Plan Review Notes
Plan Review Notes For Permit 19100754
Permit Number 19100754
Review Stop B
Sequence Number 1
Notes
Date Text
2019-11-04 10:16:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19100754
 ADD: 801 S. OLIVE AVE. SUITE: 1105
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-588-5070
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 04TH/ 2019
 ACTION: DENIED
  
 1) SHEET A-1 THE COVERSHEET:
 1A) THE COVERSHEET LIST THE BUILDING TYPE AS
 CONSTRUCTION TYPE II SPRINKLERED. THIS HIGHRISE IS A 15
 STORY BUILDING. THE CONSTRUCTION TYPE UNDER THE 2017
 FBC-B TABLE 504.4 IS CONSTRUCTION TYPE I-A. PLEASE
 CORRECT.
  
 1B) THE COVERSHEET LIST THE OCCUPANCY TYPE AS R-3. A
 R-3 OCCUPANCY IN THE 2017 FBC-B WOULD BE A MIXED USE
 BUILDING, FOR EXAMPLE, MERCANTILE 1ST FLOOR, AND A
 SINGLE RESIDENTIAL UNIT ON THE 2ND FLOOR, THIS WHERE A
 R-3 OCCUPANCY COULD OCCUR UNDER THE COMMERCIAL CODE.
 APARTMENT BUILDINGS WITH NON-TRANSIENT OCCUPANTS AND
 CONDOMINIUM BUILDINGS WITH LONG TERM NON-TRANSIENT
 RESIDENTS ARE CONSIDERED AN R-2 OCCUPANCY. SEE 2017
 FBC-B SECTION 310.4.
  
 1C) IN THE COVERSHEET/ DEMOLITION PLAN INDICATES TO
 DEMOLISH THE ENTIRE MASTER BATH. IF THIS IS SO, THEN
 COMPLIANCE WITH FLOOR INSULATION WILL BE REQUIRED.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH:
  
 1C)(1) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1C)(2) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C)(3) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) SHEET A-2:
 2A) SHEET A-2 HAS A DETAIL B TYPICAL SOFFIT WITH A NOTE
 TO USE TAPCONS ? INCH DIAMETER, AND A MAXIMUM EMBEDMENT
 OF ? INCH. IN GOING TO THE TAPCON TECHNICAL
 SPECIFICATIONS FOR TAPCON CONCRETE SCREWS THE MINIMUM
 TAPCON SIZE SHOWN ON THE CHARTS IS 1 ? INCH IN LENGTH.
 THE MINIMUM EMBEDMENT LENGTH IS 1 INCH. WITH THIS
 KNOWLEDGE YOU WILL NEED NOTE SO ON THE PLANS TO HAVE
 THE SLAB X-RAYED BEFORE DRILLING FOR TAPCONS TO LOCATE
 THE EXISTING POST-TENSION TENDONS EMBEDDED WITHIN THE
 SLAB. PLEASE ALSO UPDATE THE PLANS AS TO THE MINIMUM
 LENGTH OF THE TAPCON. SHOW COMPLIANCE WITH FBC-B
 1703.6.2.
  
 2B) THE FLOOR PLAN OF THE MASTER BATHROOM AND SHOWER
 SHOWS A NICHE IN THE 1 HOUR RATED CORRIDOR WALL COMMON
 TO THE SHOWER. THERE IS ALSO A NOTE THAT 5/8 INCH TYPE
 X DRYWALL ARE TO BE ATTACHED TO ALL SIDES OF THE NICHE.
 PLEASE NOTE THERE IS ANOTHER CONCERN NOT ONLY THE FIRE
 RATING BUT ALSO THE REQUIREMENTS FOUND IN SECTION
 2509.2 BASE FOR TILE.
  
 2017 FBC-B2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND
 CEILING PANELS IN SHOWER AREAS SHALL BE OF MATERIALS
 LISTED IN TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER?S RECOMMENDATIONS. WATER-RESISTANT
 GYPSUM BACKING BOARD SHALL BE USED AS A BASE FOR TILE
 IN WATER CLOSET COMPARTMENT WALLS WHEN INSTALLED IN
 ACCORDANCE WITH GA-216 OR ASTM C840 AND THE
 MANUFACTURER?S RECOMMENDATIONS. REGULAR GYPSUM
 WALLBOARD IS PERMITTED UNDER TILE OR WALL PANELS IN
 OTHER WALL AND CEILING AREAS WHEN INSTALLED IN
 ACCORDANCE WITH GA-216 OR ASTM C840.
  
 TABLE 2509.2
 BACKERBOARD MATERIALS
  
 MATERIAL_______________________________________
 STANDARD
 GLASS MAT GYPSUM BACKING PANEL ____________________ASTM
 C1178
 NONASBESTOS FIBER-CEMENT BACKER BOARD__________ ASTM
 C1288 OR ISO 8336,
 _______________________________________________CATEGORY
 C
  
 NONASBESTOS FIBER-MAT REINFORCED ___________________
 ASTM C1325
 CEMENTITIOUS BACKER UNIT
  
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1.OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2.WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 2C) WITHIN THE MASTER BATHROOM THE PLANS ALSO INDICATE
 THE USE OF TRANSLUCENT BYPASS DOOR ENCLOSURE TO THE
 WATER CLOSET ROOM. THE USE OF GLASS PRODUCTS IN THIS
 APPLICATION IS CONSIDERED A HAZARDOUS LOCATION SEE THE
 2017 FBC-B SECTION 2406.4.1.
 2406.2 IMPACT TEST. WHERE REQUIRED BY OTHER SECTIONS OF
 THIS CODE, GLAZING SHALL BE TESTED IN ACCORDANCE WITH
 CPSC 16 CFR PART 1201. GLAZING SHALL COMPLY WITH THE
 TEST CRITERIA FOR CATEGORY II, UNLESS OTHERWISE
 INDICATED IN TABLE 2406.2(1).
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved