2019-10-29 14:46:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19100568 |
| 10/29/19 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PREVIOUSLY NONCONDITIONED RESIDENCE NOW BEING |
| CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH |
| THE FBC-17 ENERGY CONSERVATION CODE- SECTION R503.2 FBC |
| EC. SUBMIT AN ENERGY COMPLIANCE FORM IN ACCORDANCE WITH |
| SECTION R101.5 FBC EC. |
| |
| 2) SUBMIT ACCA MANUAL J COOLING AND HEATING |
| CALCULATIONS FOR THE NEW AC SYSTEM- SECTION R403.6.1 |
| FBC EC. |
| |
| 3) SHEET M-1: REQUIRED RETURN AIR FROM BEDROOMS NOT |
| SHOWN ON THE PLAN- M1602.3 FBC RES. |
| |
| 4) M-1: IT APPEARS THAT THE REQUIRED 30X30 ACCESS SPACE |
| IN FRONT OF THE WATER HEATER WILL BE BLOCKED BY THE |
| DRYER- SECTION M1305.1 FBC RES. |
| |
| 5) M-1: INDICATE THE CLEAR OPENING DIMENSIONS OF THE |
| AIR HANDLER ATTIC ACCESS PANEL, AND VERIFY IT IS SIZED |
| LARGE ENOUGH TO ALLOW REMOVAL OF THE APPLIANCE- SECTION |
| M1305.1.3 FBC RES. |
| |
| 6) M-1: EXHAUST VENTILATION AT A RATE OF 100 CFMS |
| INTERMITTENT OR 25 CFMS CONTINUOUS SHALL BE PROVIDED |
| FOR THE KITCHEN- TABLE M1507.4 FBC RES. PLEASE SEE |
| SECTION M1503.1 FOR RANGE HOOD REQUIREMENTS, AND |
| M1503.4 FOR MAKEUP AIR. |
| |
| 7) M-1: VERIFY COMPLIANCE WITH SECTION R403.3.6 FBC EC |
| AIR-HANDLING UNITS IN ATTICS: |
| |
| AIR-HANDLING UNITS SHALL NOT BE INSTALLED IN THE ATTIC |
| WHEN A HOME IS BROUGHT INTO CODE COMPLIANCE BY SECTION |
| R402. AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS FOR |
| COMPLIANCE BY SECTION R405 ONLY IF THE FOLLOWING |
| CONDITIONS ARE MET: |
| |
| 1.THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| |
| 2.A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT DOWN |
| THE UNIT WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| |
| 3.THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER. |
| |
| 4.A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |
| NOTICE TO HOMEOWNER |
| A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR |
| HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| AND ECONOMIC OPERATION OF THE AIRCONDITIONING SYSTEM, |
| YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR |
| BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU |
| WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR |
| (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE |
| CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| PEAK OPERATION. |
| |
| 8) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN SHOWING THE |
| PIPING RUN AND DISHARGE LOCATION, AND THE TYPE AND SIZE |
| OF PIPE- SECTION M1411.3 FBC RES. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |