Plan Review Notes For Permit 19100709 |
Permit Number |
19100709 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-12-19 13:00:05 | GAS PROVISO: PROVIDE PRIOR TO ROUGH INSPECTION PROVIDE | | HARD COPY OF GAS PLAN FOR PERMIT ISSUANCE | | | | 1. PROVIDE EXITING BTU LOAD FOR ALL GAS APPLIANCES. WPB | | AMEND TO FBC 107.2.1 | | | | 2. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM FOR EXISTING .5LB AND 2LB SYSTEM PER THE | | FBC-2017 FUEL GAS APPENDIX A ? USE OF CAPACITY SECTION | | A.3.1(4) & 2017 FUEL GAS CODE SEC. 402.4.1. | | | | 3. SHOW SIZE OF EXISTING .5LB SYSTEM PIPING. WPB AMEND | | TO FBC 107.2.1 | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND | | INSTILLATION GUIDES FOR ALL NEW GAS EQUIPMENT AND | | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | NFPA 58, AND FBC-2017 FUEL GAS SEC. 402.2 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|