Plan Review Notes
Plan Review Notes For Permit 19100704
Permit Number 19100704
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-21 16:06:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN TABLE "A" ON PAGE 9 OF PRODUCT APPROVAL FL
 11422.7 R5 FOR THE METAL ROOFING, ATTACHMENT METHOD 1
 FOR -134.75 PSF IS MARKED AND METHOD 2 FOR -206 PSF IS
 REQUIRED. ON SHEET S011 OF THE APPROVED PLANS THE
 COMPONENT AND CLADDING TABLE FOR THE SLOPED AREA HAS
 -181 PSF FOR THE EFFECTIVE WIND AREA OF 9 SQFT OR LESS
 IN ZONE A.