2019-10-31 16:15:22 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19100910 |
| REVIEWED: OCTOBER 31, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR |
| WORK BEING PERFORMED. |
| - PLEASE CHANGE LEVEL OF ALTERATION TO LEVEL 3 SINCE |
| THE WORK AREA CONSISTS OF MORE THAN 50% OF THE BUILDING |
| AREA. |
| |
| 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS AND DOORS. |
| |
| 3) 703.7.3 FBC[R]WATER-RESISTIVE BARRIERS. |
| WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| -15# FELT CAN ACT AS WATER BARRIER AND PAPER BACKED |
| LATHE CAN SERVE AS TYPE D LAYER OVER TOP TO ALLOW |
| MOISTURE TO ESCAPE FROM BETWEEN THE 2 LAYERS. |
| -ADJUST NOTE ON A3 TO SHOW HOW REQUIREMENTS IN R703.7.3 |
| WILL BE MET. |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |