2019-10-21 14:04:15 | 10/21/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS |
| INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED. |
| NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE |
| REQUIREMENTS OF UL 2200. |
| |
| 2. PLEASE CLARIFY IF CABLE IS PROTECTED FOR THE LP TANK |
| AND APPURTENANCES AND WHAT ARE YOU GOING TO USE TO DO |
| SO PER NFPA 58. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE. |
| COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| |
| 4. FOR CATHODIC PROTECTION PLEASE SHOW SIZE (LBS.) & A |
| NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE, |
| HOW IS IT GOING TO BE ACTIVATED (EXAMPLE WATER) PER |
| NFPA 58 SEC. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| MONITORED PER NFPA 58 SEC.6.6.6.1 (J). |
| |
| 5. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017 |
| FBC FG SEC 410.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |