2019-10-21 14:55:32NFPA 1.14.4: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE APPLICANT OF THE RESPONSIBILITY OF
 COMPLIANCE WITH THIS CODE.
  
 NFPA 72-7.4.4.1: WHERE AUDIBLE APPLIANCES ARE INSTALLED
 TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE
 A SOUND LEVEL OF LEAST 15 DB ABOVE THE AVERAGE AMBIENT
 SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL
 HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND
 LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
 MEASURED AT THE PILLOW LEVEL IN AREA REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE(DBA).
  