2019-10-24 11:03:30 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW THE LAVATORY AND KITCHENETTE SINK ON FLOOR |
| PLAN. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHOW THE DIMENSIONS OF THE BATHROOM TO DETERMINE |
| CODE COMPLIANCE OF FBC RES P2705.1(5) |
| |
| 3. THE SANITARY ISOMETRIC HAS A CODE VIOLATION NOT MORE |
| THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE |
| UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.THE |
| LAVATORY FIXTURE DRAIN SHALL CONNECT BETWEEN THE WATER |
| CLOSET AND THE SHOWER. PER FBC RES P3108.2.1 |
| |
| 4. PLEASE CLARIFY ON THE PLAN NOTE STATES ROUGH IN |
| ONLY, IS IT FOR UNDERGROUND PIPING OR WILL THE WATER |
| AND SANITARY BE INSTALLED IN THE WALLS ALSO. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |