2019-10-28 10:48:56 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) VALUE OF WORK SHOWN IS LOW |
| |
| 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL |
| |
| 2) NEED SIZES OF THE CONDUCTORS IN RISER TO THE WEATHER |
| HEAD 215.5 |
| |
| 3) NOT SURE YOU HAVE A NEUTRAL CONDUCTOE TO THE MAIN |
| AND OR TRANSFER SWITCH IF THE #1 IS THE NEUTRAL IT IS |
| TO SMALL |
| |
| NEUTRAL CAN NOT BE SMALL THAN THE REQUIRED GROUNDING |
| ELECTRODE CONDUCTOR. 250.66 |
| |
| 4) NEED A CUT SHEET DETAIL SHOWING THE HEIGHT, WIDTH, |
| AND DEPTH OF SWITCH GEAR IN NEW ROOM LOOKING AT WORKING |
| CLEARANCES 110.26 |
| |
| 5) FLOOR PLAN ON PAGE E-2 SHOWS A SEPARATE |
| TRANSFORMER???? NOT SHOWN ON RISER DETAIL. |
| |
| 6) PAGE E-4 NEUTRAL NOT SHAN AS BONDED TO THE GE SYSTEM |