Plan Review Notes
Plan Review Notes For Permit 19100975
Permit Number 19100975
Review Stop R
Sequence Number 1
Notes
Date Text
2019-11-25 09:09:262017 FBC- ROOFING PLAN REVIEW
 W. P. B. PERMIT: 19100975
 ADD: 4400 TBD/ TO BE DETERMINED
 TEL: ????
 E-MAIL: [email protected]
 CONTACT: EDNA BONELLI
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 25/ 2019
 ACTION: DENIED
  
 1) SHEET S1.03 PROVIDES THE WALL PRESSURES FOR WALL
 ZONES 4 & 5 BUT THE PLAN DOES NOT PROVIDE THE ROOF
 PRESSURES FOR ZONES 1,2, &3 FOR A FLAT ROOF NOR A
 HIPPED ROOF, THE PLAN IS ALSO MISSING THE ROOF PITCH/
 SLOPE. PLEASE PROVIDE THIS INFORMATION FOR CODE
 COMPLIANCE CAN BE DETERMINED.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 2) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
 (C) PANEL WALLS, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 3A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 4A) FLAT ROOFING: : FOR ALL ROOFING PRODUCTS PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4B) SLOPED ROOF TILE: PLEASE SUBMIT THE PRODUCT
 APPROVAL FOR THE TYPE OF UNDERLAYMENT, ROOF TILE,
 INDICATE THE TYPE OF TILE, SLOPE, FASTENER METHOD, IF
 FOAM ADHESIVE THE PRODUCT APPROVAL FOR THE FOAM AND
 ASSOCIATED PRESSURES. IF THE TILE IS TO BE NAILED AND
 OR SCREWED IN PLACE INDICATE THE FASTENING METHOD AND
 THE MOMENT OF UPLIFT. PLEASE SHOW COMPLIANCE WITH THE
 2017 FBC-B 1609.5.3. RIGID TILE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  