2019-10-28 13:32:45BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19100813
 REVIEWED: OCTOBER 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
  
 1) 107.5.3 FBC[AMENDED]PLEASE SHOW THE GENERATOR WITH
 ENCLOSURE IMPOSED ON A FLOOR PLAN TO SHOW HOW EGRESS
 WILL WORK. THE ENCLOSURE SHOWN ON THE GENERATOR
 SUBMITTAL IN PERMIT 19100815 SHOWS DIMENSIONS OF 10
 FEET WIDE BY 28 FOOT 4 INCHES LONG. THE SUBMITTAL ALSO
 SHOWS THE ACCESS DOORS ARE 4 FOOT OUTSWING.
 SHEET C-400 APPEARS TO SHOW OUTLNE WITH 3 FEET AROUND
 THE UNIT FOR ACCESS.
 IS THE INTENTION TO HAVE ACCESS DOORS SWING ALL THE WAY
 OPEN?
 PLEASE VERIFY THE SIZE OF ACCESS DOORS AND IF THEY WILL
 BE OBSTRUCTED FROM FULL OPEN BY THE MASONRY WALL.
  
 2) 107.2.1.1 FBC[AMENDED]PROVIDE PRODUCT APPROVAL FOR
 THE ROLLING DOOR ATTACHED TO WALL THAT IS BEING USED
 FOR ACCESS TO THE GENERATOR.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  