Plan Review Notes For Permit 19100800 |
Permit Number |
19100800 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-21 14:55:32 | NFPA 1.14.4: REVIEW AND APPROVAL BY THE AHJ SHALL NOT | | RELIEVE THE APPLICANT OF THE RESPONSIBILITY OF | | COMPLIANCE WITH THIS CODE. | | | | NFPA 72-7.4.4.1: WHERE AUDIBLE APPLIANCES ARE INSTALLED | | TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE | | A SOUND LEVEL OF LEAST 15 DB ABOVE THE AVERAGE AMBIENT | | SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL | | HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND | | LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER, | | MEASURED AT THE PILLOW LEVEL IN AREA REQUIRED TO BE | | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE(DBA). | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | WEST PALM BEACH FIRE PREVENTION BUREAU | | 500 N. DIXIE HWY | | WEST PALM BEACH, FLORIDA 33401 | | [email protected] |
|