Plan Review Notes For Permit 19100637 |
Permit Number |
19100637 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-15 12:12:36 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | 805-6724 | | [email protected] | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF | | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN | | HEADING ?ANCHOR SPACING?; PROVIDE INFORMATION FROM PAGE | | FROM PAGES 11-17 OF FL5790-R12. EXAMPLE: 5/16? ELCO | | ULTRACON; CONC. & FILLED CMU; MAXIMUM (PSF) 78/79; 4? | | BUILD-OUTS/3? BUILD-INS; SLAT SPAN 96? ANCHOR SPACING | | IS 4?. | | |
|