO THE ABOVE REQUIREMENTS PLEASE PROVIDE |
| THE FOLLOWING INFORMATION. |
| |
| 9) COMPLIED. SPECIFY THE SIZE OF THE AREA THAT WILL BE |
| USED FOR THE HAUNTED HOUSE. |
| |
| 10) COMPLIED. THE LOCATIONS AND NUMBER OF EXITS. |
| SPECIFY THE CLEAR OPENING SIZES OF EACH OF THEM. |
| |
| 11) MORE INFORMATION IS REQUIRED. (SPECIFY THE NUMBER, |
| SIZE, LENGTH AND TYPE OF FASTENERS THAT WILL BE USED TO |
| ATTACH THE PLYWOOD TO THE 2X4S AND TO ATTACH THE 2X4S |
| TO THE CEILING JOISTS/RAFTERS.) PROVIDE |
| DETAILS/DRAWINGS SHOWING HOW THE PLYWOOD WITH WOOD BEAM |
| SUPPORTS WILL BE CONSTRUCTED AND ATTACHED TO THE |
| STRUCTURE. |
| |
| 12) MORE INFORMATION IS REQUIRED. (CONFIRM THAT THE |
| ENTRANCE AND ROUTE THROUGH THE ATTRACTION IS STABLE, |
| FIRM, SLIP RESISTANT AND LEVEL, RUNNING SLOPE NOT |
| STEEPER THAN 1:20. THE CLEAR WIDTH OF WALKING SURFACES |
| SHALL BE 36 INCHES MINIMUM. WHERE THE ACCESSIBLE ROUTE |
| MAKES A 180 DEGREE TURN THE CLEAR WIDTH SHALL BE 42 |
| INCHES MINIMUM APPROACHING THE TURN, 48 INCHES MINIMUM |
| AT THE TURN AND 42 INCHES MINIMUM LEAVING THE TURN.) |
| FBC ACCESSIBILITY CHAPTER 4 REQUIRES AN ACCESSIBLE |
| ENTRANCE, ROUTE THROUGH AND EXIT FROM THE ATTRACTION. |
| |
| 13) MORE INFORMATION IS REQUIRED. (EXPLAIN HOW THE |
| CURTAIN WILL BE OPENED IN AN EMERGENCY. WILL THEY BE |
| OPENED AUTOMATICALLY BY SOME TYPE OF MOTOR OR WILL THEY |
| DEPEND ON SOMEONE TO PHYSICALLY OPEN THEM. INDICATE HOW |
| THE CURTAINS WILL BE HUNG. WILL THEY BE HUNG FROM SOME |
| TYPE OF CURTAIN ROD OR A TRACK? WILL THE EXIT SIGNS BE |
| VISIBLE OVER THE TOP OF THEM? PLEASE PROVIDE SPECIFIC |
| DETAILS.) HOW PROVIDE DETAILS/DRAWINGS TO SHOW HOW THE |
| FIREPROOF CURTAINS WILL BE HUNG AND HOW THEY WILL BE |
| OPENED IN AN EMERGENCY. |
| |
| 14) COMPLIED. INDICATE THE LOCATIONS OF THE BATHROOMS |
| FOR STAFF. |
| |
| 15) MORE INFORMATION IS REQUIRED. (THE DRAWINGS SHOW |
| THE EXIT SIGNS ON THE WRONG SIDE OF THE WALL BETWEEN |
| THE NORTH AND SOUTH ROOMS. CLARIFY HOW THE SIGNS WILL |
| REMAIN VISIBLE WHEN THE CURTAINS, WOOD PANELS AND |
| DECORATIONS ARE IN PLACE.) THE EXIT SIGNS NEED TO BE |
| VISIBLE AND CAN NOT BE BLOCKED FROM VIEW. |
| |
| 16) NOT SPECIFIED ON DRAWINGS. (SHOW THE LOCATIONS OF |
| EMERGENCY LIGHTS ON THE DRAWINGS.) EMERGENCY LIGHTING |
| WITH BATTERY BACKUP SHALL BE PROVIDED IN ALL ROOMS, |
| AREAS AND EXIT PATHWAYS. |
| |
| 17) MORE INFORMATION IS REQUIRED. (SUBMIT THE |
| MANUFACTURER'S FIREPROOFING INFORMATION/TEST REPORTS |
| FOR THE CURTAINS, FABRICS, DECORATIONS AND |
| FURNISHINGS.) ALL FURNISHINGS AND DECORATIONS |
| (INCLUDING ALL DRAPERIES AND CURTAINS) ARE REQUIRED TO |
| BE FLAME RESISTANT. |
| |
| 18) COMPLIED. SHOW THE LOCATION OF ELECTRICAL PANELS |
| AND LIGHTING CONTROLS. |
| |
| 19) MORE INFORMATION IS REQUIRED. (PROVIDE THE |
| EXPERIENCE AND TRAINING OF THE TWO SECURITY GUARDS THAT |
| WILL BE EMPLOYED. SPECIFY WHO WILL BE RESPONSIBLE FOR |
| EDUCATING THE ACTORS ON EMERGENCY PROCEDURES. SPECIFY |
| HOW THE "LIGHT EFFECTS" WILL BE TURNED OFF AND WHO WILL |
| DO SO. ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR |
| MULTIPLY SWITCHES IN THE SAME LOCATION? SPECIFY HOW THE |
| EXISTING BUILDING LIGHTS WILL BE TURNED ON AND BY WHOM. |
| ARE THEY ALL CONNECTED TO A SINGLE SWITCH OR MULTIPLY |
| SWITCHES IN THE SAME LOCATION? HOW MANY MEGAPHONES WILL |
| BE PROVIDED AND WHO WILL HAVE THEM? WHAT IS A BLOW HORN |
| AND HOW WILL IT BE USED TO NOTIFY PEOPLE OF AN |
| EMERGENCY SITUATION?) SUBMIT A WRITTEN EMERGENCY |
| PROCEDURE PLAN. |
| |
| 20) FBC 107.2.1 - INFORMATION ON CONSTRUCTION |
| DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |