2019-11-16 15:09:4511/16/2019 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE THE ADDRESS IS CUT OFF AND THE HOLE PHYSICAL
 ADDRESS OF THE RESIDENCE MUST BE ON PLANS IN FULL,
 NUMBER, STREET, CITY, STATE AND ZIP CODE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. SECOND REQUEST SUBMIT TWO COPIES OF THE SIZING TABLE
 USED IN THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE
 ON BOTH SETS OF PLANS LISTING THE SIZING TABLES FROM
 GAS CODES OR ANOTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS SYSTEM PER THE 2017 FBC RES. SEC.
 G2413.3
 3. WHAT IS THE DEVELOP LENGTH SHOW THE DISTANCE FROM
 THE POINT OF DELIVERY, (GAS METER) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 FBC
 RES. SECS. G2413.4.1, G2413.4.2.
  
 PLEASE REMOVE OLD ISOMETRIC FROM PACKAGE AND MARK VOID
 OLD ISOMETRIC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  